For the Omron C28P

Page 160

SECTION 8 Troubleshooting 8–1 8–2 8–3 8–4

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reading and Clearing Errors and Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

154 154 154 156

153

Page 161

Section 8–3

Error Messages

8–1

Introduction The P-type PCs provide self-diagnostic functions to identify many types of abnormal system conditions. These functions minimize downtime and enable quick, smooth error correction. This section provides information on hardware and software errors that occur during PC operation. Program input and program syntax errors are described in 7–5 Inputting, Modifying and Checking the Program. Although described in Section 3 Memory Areas, flags and other error information provided in SR areas are listed in 8–4 Error Flags. There are two indicators on the front of the CPU that provide visual indication of an abnormality in the PC. The error indicator (ERR) indicates fatal errors (i.e., ones that will stop PC operation); the alarm indicator (ALARM) indicates nonfatal ones. These indicators are shown in 2–2 Indicators. ! WARNING The PC will turn ON the error indicator (ERR), stop program execution, and turn OFF all outputs from the PC for most hardware errors, or certain fatal software errors. PC operation will continue for all other errors. It is the user’s responsibility to take adequate measures to ensure that a hazardous situation will not result from automatic system shutdown for fatal errors and to ensure that proper actions are taken for errors for which the system is not automatically shut down. System flags and other system and/or user-programmed error indications can be used to program proper actions.

8–2

Reading and Clearing Errors and Messages System error messages can be displayed on the Programming Console or any other Programming Device. On the Programming Console, press the CLR, FUN, and MONTR keys. If there are multiple error messages stored by the system, the MONTR key can be pressed again to access the next message. If the system is in PROGRAM mode, pressing the MONTR key will clear the error message, so be sure to write down all message errors as you read them out. (It is not possible to clear an error or a message while in RUN or MONITOR mode; the PC must be in PROGRAM mode.) When all messages have been cleared, “ERR CHK OK” will be displayed. Details on accessing error messages from the Programming Console are provided in 7–8 Monitoring Operation and Modifying Data. Procedures for the GPC, LSS, and FIT are provided in the relevant Operation Manual.

8–3

Error Messages There are basically two types of errors for which messages are displayed: non-fatal operating errors, and fatal operating errors. The type of error can be quickly determined from the indicators on the CPU, as described below for the two types of errors. If the status of an indicator is not mentioned, it makes no difference whether it is lit or not. After eliminating the cause of an error, clear the error message from memory before resuming operation.

Non-fatal Operating Errors

154

The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will continue after one or more of these error have occurred. The POWER, RUN, and ALARM indicators will be lit and the ERR indicator will not be lit for any of these errors. The RUN output will be ON.

Page 162

Section 8–3

Error Messages Error and message

Probable cause

Possible correction

Scan time overrun

Watchdog timer has exceeded 100 ms.

Program scan time is longer then desirable. Reduce scan time if possible.

Battery error

Backup battery is missing or it’s voltage has dropped.

Check battery and replace if necessary.

Fatal Operating Errors

The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of the following errors occur. All CPU indicators will not be lit for the power interruption error. For all other fatal operating errors, the POWER, and ERR indicators will be lit and the RUN indicator will not be lit. The RUN output will be OFF.

Error and message

Probable cause

Possible correction

Power interruption

Power has been interrupted for at least 10 ms.

Check power supply voltage and power lines. Try to power-up again.

Watchdog timer has exceeded maximum setting (default setting: 130 ms).

Restart system in PROGRAM mode and check program. Reduce scan time or reset watchdog timer if longer time required. (Consider effects of longer scan time before resetting).

Memory error

Memory Unit is incorrectly mounted or missing or parity error has occurred.

Check Memory Unit to make sure it is mounted and backed up properly. Perform a Program Check Operation to locate cause of error. If error not correctable, try inputting program again.

No END(01) instruction

END(01) is not written anywhere in program.

Write END(01) at the final address of the program.

I/O bus error

Error has occurred in the bus line between the CPU and Units.

Check the CPU Left/Right selector switch on the Expansion I/O Unit. Check cable connections between the Units and Racks.

No message

CPU error No message

155

Page 163

Section 8–4

Error Flags

8–4

Error Flags The following table lists the flags and other information provided in the SR area that can be used in troubleshooting. Details are provided in 3–4 SR Area.

SR Area

Other Error Messages

156

Address

Function

1808

Battery Alarm Flag

1809

Scan Time Error Flag

1903

Instruction Execution Error (ER) Flag

A number of other error messages are detailed within this manual. Errors in program input and debugging can be examined in Sections 7–5–2 and 7–5–3 and errors in cassette tape operation are detailed in Section 7–8.