Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 10 of 48

SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 2 Basic System Configuration and Devices, pages 71 to 80

Pages 71 to 80 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 71

Basic System Configuration and Devices

2

This section describes the basic system configuration and devices used in a CJ2 PLC. The CJ Series supports the following two types of system configuration. • Basic System Configuration: System consisting of CPU Rack and Expansion Racks. • Expanded System Configuration: System connected via CPU Unit built-in serial port and PLC Units, such as Communications Units.

2-1 Basic System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2-1-1 2-1-2 2-1-3 2-1-4 2-1-5 2-1-6

Basic System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 CPU Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Expansion Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11 Configuration Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14 Calculating Unit Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22 Calculating Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25

2-2 Expanded System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27 2-2-1 2-2-2

CJ2 CPU Unit Hardware User’s Manual

Serial Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27 Communications Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29

2-1

Page 72

2 Basic System Configuration and Devices

2-1

Basic System Configuration

2-1-1

Basic System Configuration z CPU Rack A CPU Rack can consist of a CJ2 CPU Unit, a CJ-series Power Supply Unit, CJ-series Configuration Units (Basic I/O Units, Special I/O Units, CPU Bus Units), and a CJ-series End Cover. The same CJseries Power Supply Units and CJ-series Configuration Units that are used with CJ1 CPU Units are used with CJ2 CPU Units.* An I/O Control Unit is required to connect a CJ-series Expansion Rack. A Memory Card is optional. * All CJ-series Units can be used as Configuration Units, but only Units that specifically support the CJ2 CPU Unit can access the expanded portions of the I/O memory areas of the CJ2 CPU Units (i.e., A960 to A1471, A10000 to A11535, and EM banks D to 18). Only the following CJ1 Units specifically support the CJ2 CPU Units. • EtherNet/IP Unit: CJ1W-EIP21 • Position Control Units: CJ1W-NC214, CJ1W-NC234, CJ1W-NC281, CJ1W-NC414, CJ1W-NC434, CJ1WNC481, and CJ1W-NC881 • Analog Input Unit: CJ1W-AD042 • Analog Output Unit: CJ1W-DA042V • Serial Communications Units: CJ1W-SCU22, CJ1W-SCU32, and CJ1W-SCU42 z Expansion Racks A CJ-series Expansion Rack can be connected to the CPU Rack or another CJ-series Expansion Rack. An Expansion Rack can consist of an I/O Interface Unit, a Power Supply Unit, Basic I/O Units, Special I/O Units, CPU Bus Units, and an End Cover. CPU Rack Power Supply Unit CPU Unit Memory Card

I/O Control Unit

Expansion Rack Power Supply Unit

2-2

I/O Interface Unit

Configuration Units (Basic I/O Units, Special I/O Units, CPU Bus Units)

Configuration Units (Basic I/O Units, Special I/O Units, CPU Bus Units)

End Cover

End Cover

CJ2 CPU Unit Hardware User’s Manual

Page 73

2 Basic System Configuration and Devices

CPU Rack The CPU Rack consists of a CJ2 CPU Unit, a CJ-series Power Supply Unit, CJ-series Configuration Units, and a CJ-series End Cover. Up to 10 Configuration Units can be connected.

z CJ2H CPU Units I/O Control Unit*1 Power Supply Unit

CPU Unit

PA205R SYSMAC CJ2H CPU64-EIP

RUN ERR/ALM INH PRPHL PROGRAMMABLE COMM CONTROLLER BKUP

POWER

End Cover MS NS COMM 100M 10M

OPEN

2

MCPWR

L1

2-1 Basic System Configuration

2-1-2

BUSY

AC100-240V INPUT PERIPHERAL

L2/N

PORT

2-1-2 CPU Rack

RUN OUTPUT AC240V DC24V

Configuration Units (10 max.) (Basic I/O Units, Special I/O Units, CPU Bus Units) Memory Card

*1 The I/O Control Unit is required only to connect an Expansion Rack. It must be connected next to the CPU Unit.

z CJ2M CPU Units Power Supply Unit

Pulse I/O Modules*1

CPU Unit

I/O Control Unit*3

End Cover

PA205R POWER

L1

AC100-240V INPUT L2/N

RUN OUTPUT AC240V DC24V

Configuration Units (10 max.) Memory Card

RS-232C

RS-422A/485

*1 Up to two Pulse I/O Modules can be connected to the left of the CPU Unit. *2 CJ2M-CPU3@ only. *3 The I/O Control Unit is required only to connect an Expansion Rack. It must be connected immediately to the right of the CPU Unit.

Serial Option Board*2

Even though the CJ-series PLCs do not have Backplanes, the term “slot” is still used to refer to the location of Units. Slot numbers are assigned in order to Units from left to right on the CPU Rack (slot 0, slot 1, slot 2, etc.).

CJ2 CPU Unit Hardware User’s Manual

2-3

Page 74

2 Basic System Configuration and Devices

Although the CJ-series PLCs do not require Backplanes, the term “slot” is still used to refer to the relative position of a Unit in the Rack. Slot numbers increase toward the right side of the Rack. Name

Configuration

CJ-series CPU Unit CPU Rack

CJ2H CPU Units CJ2M CPU Units

Remarks One required for every CPU Rack. One required for every CPU Rack.

Pulse I/O Module (Can be connected only with a CJ2M CPU Unit.)

Connected to use pulse I/O. Up to two Pulse I/O Modules can be connected. They must be connected to the immediate left of the CPU Unit. The Pulse I/O Module closest to the CPU Unit is Pulse I/O Module 0 and the other one is Pulse I/O Module 1.

Serial Option Board (Can be mounted only with the CJ2MCPU3@.)

One Serial Option Board can be mounted in the CJ2M-CPU3@.

Memory Card

Install as required.

CJ-series Power Supply Unit

One required for every CPU Rack.

I/O Control Unit

Required to connect an Expansion Rack. Must be connected immediately to the right of the CPU Unit.

Configuration Units

A total of up to 10 Units can be connected to the CPU Rack and to each of the Expansion Racks. (An error will occur if 11 or more Units are connected.)

CJ-series Basic I/O Units CJ-series Special I/O Units CJ-series CPU Bus Units

End Cover

Must be connected to the right end of the CPU Rack. One End Cover is provided with the CPU Unit. A fatal error will occur if the End Cover is not connected.

2-4

CJ2 CPU Unit Hardware User’s Manual

Page 75

2 Basic System Configuration and Devices z CJ2H CPU Units Model CJ2H-CPU68-EIP

I/O capacity 2,560 points

CJ2H-CPU67-EIP

Program capacity

DM Area capacity

5 VDC

400 Ksteps

832 Kwords (DM: 32 Kwords, EM: 32 Kwords × 25 banks)

250 Ksteps

512 Kwords (DM: 32 Kwords, EM: 32 Kwords × 15 banks)

150 Ksteps

352 Kwords (DM: 32 Kwords, EM: 32 Kwords × 10 banks)

CJ2H-CPU65-EIP

100 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

CJ2H-CPU64-EIP

50 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

400 Ksteps

832 Kwords (DM: 32 Kwords, EM: 32 Kwords × 25 banks)

CJ2H-CPU67

250 Ksteps

512 Kwords (DM: 32 Kwords, EM: 32 Kwords × 15 banks)

CJ2H-CPU66

150 Ksteps

352 Kwords (DM: 32 Kwords, EM: 32 Kwords × 10 banks)

CJ2H-CPU65

100 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

CJ2H-CPU64

50 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

2,560 points

0.82*1

Weight

24 VDC ---

280 g max.*2

2 2-1-2 CPU Rack

CJ2H-CPU66-EIP

CJ2H-CPU68

Current consumption (A)

0.42*1

---

190 g max.*2

*1 Increases by 0.15 A/Unit when an NT-AL001 Link Adapter is used. Increases by 0.04 A/Unit when a CJ1W-CIF11 RS-422A Converter is used. Increases by 0.20 A/Unit when an NV3W-M@20L Programmable Terminal is used. *2 Includes the weight of the End Cover.

CJ2 CPU Unit Hardware User’s Manual

2-1 Basic System Configuration

Units

2-5

Page 76

2 Basic System Configuration and Devices z CJ2M CPU Units Model

I/O capacity

Program capacity

CJ2M-CPU35

2,560 points

60 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

CJ2M-CPU34

30 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

CJ2M-CPU33

20 Ksteps

64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)

CJ2M-CPU32

10 Ksteps

64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)

CJ2M-CPU31

5 Ksteps

64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)

60 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

CJ2M-CPU14

30 Ksteps

160 Kwords (DM: 32 Kwords, EM: 32 Kwords × 4 banks)

CJ2M-CPU13

20 Ksteps

64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)

CJ2M-CPU12

10 Ksteps

64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)

CJ2M-CPU11

5 Ksteps

64 Kwords (DM: 32 Kwords, EM: 32 Kwords × 1 bank)

CJ2M-CPU15

2,560 points

DM Area capacity

Current consumption (A) 5 VDC

Weight

24 VDC

0.7*1

---

190 g max.*2, *3

0.5*1

---

130 g max.*2, *3

*1 Increases by 0.15 A/Unit when an NT-AL001 Link Adapter is used. Increases by 0.04 A/Unit when a CJ1W-CIF11 RS-422A Converter is used. Increases by 0.20 A/Unit when an NV3W-M@20L Programmable Terminal is used. *2 Includes the weight of the End Cover. *3 The weight of a Serial Option Board is not included.

2-6

CJ2 CPU Unit Hardware User’s Manual

Page 77

2 Basic System Configuration and Devices

Model

Current consumption (A)

Specifications

5 VDC

24 VDC

Weight

CJ2M-MD211

Sinking outputs, MIL connector 10 inputs (including four interrupt/quickresponse inputs and two high-speed counter inputs) 6 outputs (including two pulse outputs and two PWM outputs)

0.08

---

70 g

CJ2M-MD212

Sourcing outputs, MIL connector 10 inputs (including four interrupt/quickresponse inputs and two high-speed counter inputs) 6 outputs (including two pulse outputs and two PWM outputs)

0.08

---

70 g

2

Model

Specifications

RS-232C Option Board

CP1W-CIF01

Mounted in the Option Board slot in the CJ2M-CPU3@ to enable using an RS232C port. Maximum transmission distance: 15 m

RS-422A/485 Option Board

CP1W-CIF11

Mounted in the Option Board slot in the CJ2M-CPU3@ to enable using an RS422A/485 port. Maximum transmission distance: 50 m

Isolated RS422A/485 Option Board

CP1W-CIF12

Mounted in the Option Board slot in the CJ2M-CPU3@ to enable using an RS422A/485 port. Maximum transmission distance: 500 m

Serial communications mode

Current consumption (A)

Host Link, 1:N NT Link, Noprotocol, Serial PLC Link Slave, Serial PLC Link Master, Serial Gateway converted to CompoWay/F, and Tool Bus*

0.005 A

---

20 g

0.030 A

---

20 g

0.075 A

---

30 g

5 VDC

Weight

24 VDC

* The following modes cannot be used: 1:1 NT Link, Serial Gateway converted to Host Link FINS, 1:1 Link Master, and 1:1 Link Slave.

z CJ-series Power Supply Units Output capacity

Model

Power supply voltage

CJ1W-PA205R

100 to 240 VAC

5.0 A

0.8 A

RUN output

350 g max.

CJ1W-PA205C

100 to 240 VAC

4.6 A

0.8 A

Replacement notification

400 g max.

CJ1W-PA202

100 to 240 VAC

2.8 A

0.4 A

---

200 g max.

CJ1W-PD025

24 VDC

5.0 A

0.8 A

---

335 g max.

CJ1W-PD022

24 VDC (noninsulated type)

2.0 A

0.4 A

---

130 g max.

CJ2 CPU Unit Hardware User’s Manual

5 VDC

Additional functions

24 VDC

Weight

2-7

2-1-2 CPU Rack

Serial Option Boards (CJ2M-CPU3@ Only) Name

2-1 Basic System Configuration

Pulse I/O Modules (CJ2M CPU Unit Only)

Page 78

2 Basic System Configuration and Devices z Memory Cards Model

Specifications

HMC-EF183

Flash memory, 128 MB

HMC-EF283

Flash memory, 256 MB

HMC-EF583

Flash memory, 512 MB

HMC-AP001

Memory Card Adapter (for PCMIA slot in personal computer)

z I/O Control Unit Model

Specifications

Current consumption (A) 5 VDC

CJ1W-IC101

Required to connect a CJ-series Expansion Rack to a CJ-series CPU Rack. Must be connected immediately to the right of the CPU Unit. Connect to the I/O Interface Unit (CJ1W-II101) on the first Expansion Rack with a CS/CJ-series I/O Connecting Cable.

0.020 A

Weight

24 VDC ---

70 g max.

z End Cover Model

Specifications

Current consumption (A)

CJ1W-TER01

Must be connected to the right end of the CPU Rack. (A fatal error will occur if the End Cover is not connected to the right end of the Rack.)*1

Included with CPU Unit and I/O Interface Unit.

Weight ---

*1 One End Cover is provided with the CPU Unit and with an I/O Interface Unit.

2-8

CJ2 CPU Unit Hardware User’s Manual

Page 79

2 Basic System Configuration and Devices

Name DIN Track

Model

Specifications

PFP-50N

Track length: 50 cm, height: 7.3 mm

PFP-100N

Track length: 1 m, height: 7.3 mm

PFP-100N2

Track length: 1 m, height: 16 mm

PFP-M

Stopper to prevent Units from moving on the track. Two each are provided with the CPU Unit and with an I/O Interface Unit.

Programming Device Connecting Cable for peripheral (USB) port

Commercially available USB cable

USB 2.0 (or 1.1) cable (A connector - B connector), 5.0 m max.

Programming Device Connecting Cables for serial port

XW2Z-200S-CV

Connects to IBM PC/AT computer Uses static-resistant connector.

XW2Z-500S-CV

Connects to IBM PC/AT computer D-Sub 9-pin connector (Cable length: 5.0 m). Uses static-resistant connector.

XW2Z-200S-V

Connects to IBM PC/AT computer D-Sub 9-pin connector. (Cable length: 2.0 m)

XW2Z-500S-V

Connects to IBM PC/AT computer D-Sub 9-pin connector. (Cable length: 5.0 m)

Connecting Cable for EtherNet/IP port*

Commercially available 100Base-TX twisted-pair cable

Recommended: Fujikura F-LINK-E 0.5 mm × 4P Twisted-pair cable with RJ45 Modular Connectors on both ends. Connect between EtherNet/IP Unit or built-in EtherNet/IP port and Ethernet switch. Use STP (shielded twisted-pair) cable of category 5 or 5e.

Communications Adaptor (RS-422A Converter)

CJ1W-CIF11

Current consumption at 5 V: 0.04 A

RS-232C/RS-422A Link Adapter

NT-AL001

Maximum distance: 500 m; only RS-422A is supported. Current consumption at 5 V: 0.15 A

MIL Flat Cable Connector for Pulse I/O Modules

XG4M-4030-T

40-pin MIL connector, pressure-welded type (This connector is used by user to make a cable.)

Connector-Terminal Block Conversion Units

XW2D-40G6

Slim model (M3 screw terminals), 40 terminals

XW2B-40G5

Through model (M3 screw terminals), 40 terminals

XW2B-40G4

Through model (M3.5 screw terminals), 40 terminals

XW2Z-100K

Cable length: 1 m

Connector-Terminal Block Conversion Cables

Servo Relay Units

XW2Z-150K

Cable length: 1.5 m

XW2Z-200K

Cable length: 2 m

XW2Z-300K

Cable length: 3 m

XW2Z-500K

Cable length: 5 m

XW2B-20J6-8A

To connect one axis

XW2B-20J6-9A

To connect two axes

* CJ2H-CPU6@-EIP or CJ2M-CPU3@ only.

CJ2 CPU Unit Hardware User’s Manual

2 2-1-2 CPU Rack

D-Sub 9-pin connector (Cable length: 2.0 m).

2-1 Basic System Configuration

Others

2-9

Page 80

2 Basic System Configuration and Devices

Name Servo Relay Unit Connection Cables

OMNUC G Series

OMNUC G5 Series

SMARTSTEP 2 Series

SMARTSTEP A Series

SMARTSTEP Junior

OMNUC W Series

Model CJ2M Pulse I/O Module side

XW2Z-050J-A33

Cable length: 0.5 m

XW2Z-100J-A33

Cable length: 1 m

Servo Drive side

XW2Z-100J-B31

Cable length: 1 m

XW2Z-200J-B31

Cable length: 2 m

CJ2M Pulse I/O Module side

XW2Z-050J-A33

Cable length: 0.5 m

XW2Z-100J-A33

Cable length: 1 m

Servo Drive side

XW2Z-100J-B31

Cable length: 1 m

XW2Z-200J-B31

Cable length: 2 m

CJ2M Pulse I/O Module side

XW2Z-050J-A33

Cable length: 0.5 m

XW2Z-100J-A33

Cable length: 1 m

Servo Drive side

XW2Z-100J-B32

Cable length: 1 m

XW2Z-200J-B32

Cable length: 2 m

CJ2M Pulse I/O Module side

XW2Z-100J-A26

Cable length: 1 m

Servo Drive side

XW2Z-100J-B5

Cable length: 1 m

XW2Z-200J-B5

Cable length: 2 m

CJ2M Pulse I/O Module side

XW2Z-100J-A26

Cable length: 1 m

Servo Drive side

XW2Z-100J-B17

Cable length: 1 m

XW2Z-200J-B17

Cable length: 2 m

CJ2M Pulse I/O Module side

XW2Z-050J-A27

Cable length: 0.5 m

XW2Z-100J-A27

Cable length: 1 m

Servo Drive side

XW2Z-100J-B4

Cable length: 1 m

XW2Z-200J-B4

Cable length: 2 m

CJ1W-BAT01

For CJ2 CPU Unit

CXONE-AL@@C-V@ CXONE-AL@@D-V@

CX-One is an FA Integrated Tool Package that integrates the PLC, network, HMI, components, motion control, and PLC-based process control.

Battery Set Support Software

Specifications

CX-One

• CX-Programmer • CX-Integrator • SwitchBox Utility • CX-Simulator • CX-Protocol • CX-Designer • CX-Thermo • CX-Position • CX-Motion/CX-Motion-NCF/CX-Motion-MCH • CX-Drive • CX-Process Tool • NS Faceplate Auto-Builder • CX-FLnet • Network Configurator

2-10

CJ2 CPU Unit Hardware User’s Manual