Page 81
2 Basic System Configuration and Devices
Expansion Racks CJ-series Expansion Racks can be connected to the CPU Rack to expand the number of Units in the System beyond the CPU Rack. Up to 10 I/O Units can be mounted to each Expansion Rack and a total of 3 Expansion Racks can be connected. Mount an I/O Control Unit immediately to the right of the CPU Unit, and mount the I/O Interface Unit immediately to the right of the Power Supply Unit on the Expansion Rack. Mounting them in other locations may cause malfunctions.
2-1 Basic System Configuration
2-1-3
10 Units max.
2 CPU Rack
CS/CJ-series I/O Connecting Cable 30 cm, 70 cm, 2 m, 3 m, 5 m, 10 m, 12 m
CPU Unit
I/O Control Unit End Cover
CJ-series Expansion Rack
Power Supply Unit
Total cable length: 12 m
Expansion Racks: 3 maximum
CS/CJ-series I/O Connecting Cable 30 cm, 70 cm, 2 m, 3 m, 5 m, 10 m, 12 m
I/O Interface Unit
CS/CJ-series I/O Connecting Cables Cable Length CS1W-CN313 0.3 m CS1W-CN713 0.7 m CS1W-CN223 2m CS1W-CN323 3m CS1W-CN523 5m CS1W-CN133 10 m CS1W-CN133B2 12 m
I/O Interface Unit
CJ-series Expansion Rack
Power Supply Unit
10 Units max.
Maximum Number of Expansion Racks Expansion pattern CJ-series CPU Rack plus CJ-series Expansion Racks
CJ2 CPU Unit Hardware User’s Manual
Maximum number of Racks 3 Racks
Remarks The total length of I/O Connecting Cable between the CPU Rack and an Expansion Rack, and between all Expansion Racks, must be no more than 12 m.
2-11
2-1-3 Expansion Racks
Power Supply Unit
Page 82
2 Basic System Configuration and Devices
Units z Units for CJ-series Expansion Racks Rack CJ-series Expansion Racks
Configuration
Remarks
CJ-series Power Supply Unit I/O Interface Unit (one End Cover included.) CJ-series Basic I/O Units
One required for each Expansion Rack. (An I/O Control Unit is required on the CJ-series CPU Rack.) A total of up to 10 Units can be connected to the CPU Rack and to each of the Expansion Racks. (An error will occur if 11 or more Units are connected.)
CJ-series Special I/O Units CJ-series CPU Bus Units End Cover
Must be connected to the right end of the Expansion Rack. (One End Cover is provided with the I/O Interface Unit. A fatal error will occur if the End Cover is not connected.)
CS/CJ-series I/O Connecting Cable
Required to connect the I/O Interface Unit to the I/O Control Unit or previous I/O Interface Unit.
z CJ-series Power Supply Unit Model
Output capacity
Power supply voltage
5 VDC
Functions
24 VDC
CJ1W-PA205R
100 to 240 VAC
5.0 A
0.8 A
RUN output
CJ1W-PA205C
100 to 240 VAC
5.0 A
0.8 A
Replacement notification
CJ1W-PA202
100 to 240 VAC
2.8 A
0.4 A
---
CJ1W-PD025
24 VDC
5.0 A
0.8 A
---
CJ1W-PD022
24 VDC (non-insulated type)
2.0 A
0.4 A
--- z I/O Interface Unit Model
Specifications
Current consumption (A) 5 VDC
CJ1W-II101
One Interface Unit is required for each CJ-series Expansion Rack. One End Cover is provided with each Unit.
0.13 A
Weight
24 VDC ---
130 g max.*1
*1 Includes the weight of the End Cover.
2-12
CJ2 CPU Unit Hardware User’s Manual
Page 83
2 Basic System Configuration and Devices
Model
Specifications
Current consumption (A)
CJ1W-TER01
Must be connected to the right end of the CPU Rack. (A fatal error will occur if the End Cover is not connected to the right end of the Rack.)
Included with the CPU Unit or I/O Interface Unit.
Weight ---
One End Cover is provided with the CPU Unit and with an I/O Interface Unit.
z CS/CJ-series I/O Connecting Cables Model CS1W-CN313 CS1W-CN713
Cable length 0.3 m 0.7 m 2m
CS1W-CN323
3m
CS1W-CN523
5m
CS1W-CN133
10 m
CS1W-CN133B2
12 m
CJ2 CPU Unit Hardware User’s Manual
2 2-1-3 Expansion Racks
CS1W-CN223
Specifications An I/O Connecting Cable connects an I/O Control Unit (CJ1W-IC101) to an I/O Interface Unit (CJ1W-II101), or connects an I/O Interface Unit to another I/O Interface Unit.
2-1 Basic System Configuration z End Cover
2-13
Page 84
2 Basic System Configuration and Devices
2-1-4
Configuration Units
Maximum Number of Units A maximum of 10 Units can be connected to the CPU Rack for a CJ2 CPU Unit or to an Expansion Rack. There are no restrictions in the number of each model of Unit based on location. Note A fatal error will occur and the CPU Unit will not operate if more than the allowable number of Units is connected to a CJ2 CPU Rack or to an Expansion Rack.
Models of Configuration Units The Configuration Units with which the CJ2 CPU Unit can exchange data are classified into three groups. The number of Units that can be mounted depends on the type of Unit. Units
Description
Number of mountable Units
Basic I/O Units
Basic I/O Units are used for discrete inputs and outputs.
Identified by the CPU Unit according to mounting position.
Up to 40 Basic I/O Units can be mounted.
Special I/O Units
Special I/O Units are more advanced than Basic I/O Units. They support functions other than discrete inputs and outputs.
Identified by the CPU Unit using unit numbers 0 to 95 set with the rotary switches on the front panel of the Unit.
Up to 40 Special I/O Units can be mounted. (Depending on the model, more than one unit number is used for one Unit.)
Identified by the CPU Unit using unit number 0 to F Examples: Network Communications Units and Serial Com- set with the rotary switch on the front munications Units panel of the Unit. CPU Bus Units have a larger area for exchanging data with the CPU Unit than Special I/O Units.
Up to 16 CPU Bus Units can be mounted.
Examples: Analog I/O Units and High-speed Counter Units Special I/O Units have a smaller area for exchanging data with the CPU Unit than CPU Bus Units (including Network Communications Units). CPU Bus Unit
2-14
Unit identification method
CPU Units are advanced units that exchange data with the CPU Unit via the CPU bus.
CJ2 CPU Unit Hardware User’s Manual
Page 85
2 Basic System Configuration and Devices z CJ-series Basic I/O Units Input Units Name
Specifications
Model
Number of bits allocated
Current consumption (A) 5 VDC
Weight
24 VDC
CJ1W-ID201
16*1
0.08
---
110 g max.
Terminal block 24 VDC, 16 inputs
CJ1W-ID211*2
16
0.08
---
110 g max.
CJ1W-ID212*2
16
0.13
---
110 g max.
Fujitsu-compatible connector 24 VDC, 32 inputs
CJ1W-ID231*3
32
0.09
---
70 g max.
MIL connector 24 VDC, 32 inputs
CJ1WID232*2*3
32
0.09
---
70 g max.
CJ1WID233*2*3
32
0.20
---
70 g max.
Fujitsu-compatible connector 24 VDC, 64 inputs
CJ1W-ID261*3
64
0.09
---
110 g max.
MIL connector
CJ1W-ID262*3
64
0.09
---
110 g max.
200 to 240 VAC, 8 inputs
CJ1W-IA201
16*1
0.08
---
130 g max.
100 to 120 VAC, 16 inputs
CJ1W-IA111
16
0.09
---
130 g max.
Interrupt Input Units
24 VDC, 16 inputs
CJ1W-INT01*4
16
0.08
---
110 g max.
Quickresponse Input Units
24 VDC, 16 inputs
CJ1W-IDP01
16
0.08
---
110 g max.
B7A Interface Units
64 inputs
CJ1W-B7A14
64
0.09
---
80 g max.
24 VDC, 64 inputs AC Input Units
*1 Although 16 I/O bits are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables. *2 The ON/OFF response time for the CJ1W-ID212/CJ1W-ID233 is shorter than for the CJ1W-ID211/CJ1WID232, as shown below. • ON response time: 20 µs improved to 15 µs • OFF response time: 400 µs improved to 90 µs *3 The cable-side connector is not provided with Units equipped with cables. Purchase the connector separately (Refer to 5-3-3 Wiring Basic I/O Units with Connectors.), or use an OMRON Connector- Terminal Block Conversion Unit or I/O Terminal (Refer to 5-3-4 Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals.). *4 An Interrupt Input Unit can be connected only in a CJ-series CPU Rack. Connect the Interrupt Input Units in following slots on the CPU Rack. An I/O setting error will occur if an Interrupt Input Unit is connected in other positions on the CPU Rack or to any position on an Expansion Rack. Up to two Interrupt Input Units can be connected. • CJ2H-CPU6@-EIP: Slots 0 to 3 • CJ2H-CPU6@ or CJ2M-CPU@@: Slots 0 to 4
CJ2 CPU Unit Hardware User’s Manual
2-15
2 2-1-4 Configuration Units
Terminal block 12 to 24 VDC, 8 inputs
DC Input Units
2-1 Basic System Configuration
Configuration Units
Page 86
2 Basic System Configuration and Devices
Output Units Name Relay Output Units
Triac Output Unit Transistor Output Units
Sinking outputs
Sourcing outputs
B7A Interface Units
Specifications
Model
Current consumption (A)
Number of bits allocated
5 VDC
24 VDC
Weight
Terminal block, 250 VAC/24 VDC, 2 A; 8 points, independent contacts
CJ1W-OC201
16*1
0.09
0.048 (0.006 × Number of ON outputs)
140 g max.
Terminal block, 250 VAC/24 VDC, 2 A; 16 points
CJ1W-OC211
16
0.11
0.096 (0.006 × Number of ON outputs)
170 g max.
Terminal block, 250 VAC, 0.6 A; 8 points
CJ1W-OA201
16*1
0.22
---
150 g max.
Terminal block, 12 to 24 VDC, 2 A; 8 outputs
CJ1W-OD201
16*1
0.09
---
110 g max.
Terminal block, 12 to 24 VDC, 0.5 A; 8 outputs
CJ1W-OD203
16*1
0.10
---
110 g max.
Terminal block, 12 to 24 VDC, 0.5 A; 16 outputs
CJ1W-OD211*2
16
0.10
---
110 g max.
Terminal block, 24 VDC, 0.5 A; 16 outputs
CJ1W-OD213*2
16
0.15
---
110 g max.
Fujitsu-compatible connector, 12 to 24 VDC, 0.5 A; 32 outputs
CJ1W-OD231*3
32
0.14
---
70 g max.
MIL connector, 12 to 24 VDC, 0.5 A; 32 outputs
CJ1WOD233*2*3
32
0.14
---
70 g max.
MIL connector, 24 VDC, 0.5 A; 32 outputs
CJ1WOD234*2*3
32
0.22
---
70 g max.
Fujitsu-compatible connector, 12 to 24 VDC, 0.3 A; 64 outputs
CJ1W-OD261*3
64
0.17
---
110 g max.
MIL connector, 12 to 24 VDC, 0.3 A; 64 outputs
CJ1W-OD263*3
64
0.17
---
110 g max.
Terminal block, 24 VDC, 2 A; 8 outputs, load short-circuit protection and disconnected line detection
CJ1W-OD202
16*1
0.11
---
120 g max.
Terminal block, 24 VDC, 0.5 A; 8 outputs, load short-circuit protection
CJ1W-OD204
16*1
0.10
---
120 g max.
Terminal block, 24 VDC, 0.5 A; 16 outputs, load short-circuit protection
CJ1W-OD212
16
0.10
---
120 g max.
MIL connector, 24 VDC, 0.5 A; 32 outputs, load short-circuit protection
CJ1W-OD232*3
32
0.15
---
80 g max.
MIL connector, 12 to 24 VDC, 0.3 A; 64 outputs
CJ1W-OD262*3
64
0.17
---
110 g max.
64 outputs
CJ1W-B7A04
64
0.07
---
80 g max.
*1 Although 16 I/O bits are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables. *2 The ON/OFF response time for the CJ1W-OD213/CJ1W-OD234 is shorter than for the CJ1W-OD211/CJ1WOD233, as shown below. • ON response time: 0.1 ms improved to 0.015 ms • OFF response time: 0.8 ms improved to 0.08 ms *3 The cable-side connector is not provided with Units equipped with cables. Purchase the connector separately (Refer to 5-3-3 Wiring Basic I/O Units with Connectors.), or use an OMRON Connector- Terminal Block Conversion Unit or I/O Terminal (Refer to 5-3-4 Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals.).
2-16
CJ2 CPU Unit Hardware User’s Manual
Page 87
2 Basic System Configuration and Devices
Name 24-VDC Input/ Transistor Output Units
Sinking
Current consumption (A) 5 VDC
24 VDC
CJ1W-MD231*1
32
0.13
---
90 g max.
CJ1W-MD261*1
64
0.14
---
110 g max.
CJ1W-MD233*1
32
0.13
---
90 g max.
CJ1W-MD263*1
64
0.14
---
110 g max.
CJ1W-MD232*1
32
0.13
---
80 g max.
CJ1W-MD563*1
64
0.19
---
110 g max.
CJ1W-B7A22
64
0.07
---
80 g max.
Model
Fujitsu-compatible connector
Weight
Inputs: 24 VDC, 16 inputs Outputs: 12 to 24 VDC, 0.5 A; 16 outputs Fujitsu-compatible connector Inputs: 24 VDC, 32 inputs Outputs: 12 to 24 VDC, 0.3 A; 32 outputs MIL connector Inputs: 24 VDC, 16 inputs Outputs: 12 to 24 VDC, 0.5 A; 16 outputs MIL connector Inputs: 24 VDC, 32 inputs Outputs: 12 to 24 VDC, 0.3 A; 32 outputs Sourcing
MIL connector Inputs: 24 VDC, 16 inputs Outputs: 24 VDC, 0.5 A; 16 outputs Load-short circuit protection
TTL I/O Units
MIL connector Inputs: TTL (5 VDC), 32 inputs Outputs: TTL (5 VDC, 35 mA), 32 outputs
B7A Interface Units
32 inputs, 32 outputs
*1 The cable-side connector is not provided with Units equipped with cables. Purchase the connector separately (Refer to 5-3-3 Wiring Basic I/O Units with Connectors.), or use an OMRON Connector- Terminal Block Conversion Unit or I/O Terminal (Refer to 5-3-4 Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals.).
CJ2 CPU Unit Hardware User’s Manual
2-17
2 2-1-4 Configuration Units
Number of bits allocated
Specifications
2-1 Basic System Configuration
Mixed I/O Units
Page 88
2 Basic System Configuration and Devices z CJ-series Special I/O Units
Type
Special I/O Units
Name
Specifications
Model
Number of words allocated (CIO 2000 to CIO 2959)
Number of words allocated (D20000 to D29599)
Unit No.
Number of moun table Units
Current consumption (A) 5 VDC
24 VDC
Weight
General-purpose Universal Analog Input Unit
4 inputs, fully universal
CJ1W-AD04U
10 words
100 words
0 to 95
40 Units
0.32
---
150 g max.
Analog Input Units
8 inputs (4 to 20 mA, 1 to 5 V, etc.)
CJ1W-AD081-V1
10 words
100 words
0 to 95
40 Units
0.42
---
140 g max.
4 inputs (4 to 20 mA, 1 to 5 V, etc.)
CJ1W-AD041-V1
10 words
100 words
0 to 95
40 Units
0.42
---
140 g max.
4 inputs (4 to 20 mA, 1 to 5 V, etc.)
CJ1W-AD042
10 words
100 words
0 to 95
40 Units
0.52
---
150 g max.
4 outputs (1 to 5 V, 4 to 20 mA, etc.)
CJ1W-DA041
10 words
100 words
0 to 95
40 Units
0.12
---
150 g max.
2 outputs (1 to 5 V, 4 to 20 mA, etc.)
CJ1W-DA021
10 words
100 words
0 to 95
40 Units
0.12
---
150 g max.
8 outputs (1 to 5 V, 0 to 10 V, etc.)
CJ1W-DA08V
10 words
100 words
0 to 95
40 Units
0.14
---
150 g max.
8 outputs (4 to 20 mA)
CJ1W-DA08C
10 words
100 words
0 to 95
40 Units
0.14
---
150 g max.
4 outputs (1 to 5 V, 0 to 10 V, etc.)
CJ1W-DA042V
10 words
100 words
0 to 95
40 Units
0.40
---
150 g max.
4 inputs (1 to 5 V, 4 to 20 mA, etc.)
CJ1W-MAD42
10 words
100 words
0 to 95
40 Units
0.58
---
150 g max.
Analog Output Units
Analog I/O Unit
2 outputs (1 to 5 V, 4 to 20 mA, etc.)
2-18
Isolated-type High-resolution Universal Input Unit
4 inputs, fully universal Resolution: 1/256,000, 1/64,000, 1/16,000
CJ1W-PH41U
10 words
100 words
0 to 95
40 Units
0.30
---
150 g max.
Isolated-type Thermocouple Input Units
4 thermocouple inputs
CJ1W-PTS51
10 words
100 words
0 to 95
40 Units
0.25
---
150 g max.
2 thermocouple inputs
CJ1W-PTS15
10 words
100 words
0 to 95
40 Units
0.18
---
150 g max.
Isolated-type Resistance Thermometer Input Units
4 resistance thermometer inputs
CJ1W-PTS52
10 words
100 words
0 to 95
40 Units
0.25
---
150 g max.
2 resistance thermometer inputs
CJ1W-PTS16
10 words
100 words
0 to 95
40 Units
0.18
---
150 g max.
Direct Current Input Unit
DC voltage or DC current, 2 inputs
CJ1W-PDC15
10 words
100 words
0 to 95
40 Units
0.18
---
150 g max.
Temperature Control Units
4 control loops, thermocouple inputs, NPN outputs
CJ1W-TC001
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
4 control loops, thermocouple inputs, PNP outputs
CJ1W-TC002
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
2 control loops, thermocouple inputs, NPN outputs, heater burnout detection
CJ1W-TC003
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
2 control loops, thermocouple inputs, PNP outputs, heater burnout detection
CJ1W-TC004
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
CJ2 CPU Unit Hardware User’s Manual
Page 89
2 Basic System Configuration and Devices
Special I/O Units
Name
Temperature Control Units
Model
Unit No.
Number of moun table Units
Current consumption (A) 5 VDC
24 VDC
Weight
4 control loops, temperature- resistance thermometer inputs, NPN outputs
CJ1W-TC101
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
4 control loops, temperature- resistance thermometer inputs, PNP outputs
CJ1W-TC102
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
2 control loops, temperature-resistance thermometer inputs, NPN outputs, heater burnout detection
CJ1W-TC103
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
2 control loops, temperature-resistance thermometer inputs, PNP outputs, heater burnout detection
CJ1W-TC104
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.25
---
150 g max.
1 axis, pulse output; open collector output
CJ1W-NC113
10 words
100 words
0 to 95
40 Units
0.25
---
100 g max.
2 axes, pulse outputs; open collector outputs
CJ1W-NC213
10 words
100 words
0 to 95
40 Units
0.25
---
100 g max.
CJ1WNC214*1*2
18 words*3
None
0 to 94 (uses words for 2 unit numbers)
5 Units/ Rack
0.27
---
170 g max.
CJ1W-NC413
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.36
---
150 g max.
CJ1WNC414*1*2
18 words*3
None
0 to 94 (uses words for 2 unit numbers)
5 Units/ Rack
0.31
---
220 g max.
1 axis, pulse output; line driver output
CJ1W-NC133
10 words
100 words
0 to 95
40 Units
0.25
---
100 g max.
2 axes, pulse outputs; line driver outputs
CJ1W-NC233
10 words
100 words
0 to 95
40 Units
0.25
---
100 g max.
CJ1WNC234*1*2
18 words*3
None
0 to 94 (uses words for 2 unit numbers)
5 Units/ Rack
0.27
---
170 g max.
CJ1W-NC433
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.36
---
150 g max.
CJ1WNC434*1*2
18 words*3
None
0 to 94 (uses words for 2 unit numbers)
5 Units/ Rack
0.31
---
220 g max.
CJ1W-SP001
None
None
---
---
---
---
50 g max.
4 axes, pulse outputs; open collector outputs
4 axes, pulse outputs; line driver outputs
Space Unit*4
CJ2 CPU Unit Hardware User’s Manual
2-19
2 2-1-4 Configuration Units
Position Control Units
Specifications
Number of words allocated (D20000 to D29599)
2-1 Basic System Configuration
Type
Number of words allocated (CIO 2000 to CIO 2959)
Page 90
2 Basic System Configuration and Devices
Type
Special I/O Units
*1
*2 *3
Name
ID Sensor Units
Specifications
Model
Number of words allocated (CIO 2000 to CIO 2959)
Number of words allocated (D20000 to D29599)
Unit No.
Number of moun table Units
Current consumption (A) 5 VDC
24 VDC
Weight
V600-series singlehead type
CJ1W-V600C11
10 words
100 words
0 to 95
40 Units
0.26
0.12
120 g max.
V600-series two-head type
CJ1W-V600C12
20 words
200 words
0 to 94 (uses words for 2 unit numbers)
40 Units
0.32
0.24
130 g max.
V680-series singlehead type
CJ1W-V680C11
10 words
100 words
0 to 95
40 Units
0.26
0.13
120 g max.
V680-series two-head type
CJ1W-V680C12
20 words
200 words
0 to 94
40 Units
0.32
0.26
130 g max.
High-speed Counter Unit
Number of counter channels: 2, Maximum input frequency: 500 kHz, line driver compatible*5
CJ1W-CT021
40 words
400 words
0 to 92 (uses words for 4 unit numbers)
24 Units
0.28
---
100 g max.
CompoBus/S Master Units
CompoBus/S remote I/O, 256 bits max.
CJ1W-SRM21
10 words or 20 words
None
0 to 95 or 0 to 94
40 Units
0.15
---
66 g max.*6
CompoNet Master Unit
CompoNet remote I/O
CJ1W-CRM21
Communications mode No. 0: 128 inputs/ 128 outputs for Word Slaves
20 words
None
0 to 94 (uses words for 2 unit numbers)
40 Units
0.40
---
Communications mode No. 1: 256 inputs/ 256 outputs for Word Slaves
40 words
None
0 to 92 (uses words for 4 unit numbers)
24 Units
0.40
---
Communications mode No. 2: 512 inputs/ 512 outputs for Word Slaves
80 words
None
0 to 88 (uses words for 8 unit numbers)
12 Units
0.40
---
Communications mode No. 3: 256 inputs/ 256 outputs for Word Slaves and 128 inputs/ 128 outputs for Bit Slaves
80 words
None
0 to 88 (uses words for 8 unit numbers)
12 Units
0.40
---
Communications mode No. 8: 1,024 inputs/ 1,024 outputs for Word Slaves and 256 inputs/ 256 outputs for Bit Slaves maximum
10 words
Depends on setting
0 to 95 uses words for 1 unit number)
40 Units
0.40
---
130 g max.
With a CJ2 CPU Unit, up to 10 Configuration Units can be connected in the CPU Rack and in each Expansion Rack. The CJ1W-NC@@4, however, must be counted as two Units. Configure the Units to satisfy the following formula. Number of CJ1W-NC@@4 Units × 2 + Number of other Units ≤ 10 For example, if five CJ1W-NC@@4 Units are connected to one Rack, no other Units can be connected. The Units must be mounted on the CPU Rack to use synchronous unit operation.
*4
In addition to the words allocated in the Special I/O Unit Area, up to 144 words are allocated according to the number of axes and functions uses. Word allocations are set using the CX-Programmer. The Space Unit is for Position Control Units.
*5
If interrupts to the CPU Unit are used, mount the Interrupt Input Unit in one of the following slots on the CPU Rack.
*6
• CJ2H-CPU6@-EIP: Slots 0 to 3 • CJ2H-CPU6@ or CJ2M-CPU@@: Slots 0 to 4 Includes the weight of accessory connectors.
2-20
CJ2 CPU Unit Hardware User’s Manual