Page 44

Section 3-4

Cable Connection

5. Align the cable’s Optical Connectors so that the tabs are on the left and insert them into the Unit’s Optical Connectors.

Nut Terminal Mounting bracket (1) (5)

(1)

(2)

(3) Tension wires

(4)

Note Tighten the screws on the mounting bracket firmly. C200HW-SLK13/14

1, 2, 3...

1. Insert the terminals into the mounting bracket so that the tension wire holes are vertical, and then secure the terminals by tightening the nuts on the other side. 2. Secure the bracket to the Unit with the Philips head screws provided. 3. If the cable has tension wires, thread them through the terminals. 4. Insert the cable’s Optical Connectors into the Unit’s Optical Connectors. 5. Place the cables behind the clamp and secure them by tightening the Philips head screw provided. Secure both cables at once.

30

Page 45

Section 3-4

Cable Connection

6. If the cable has tension wires, tighten the terminal screws to secure them. Nut Terminal Mounting bracket (1)

(2)

(1)

(3)

(4) (6) Tension wires

(5)

Note Tighten the screws on the mounting bracket firmly.

Precautions 1, 2, 3...

1. Use only the Hard Plastic-clad Optical Fiber Cable (H-PCF) listed in Appendix A Standard Models. 2. Any bends in the cable must be 10 cm in radius or greater. 3. Always hold the connector firmly when inserting or removing the cables.

31

Page 46

Section 3-4

Cable Connection

4. As shown in the diagram below, begin connecting the highest node of the network and connect the lower nodes in order. Cover the upper connector (SL1) of the highest node, and connect SL2 to SL1 of the next node. Continue connecting this way until the lowest node is reached and cover SL2 of the lowest node. Higher nodes

Lower nodes

Optical Connector Cover

Optical Connector Cover C1000H-SLK11

C1000H-SLK11

C200HW-SLK13/14

5. Allow sufficient clearance between the bottom of the Unit and the cable to prevent the cable from being bent too much, as shown in the diagram below. (The clearances are in millimeters.) C1000H-SLK11

60

55 200

32

C200HW-SLK13/14

200

Page 47

Section 3-5

Dimensions

3-5

Dimensions Dimensions for the SYSMAC LINK Units are shown below. All dimensions are in millimeters.

C1000H-SLK11

34.5

93

SLK11 RUN ERC

P/S ERH

INS

M/S

SD

RD

TS

LNK

250

105

C200HW-SLK13/14

34.5

125

SLK14

130

P/S ERH M/S TS RD LNK

C200HS–SLK14

RUN ERC INS SD

33

Page 48

Section 3-5

Dimensions C1000H-SLK21-V1

34.5

93

SLK21-V1 RUN ERC

ERH

INS

M/S

SD

RD

TS

LNK

250

109

C200HW-SLK23/24

34.5

125

C200H-TL001 F Adapter Attachment Stirrup

SLK24

130

ERH M/S TS LNK RD

54

C200HS–SLK24

RUN ERC INS SD

8.25

34

Page 49

SECTION 4 Basic Communications A description of the token bus method of communications used in SYSMAC LINK Systems is described briefly in this section. The basic settings necessary for operation are also explained. 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8

SYSMAC LINK System Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Node Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PC Mode at Start-up (C1000H only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Polling Unit Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Network Parameter Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Active Node Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

36 37 38 38 39 40 41 42

35

Page 50

Section 4-1

SYSMAC LINK System Communications

4-1

SYSMAC LINK System Communications SYSMAC LINK Units communicate through the SYSMAC LINK Network, a token bus LAN. This section describes the token bus communications used in the SYSMAC LINK Network.

Token Bus Communications In token bus communications, individual nodes are connected to a main trunk line as a common bus line, as shown in the figure below. To avoid having two nodes attempt to transmit simultaneously, only one node has the right to transmit at a time. The Unit with that right is called the polling unit. The polling unit is identified by a token that is passed in sequence from the node to node, beginning with the node with the lowest node number. If the token is passed to a node that doesn’t have data to transmit, the token is immediately passed to the node with the next higher node number. The node with the highest node number passes the token back to the node with the lowest node number. In this way, each node in the network has its turn to transmit data without interfering with other nodes. Lowest node number Node

Node

Node

Node

Connecting cable (trunk line) Node

Node

Node

Highest node number

Polling Unit In a SYSMAC LINK Network there is one node, called the polling unit, that controls communications in the network. Normally, the Unit with the lowest node number is the polling unit. If the polling unit happens to fail, the node with the next higher node number becomes the polling unit, preventing the whole network from failing.

Start-up Node The node that starts the data link in a SYSMAC LINK Network is called the start-up node. The data link operates using the settings in the memory area of the PC at the start-up node. With automatic allocation of link words the settings in AR 07 are used, and with manual allocation the common link parameters in the start-up node are used. The start-up node controls not only data link table generation, but is used to start and stop data link operation. Be sure to designate a Unit or Units participating in the data link as the start-up node(s) to enable this control.

Communications Cycle The token in a SYSMAC LINK Network is first sent out from the polling unit. The token is then is passed in sequence from the node to node by node number until it is finally returned to the polling unit. One complete circuit around the network is known as a token cycle. At the end of each token cycle, the polling unit polls all of the nodes in the network to check whether any nodes have been added to or removed from the network. The updated information on the network is transmitted to all nodes. This polling and updating process is known as the polling cycle.

36

Page 51

Section 4-2

Setting Node Numbers

When the control cycle is completed, the polling unit once again sends out the token, beginning the next token cycle. Together the token cycle and control cycle make up the communications cycle, and the time required for the communications cycle is known as the communications cycle time. Communications cycle

Communications cycle

Token cycle

Token cycle

Polling cycle

Polling cycle

Network Parameters The communications cycle time is one of the network parameters. The other network parameters are the number of polled units, maximum number of frames, and the maximum node number. These parameters are transmitted from the polling unit to the other nodes in the network. Refer to 4-6 Setting Network Parameters for details on the network parameters.

Refresh Cycle Time Data is refreshed between the SYSMAC LINK Unit and the PC’s CPU Unit while a data link is active. The PC passes the data for the local words to the SYSMAC LINK Unit and receives the words written by other nodes from the SYSMAC LINK Unit. The time required to refresh the data is called the refresh cycle time. The refresh cycle time can be monitored from Peripheral Devices.

4-2

Setting Node Numbers In token bus communications used in the SYSMAC LINK Network, the node numbers make a logical ring that the token is passed around. The logical ring of node numbers takes the place of the actual physical ring used in some other networks. Consequently, proper setting of the node numbers is essential to network operations. Node number switches determine the node number. The left switch sets the tens digit; the right switch sets the ones digit. The node number must be in the range from 01 through 62. Each SYSMAC LINK Unit in a Network must have a unique node number. Note Always turn the PC’s power off before setting a Unit’s node number. Use a small flat-blade screwdriver to set node number switches, being careful not to damage them. The following example shows the node number set to 50. NODE No.

x101

Note x100

1. If the node number set on the Unit is outside of the allowed range (01 to 62), a communications error will occur and the red ERC indicator will light on the Unit’s display. 2. Each Unit in the network must have a unique node number, so be sure not to use the same number in more than one Unit.

37

Page 52

Section 4-4

PC Mode at Start-up (C1000H only)

3. The token is passed from node to node according to node numbers, so the more dispersed the node numbers are, the greater distance the token has to travel. In optical fiber systems, the communications cycle time depends on the distance the token has to travel, so set node numbers according to the nodes positions in the network if possible. 4. When a node number has been changed, activate that node last.

4-3

Operating Levels Up to 2 Link Units can be mounted on a C-series PC at one time. Link Units include SYSMAC LINK Units, SYSMAC NET Link Units, Host Link Units, and PC Card Unit (C200HX/HG/HE CPU Units only). For details refer to 1-4-2 Compatibility with other Link Units. When two Link Units are mounted on one PC, it is necessary to differentiate between the two Networks to which the PC belongs. Units in one Network are assigned to operating level 0; Units in the other Network are assigned to operating level 1. These operating levels only distinguish between the two Networks and do not imply that one Network is operating above or below the other in any functional sense.

Setting Operating Levels

The operating level of all SYSMAC LINK Units (C1000H-SLK11/SLK21-V1 and C200HW-SLK13/14/23/24) is set with pin 3 of DIP switch 1, as shown below. DIP switch 1, pin 3

Note

4-4

Operating level

ON (1)

Operating level 0

OFF (0)

Operating level 1

1. Always turn the PC’s power off before setting a Unit’s operating level. 2. When mounting a SYSMAC LINK Unit on the same PC with a SYSMAC NET Link Unit, Host Link Unit (Rack-mounting type), or PC Card Unit, be sure they are set to different operating levels.

PC Mode at Start-up (C1000H only) This setting is available on the C1000H-SLK11 and C1000H-SLK21-V1 only. The PC mode at start-up can be set to MONITOR if it is not being controlled from the Programming Console of other Peripheral Device that might be connected to the PC.

Setting PC Mode at Start-up

The PC mode at start-up is set with pin 5 of DIP switch 1, as shown in the table below. Pin 5 ON (1)

Other unit connected None1

---

PC mode at start-up MONITOR

Programming Console

RUN

RUN

MONITOR

MONITOR

PROGRAM

PROGRAM

Host Link Unit

DIP switch 1, pin 8: ON (1)

See note 2.

(CPU Unit-mounting type)

DIP switch 1, pin 8: OFF (0)

MONITOR

Host Link Unit

DIP switch 1, pin 8: ON (1)

MONITOR3

(Backplane-mounting type) DIP switch 1, pin 8: OFF (0)

MONITOR3

SYSMAC NET Link Unit

DIP switch 3, pin 1: ON (1)

MONITOR3

DIP switch 3, pin 1: OFF (0)

MONITOR3

DIP switch 1, pin 5: ON (1)

MONITOR3

DIP switch 1, pin 5: OFF (0)

MONITOR3

---

MONITOR

SYSMAC LINK Unit Other Peripheral Devices4

38

Setting on other unit

Page 53

Section 4-5

Polling Unit Setting Pin 5 OFF (0)

Other unit connected None1

---

PC mode at start-up RUN

Programming Console

RUN

RUN

MONITOR

MONITOR

PROGRAM

PROGRAM

Host Link Unit

DIP switch 1, pin 8: ON (1)

RUN

(CPU Unit-mounting type)

DIP switch 1, pin 8: OFF (0)

PROGRAM

Host Link Unit

DIP switch 1, pin 8: ON (1)

MONITOR3

(Backplane-mounting type) DIP switch 1, pin 8: OFF (0)

RUN3

SYSMAC NET Link Unit

DIP switch 3, pin 1: ON (1)

MONITOR3

DIP switch 3, pin 1: OFF (0)

RUN3

DIP switch 1, pin 5: ON (1)

MONITOR3

DIP switch 1, pin 5: OFF (0)

RUN3

---

PROGRAM

SYSMAC LINK Unit Other Peripheral Devices4

Note

Setting on other unit

1. None of the Link Units or Peripheral Devices listed in the table. 2. Never make this combination of pin settings. 3. When a Programming Console is also connected, the PC’s start-up mode is always controlled by the mode setting on the Programming Console. 4. Other Peripheral Devices include Floppy Disk Interface Units, Printer Interface Units, PROM Writers, and Peripheral Interface Units. 5. Always turn the PC’s power off before setting the PC mode at start-up.

4-5

Polling Unit Setting The polling unit setting is used only when replacing a SYSMAC LINK Unit and is otherwise left set to OFF. Be sure to set the data link tables if data links are being set manually and to change any network parameters in Unit before performing the following procedure.

1, 2, 3...

1. When replacing a SYSMAC LINK Unit, set the Unit as the polling unit and then initialize the Unit by pressing the reset switch or turning on the power. 2. Check the status of the Unit’s indicators to see whether the Unit has entered the network normally. The INS indicator should be ON, and the ERC and ERH indicators should be OFF. 3. If the indicators show that the Unit has entered the network normally, set the Unit as a polled Unit and initialize it again. 4. Check the status of the Unit’s indicators to see whether the Unit has entered the network normally. The INS indicator should be ON, and the ERC and ERH indicators should be OFF. If the indicators show that the Unit has entered the network normally again, it is ready to be used in the Network. If the indicators do not show the expected status, check the all switch and software settings and repeat the procedure.

C1000H Units

The polling unit is set with DIP switch 1, pin 8 on the C1000H-SLK11 and C1000H-SLK21-V1 Units, as shown below. DIP switch 1, pin 8

Polling unit operation

ON (1)

Polled unit

OFF (0)

Polling unit

39