Page 71
Basic System Configuration and Devices
2
This section describes the basic system configuration and devices used in a CJ2 PLC. The CJ Series supports the following two types of system configuration. • Basic System Configuration: System consisting of CPU Rack and Expansion Racks. • Expanded System Configuration: System connected via CPU Unit built-in serial port and PLC Units, such as Communications Units.
2-1 Basic System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2-1-1 2-1-2 2-1-3 2-1-4 2-1-5 2-1-6
Basic System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 CPU Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Expansion Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11 Configuration Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14 Calculating Unit Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22 Calculating Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
2-2 Expanded System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27 2-2-1 2-2-2
CJ2 CPU Unit Hardware User’s Manual
Serial Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27 Communications Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
2-1
Page 72
2 Basic System Configuration and Devices
2-1
Basic System Configuration
2-1-1
Basic System Configuration z CPU Rack A CPU Rack can consist of a CJ2 CPU Unit, a CJ-series Power Supply Unit, CJ-series Configuration Units (Basic I/O Units, Special I/O Units, CPU Bus Units), and a CJ-series End Cover. The same CJseries Power Supply Units and CJ-series Configuration Units that are used with CJ1 CPU Units are used with CJ2 CPU Units.* An I/O Control Unit is required to connect a CJ-series Expansion Rack. A Memory Card is optional. * All CJ-series Units can be used as Configuration Units, but only Units that specifically support the CJ2 CPU Unit can access the expanded portions of the I/O memory areas of the CJ2 CPU Units (i.e., A960 to A1471, A10000 to A11535, and EM banks D to 18). Only the following CJ1 Units specifically support the CJ2 CPU Units. • EtherNet/IP Unit: CJ1W-EIP21 • Position Control Units: CJ1W-NC214, CJ1W-NC234, CJ1W-NC281, CJ1W-NC414, CJ1W-NC434, CJ1WNC481, and CJ1W-NC881 • Analog Input Unit: CJ1W-AD042 • Analog Output Unit: CJ1W-DA042V • Serial Communications Units: CJ1W-SCU22, CJ1W-SCU32, and CJ1W-SCU42 z Expansion Racks A CJ-series Expansion Rack can be connected to the CPU Rack or another CJ-series Expansion Rack. An Expansion Rack can consist of an I/O Interface Unit, a Power Supply Unit, Basic I/O Units, Special I/O Units, CPU Bus Units, and an End Cover. CPU Rack Power Supply Unit CPU Unit Memory Card
I/O Control Unit
Expansion Rack Power Supply Unit
2-2
I/O Interface Unit
Configuration Units (Basic I/O Units, Special I/O Units, CPU Bus Units)
Configuration Units (Basic I/O Units, Special I/O Units, CPU Bus Units)
End Cover
End Cover
CJ2 CPU Unit Hardware User’s Manual
Page 73
2 Basic System Configuration and Devices
CPU Rack The CPU Rack consists of a CJ2 CPU Unit, a CJ-series Power Supply Unit, CJ-series Configuration Units, and a CJ-series End Cover. Up to 10 Configuration Units can be connected.
z CJ2H CPU Units I/O Control Unit*1 Power Supply Unit
CPU Unit
PA205R SYSMAC CJ2H CPU64-EIP
RUN ERR/ALM INH PRPHL PROGRAMMABLE COMM CONTROLLER BKUP
POWER
End Cover MS NS COMM 100M 10M
OPEN
2
MCPWR
L1
2-1 Basic System Configuration
2-1-2
BUSY
AC100-240V INPUT PERIPHERAL
L2/N
PORT
2-1-2 CPU Rack
RUN OUTPUT AC240V DC24V
Configuration Units (10 max.) (Basic I/O Units, Special I/O Units, CPU Bus Units) Memory Card
*1 The I/O Control Unit is required only to connect an Expansion Rack. It must be connected next to the CPU Unit.
z CJ2M CPU Units Power Supply Unit
Pulse I/O Modules*1
CPU Unit
I/O Control Unit*3
End Cover
PA205R POWER
L1
AC100-240V INPUT L2/N
RUN OUTPUT AC240V DC24V
Configuration Units (10 max.) Memory Card
RS-232C
RS-422A/485
*1 Up to two Pulse I/O Modules can be connected to the left of the CPU Unit. *2 CJ2M-CPU3@ only. *3 The I/O Control Unit is required only to connect an Expansion Rack. It must be connected immediately to the right of the CPU Unit.
Serial Option Board*2
Even though the CJ-series PLCs do not have Backplanes, the term “slot” is still used to refer to the location of Units. Slot numbers are assigned in order to Units from left to right on the CPU Rack (slot 0, slot 1, slot 2, etc.).
CJ2 CPU Unit Hardware User’s Manual
2-3
Page 74
2 Basic System Configuration and Devices
Although the CJ-series PLCs do not require Backplanes, the term “slot” is still used to refer to the relative position of a Unit in the Rack. Slot numbers increase toward the right side of the Rack. Name
Configuration
CJ-series CPU Unit CPU Rack
CJ2H CPU Units CJ2M CPU Units
Remarks One required for every CPU Rack. One required for every CPU Rack.
Pulse I/O Module (Can be connected only with a CJ2M CPU Unit.)
Connected to use pulse I/O. Up to two Pulse I/O Modules can be connected. They must be connected to the immediate left of the CPU Unit. The Pulse I/O Module closest to the CPU Unit is Pulse I/O Module 0 and the other one is Pulse I/O Module 1.
Serial Option Board (Can be mounted only with the CJ2MCPU3@.)
One Serial Option Board can be mounted in the CJ2M-CPU3@.
Memory Card
Install as required.
CJ-series Power Supply Unit
One required for every CPU Rack.
I/O Control Unit
Required to connect an Expansion Rack. Must be connected immediately to the right of the CPU Unit.
Configuration Units
A total of up to 10 Units can be connected to the CPU Rack and to each of the Expansion Racks. (An error will occur if 11 or more Units are connected.)
CJ-series Basic I/O Units CJ-series Special I/O Units CJ-series CPU Bus Units
End Cover
Must be connected to the right end of the CPU Rack. One End Cover is provided with the CPU Unit. A fatal error will occur if the End Cover is not connected.
2-4
CJ2 CPU Unit Hardware User’s Manual
Page 75
2 Basic System Configuration and Devices z CJ2H CPU Units Model CJ2H-CPU68-EIP
I/O capacity 2,560 points
CJ2H-CPU67-EIP
Program capacity
DM Area capacity
5 VDC
400 Ksteps
832 Kwords (DM: 32 Kwords, EM: 32 Kwords × 25 banks)
250 Ksteps
512 Kwords (DM: 32 Kwords, EM: 32 Kwords × 15 banks)
150 Ksteps
352 Kwords (DM: 32 Kwords, EM: 32 Kwords × 10 banks)
CJ2H-CPU65-EIP
100 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
CJ2H-CPU64-EIP
50 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
400 Ksteps
832 Kwords (DM: 32 Kwords, EM: 32 Kwords × 25 banks)
CJ2H-CPU67
250 Ksteps
512 Kwords (DM: 32 Kwords, EM: 32 Kwords × 15 banks)
CJ2H-CPU66
150 Ksteps
352 Kwords (DM: 32 Kwords, EM: 32 Kwords × 10 banks)
CJ2H-CPU65
100 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
CJ2H-CPU64
50 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
2,560 points
0.82*1
Weight
24 VDC ---
280 g max.*2
2 2-1-2 CPU Rack
CJ2H-CPU66-EIP
CJ2H-CPU68
Current consumption (A)
0.42*1
---
190 g max.*2
*1 Increases by 0.15 A/Unit when an NT-AL001 Link Adapter is used. Increases by 0.04 A/Unit when a CJ1W-CIF11 RS-422A Converter is used. Increases by 0.20 A/Unit when an NV3W-M@20L Programmable Terminal is used. *2 Includes the weight of the End Cover.
CJ2 CPU Unit Hardware User’s Manual
2-1 Basic System Configuration
Units
2-5
Page 76
2 Basic System Configuration and Devices z CJ2M CPU Units Model
I/O capacity
Program capacity
CJ2M-CPU35
2,560 points
60 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
CJ2M-CPU34
30 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
CJ2M-CPU33
20 Ksteps
64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)
CJ2M-CPU32
10 Ksteps
64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)
CJ2M-CPU31
5 Ksteps
64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)
60 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
CJ2M-CPU14
30 Ksteps
160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)
CJ2M-CPU13
20 Ksteps
64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)
CJ2M-CPU12
10 Ksteps
64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)
CJ2M-CPU11
5 Ksteps
64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)
CJ2M-CPU15
2,560 points
DM Area capacity
Current consumption (A) 5 VDC
Weight
24 VDC
0.7*1
---
190 g max.*2, *3
0.5*1
---
130 g max.*2, *3
*1 Increases by 0.15 A/Unit when an NT-AL001 Link Adapter is used. Increases by 0.04 A/Unit when a CJ1W-CIF11 RS-422A Converter is used. Increases by 0.20 A/Unit when an NV3W-M@20L Programmable Terminal is used. *2 Includes the weight of the End Cover. *3 The weight of a Serial Option Board is not included.
2-6
CJ2 CPU Unit Hardware User’s Manual
Page 77
2 Basic System Configuration and Devices
Model
Current consumption (A)
Specifications
5 VDC
24 VDC
Weight
CJ2M-MD211
Sinking outputs, MIL connector 10 inputs (including four interrupt/quickresponse inputs and two high-speed counter inputs) 6 outputs (including two pulse outputs and two PWM outputs)
0.08
---
70 g
CJ2M-MD212
Sourcing outputs, MIL connector 10 inputs (including four interrupt/quickresponse inputs and two high-speed counter inputs) 6 outputs (including two pulse outputs and two PWM outputs)
0.08
---
70 g
2
Model
Specifications
RS-232C Option Board
CP1W-CIF01
Mounted in the Option Board slot in the CJ2M-CPU3@ to enable using an RS232C port. Maximum transmission distance: 15 m
RS-422A/485 Option Board
CP1W-CIF11
Mounted in the Option Board slot in the CJ2M-CPU3@ to enable using an RS422A/485 port. Maximum transmission distance: 50 m
Isolated RS422A/485 Option Board
CP1W-CIF12
Mounted in the Option Board slot in the CJ2M-CPU3@ to enable using an RS422A/485 port. Maximum transmission distance: 500 m
Serial communications mode
Current consumption (A)
Host Link, 1:N NT Link, Noprotocol, Serial PLC Link Slave, Serial PLC Link Master, Serial Gateway converted to CompoWay/F, and Tool Bus*
0.005 A
---
20 g
0.030 A
---
20 g
0.075 A
---
30 g
5 VDC
Weight
24 VDC
* The following modes cannot be used: 1:1 NT Link, Serial Gateway converted to Host Link FINS, 1:1 Link Master, and 1:1 Link Slave.
z CJ-series Power Supply Units Output capacity
Model
Power supply voltage
CJ1W-PA205R
100 to 240 VAC
5.0 A
0.8 A
RUN output
350 g max.
CJ1W-PA205C
100 to 240 VAC
4.6 A
0.8 A
Replacement notification
400 g max.
CJ1W-PA202
100 to 240 VAC
2.8 A
0.4 A
---
200 g max.
CJ1W-PD025
24 VDC
5.0 A
0.8 A
---
335 g max.
CJ1W-PD022
24 VDC (noninsulated type)
2.0 A
0.4 A
---
130 g max.
CJ2 CPU Unit Hardware User’s Manual
5 VDC
Additional functions
24 VDC
Weight
2-7
2-1-2 CPU Rack
Serial Option Boards (CJ2M-CPU3@ Only) Name
2-1 Basic System Configuration
Pulse I/O Modules (CJ2M CPU Unit Only)
Page 78
2 Basic System Configuration and Devices z Memory Cards Model
Specifications
HMC-EF183
Flash memory, 128 MB
HMC-EF283
Flash memory, 256 MB
HMC-EF583
Flash memory, 512 MB
HMC-AP001
Memory Card Adapter (for PCMIA slot in personal computer)
z I/O Control Unit Model
Specifications
Current consumption (A) 5 VDC
CJ1W-IC101
Required to connect a CJ-series Expansion Rack to a CJ-series CPU Rack. Must be connected immediately to the right of the CPU Unit. Connect to the I/O Interface Unit (CJ1W-II101) on the first Expansion Rack with a CS/CJ-series I/O Connecting Cable.
0.020 A
Weight
24 VDC ---
70 g max.
z End Cover Model
Specifications
Current consumption (A)
CJ1W-TER01
Must be connected to the right end of the CPU Rack. (A fatal error will occur if the End Cover is not connected to the right end of the Rack.)*1
Included with CPU Unit and I/O Interface Unit.
Weight ---
*1 One End Cover is provided with the CPU Unit and with an I/O Interface Unit.
2-8
CJ2 CPU Unit Hardware User’s Manual
Page 79
2 Basic System Configuration and Devices
Name DIN Track
Model
Specifications
PFP-50N
Track length: 50 cm, height: 7.3 mm
PFP-100N
Track length: 1 m, height: 7.3 mm
PFP-100N2
Track length: 1 m, height: 16 mm
PFP-M
Stopper to prevent Units from moving on the track. Two each are provided with the CPU Unit and with an I/O Interface Unit.
Programming Device Connecting Cable for peripheral (USB) port
Commercially available USB cable
USB 2.0 (or 1.1) cable (A connector - B connector), 5.0 m max.
Programming Device Connecting Cables for serial port
XW2Z-200S-CV
Connects to IBM PC/AT computer Uses static-resistant connector.
XW2Z-500S-CV
Connects to IBM PC/AT computer D-Sub 9-pin connector (Cable length: 5.0 m). Uses static-resistant connector.
XW2Z-200S-V
Connects to IBM PC/AT computer D-Sub 9-pin connector. (Cable length: 2.0 m)
XW2Z-500S-V
Connects to IBM PC/AT computer D-Sub 9-pin connector. (Cable length: 5.0 m)
Connecting Cable for EtherNet/IP port*
Commercially available 100Base-TX twisted-pair cable
Recommended: Fujikura F-LINK-E 0.5 mm × 4P Twisted-pair cable with RJ45 Modular Connectors on both ends. Connect between EtherNet/IP Unit or built-in EtherNet/IP port and Ethernet switch. Use STP (shielded twisted-pair) cable of category 5 or 5e.
Communications Adaptor (RS-422A Converter)
CJ1W-CIF11
Current consumption at 5 V: 0.04 A
RS-232C/RS-422A Link Adapter
NT-AL001
Maximum distance: 500 m; only RS-422A is supported. Current consumption at 5 V: 0.15 A
MIL Flat Cable Connector for Pulse I/O Modules
XG4M-4030-T
40-pin MIL connector, pressure-welded type (This connector is used by user to make a cable.)
Connector-Terminal Block Conversion Units
XW2D-40G6
Slim model (M3 screw terminals), 40 terminals
XW2B-40G5
Through model (M3 screw terminals), 40 terminals
XW2B-40G4
Through model (M3.5 screw terminals), 40 terminals
XW2Z-100K
Cable length: 1 m
Connector-Terminal Block Conversion Cables
Servo Relay Units
XW2Z-150K
Cable length: 1.5 m
XW2Z-200K
Cable length: 2 m
XW2Z-300K
Cable length: 3 m
XW2Z-500K
Cable length: 5 m
XW2B-20J6-8A
To connect one axis
XW2B-20J6-9A
To connect two axes
* CJ2H-CPU6@-EIP or CJ2M-CPU3@ only.
CJ2 CPU Unit Hardware User’s Manual
2 2-1-2 CPU Rack
D-Sub 9-pin connector (Cable length: 2.0 m).
2-1 Basic System Configuration
Others
2-9
Page 80
2 Basic System Configuration and Devices
Name Servo Relay Unit Connection Cables
OMNUC G Series
OMNUC G5 Series
SMARTSTEP 2 Series
SMARTSTEP A Series
SMARTSTEP Junior
OMNUC W Series
Model CJ2M Pulse I/O Module side
XW2Z-050J-A33
Cable length: 0.5 m
XW2Z-100J-A33
Cable length: 1 m
Servo Drive side
XW2Z-100J-B31
Cable length: 1 m
XW2Z-200J-B31
Cable length: 2 m
CJ2M Pulse I/O Module side
XW2Z-050J-A33
Cable length: 0.5 m
XW2Z-100J-A33
Cable length: 1 m
Servo Drive side
XW2Z-100J-B31
Cable length: 1 m
XW2Z-200J-B31
Cable length: 2 m
CJ2M Pulse I/O Module side
XW2Z-050J-A33
Cable length: 0.5 m
XW2Z-100J-A33
Cable length: 1 m
Servo Drive side
XW2Z-100J-B32
Cable length: 1 m
XW2Z-200J-B32
Cable length: 2 m
CJ2M Pulse I/O Module side
XW2Z-100J-A26
Cable length: 1 m
Servo Drive side
XW2Z-100J-B5
Cable length: 1 m
XW2Z-200J-B5
Cable length: 2 m
CJ2M Pulse I/O Module side
XW2Z-100J-A26
Cable length: 1 m
Servo Drive side
XW2Z-100J-B17
Cable length: 1 m
XW2Z-200J-B17
Cable length: 2 m
CJ2M Pulse I/O Module side
XW2Z-050J-A27
Cable length: 0.5 m
XW2Z-100J-A27
Cable length: 1 m
Servo Drive side
XW2Z-100J-B4
Cable length: 1 m
XW2Z-200J-B4
Cable length: 2 m
CJ1W-BAT01
For CJ2 CPU Unit
CXONE-AL@@C-V@ CXONE-AL@@D-V@
CX-One is an FA Integrated Tool Package that integrates the PLC, network, HMI, components, motion control, and PLC-based process control.
Battery Set Support Software
Specifications
CX-One
• CX-Programmer • CX-Integrator • SwitchBox Utility • CX-Simulator • CX-Protocol • CX-Designer • CX-Thermo • CX-Position • CX-Motion/CX-Motion-NCF/CX-Motion-MCH • CX-Drive • CX-Process Tool • NS Faceplate Auto-Builder • CX-FLnet • Network Configurator
2-10
CJ2 CPU Unit Hardware User’s Manual