The text of a manual · part 20 of 27
SYSMAC C20P/C28P/C40P/C60P P-type Programmable Controllers Operation Manual: SECTION 8
Pages 160 to 163 of 211, from SYSMAC C20P/C28P/C40P/C60P P-type Programmable Controllers Operation Manual
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C28P
Page 160
SECTION 8 Troubleshooting 8–1 8–2 8–3 8–4
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reading and Clearing Errors and Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
154 154 154 156
153
Page 161
Section 8–3
Error Messages
8–1
Introduction The P-type PCs provide self-diagnostic functions to identify many types of abnormal system conditions. These functions minimize downtime and enable quick, smooth error correction. This section provides information on hardware and software errors that occur during PC operation. Program input and program syntax errors are described in 7–5 Inputting, Modifying and Checking the Program. Although described in Section 3 Memory Areas, flags and other error information provided in SR areas are listed in 8–4 Error Flags. There are two indicators on the front of the CPU that provide visual indication of an abnormality in the PC. The error indicator (ERR) indicates fatal errors (i.e., ones that will stop PC operation); the alarm indicator (ALARM) indicates nonfatal ones. These indicators are shown in 2–2 Indicators. ! WARNING The PC will turn ON the error indicator (ERR), stop program execution, and turn OFF all outputs from the PC for most hardware errors, or certain fatal software errors. PC operation will continue for all other errors. It is the user’s responsibility to take adequate measures to ensure that a hazardous situation will not result from automatic system shutdown for fatal errors and to ensure that proper actions are taken for errors for which the system is not automatically shut down. System flags and other system and/or user-programmed error indications can be used to program proper actions.
8–2
Reading and Clearing Errors and Messages System error messages can be displayed on the Programming Console or any other Programming Device. On the Programming Console, press the CLR, FUN, and MONTR keys. If there are multiple error messages stored by the system, the MONTR key can be pressed again to access the next message. If the system is in PROGRAM mode, pressing the MONTR key will clear the error message, so be sure to write down all message errors as you read them out. (It is not possible to clear an error or a message while in RUN or MONITOR mode; the PC must be in PROGRAM mode.) When all messages have been cleared, “ERR CHK OK” will be displayed. Details on accessing error messages from the Programming Console are provided in 7–8 Monitoring Operation and Modifying Data. Procedures for the GPC, LSS, and FIT are provided in the relevant Operation Manual.
8–3
Error Messages There are basically two types of errors for which messages are displayed: non-fatal operating errors, and fatal operating errors. The type of error can be quickly determined from the indicators on the CPU, as described below for the two types of errors. If the status of an indicator is not mentioned, it makes no difference whether it is lit or not. After eliminating the cause of an error, clear the error message from memory before resuming operation.
Non-fatal Operating Errors
154
The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will continue after one or more of these error have occurred. The POWER, RUN, and ALARM indicators will be lit and the ERR indicator will not be lit for any of these errors. The RUN output will be ON.
Page 162
Section 8–3
Error Messages Error and message
Probable cause
Possible correction
Scan time overrun
Watchdog timer has exceeded 100 ms.
Program scan time is longer then desirable. Reduce scan time if possible.
Battery error
Backup battery is missing or it’s voltage has dropped.
Check battery and replace if necessary.
Fatal Operating Errors
The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of the following errors occur. All CPU indicators will not be lit for the power interruption error. For all other fatal operating errors, the POWER, and ERR indicators will be lit and the RUN indicator will not be lit. The RUN output will be OFF.
Error and message
Probable cause
Possible correction
Power interruption
Power has been interrupted for at least 10 ms.
Check power supply voltage and power lines. Try to power-up again.
Watchdog timer has exceeded maximum setting (default setting: 130 ms).
Restart system in PROGRAM mode and check program. Reduce scan time or reset watchdog timer if longer time required. (Consider effects of longer scan time before resetting).
Memory error
Memory Unit is incorrectly mounted or missing or parity error has occurred.
Check Memory Unit to make sure it is mounted and backed up properly. Perform a Program Check Operation to locate cause of error. If error not correctable, try inputting program again.
No END(01) instruction
END(01) is not written anywhere in program.
Write END(01) at the final address of the program.
I/O bus error
Error has occurred in the bus line between the CPU and Units.
Check the CPU Left/Right selector switch on the Expansion I/O Unit. Check cable connections between the Units and Racks.
No message
CPU error No message
155
Page 163
Section 8–4
Error Flags
8–4
Error Flags The following table lists the flags and other information provided in the SR area that can be used in troubleshooting. Details are provided in 3–4 SR Area.
SR Area
Other Error Messages
156
Address
Function
1808
Battery Alarm Flag
1809
Scan Time Error Flag
1903
Instruction Execution Error (ER) Flag
A number of other error messages are detailed within this manual. Errors in program input and debugging can be examined in Sections 7–5–2 and 7–5–3 and errors in cassette tape operation are detailed in Section 7–8.