Page 91
2 Basic System Configuration and Devices
Type
CPU Bus Units*1
Name
Specifications
Model
Number of words allocated (CIO 1500 to CIO 1899)
Unit No.
Current consumption (A)
Maximum number of Units*1
5 VDC
24 VDC
Weight
High-speed Analog Input Unit
4 inputs: 80 µs/2 inputs, 160 µs/4 inputs
CJ1W-ADG41*2
25 words
0 to F
16 Units*3
0.65
---
150 g max.
Controller Link Units
Wired data links
CJ1W-CLK23
25 words
0 to F
8 Units
0.35
---
110 g max.
Serial Communications Units
One RS-232C port and one RS-422A/485 port
CJ1W-SCU41-V1
25 words
0 to F
16 Units*3
0.38*4
---
110 g max.
Two RS-232C ports
CJ1W-SCU21-V1
0.28*4
Two RS-422A/485 ports
CJ1W-SCU31-V1
0.38
Two RS-232C ports High-speed models
CJ1W-SCU22
Two RS-422A/485 ports High-speed models
2 160 g max.
CJ1W-SCU32
0.4
120 g max.
One RS-232C port and one RS-422A/485 port High-speed models
CJ1W-SCU42
0.36*4
140 g max.
Ethernet Units
100Base-TX, FINS communications, socket service, FTP server, and mail communications
CJ1W-ETN21
25 words
0 to F
4 Units
0.37
---
100 g max.
EtherNet/IP Unit
Tag data links, FINS communications, CIP message communications, FTP server, etc.
CJ1W-EIP21
25 words
0 to F
*5
0.41
---
94 g max.
FL-net Unit
100Base-TX cyclic transmissions and message transmissions
CJ1W-FLN22
25 words
0 to F
4 Units
0.37
---
100 g max.
DeviceNet Unit
DeviceNet remote I/O, 2,048 points; Both Master and Slave functions, Automatic allocation possible without Configurator
CJ1W-DRM21
25 words*6
0 to F
16 Units*3
0.29
---
118 g max.*7
EtherCAT-compatible Position Control Units*8
2 servo axes
CJ1W-NC281
25 words
0 to F
16 Units*3
0.46
---
110 g max.
4 servo axes
CJ1W-NC481
8 servo axes
CJ1W-NC881
16 servo axes
CJ1W-NCF81
4 servo axes and 64 I/O slaves
CJ1W-NC482
8 servo axes and 64 I/O slaves
CJ1W-NC882
Position Control Units supporting MECHATROLINK-II communications
MECHATROLINK-II, 16 axes max.
CJ1W-NCF71 (-MA)
25 words
0 to F
16 Units*3
0.36
---
95 g max.
Motion Control Units supporting MECHATROLINK-II communications
MECHATROLINK-II, Real axes: 30 max., Virtual axes: 2 max., Special motion control language
CJ1W-MCH71
25 words
0 to F
3 Units/Rack
0.60
---
210 g max.
SYSMAC SPU Unit (Highspeed Storage and Processing Unit)
One CF card type I/II slot (used with OMRON HMC-EF@@@ Memory Card), one Ethernet port
CJ1W-SPU01V2*10
0.56
---
180 g max.
CJ2 CPU Unit Hardware User’s Manual
*9
Not used.
0 to F
16 Units*3
2-21
2-1-4 Configuration Units
0.28*4
16 Units*3
2-1 Basic System Configuration z CJ-series CPU Bus Units
Page 92
2 Basic System Configuration and Devices
*1 Some CJ-series CPU Bus Units are allocated words in the CPU Bus Unit Setup Area. The system must be designed so that the number of words allocated in the CPU Bus Unit Setup Area does not exceed its capacity. Refer to 4-6-2 CPU Bus Unit Setup Area in CJ2 CPU Unit Software User’s Manual (Cat. No. W473). There may also be limits due to the capacity of the Power Supply Unit that you are using or the maximum number of Units to which memory can be allocated in the CPU But Unit Setup Area. *2 If interrupts to the CPU Unit are used, mount the Interrupt Input Unit in one of the following slots on the CPU Rack. • CJ2H-CPU6@-EIP: Slots 0 to 3 • CJ2H-CPU6@ or CJ2M-CPU@@: Slots 0 to 4 *3 Up to 15 Units can be connected for a CJ2H-CPU6@-EIP or CJ2M-CPU3@ CPU Unit. *4 Increases by 0.15 A/Unit when an NT-AL001 RS-232C/RS-422A Link Adapter is used. Increases by 0.04 A/Unit when a CJ1W-CIF11 RS-422A Converter is used. Increases by 0.20 A/Unit when an NV3W-M@20L Programmable Terminal is used. *5 Up to seven Units can be connected for a CJ2H-CPU6@-EIP CPU Unit, up to eight Units can be connected for a CJ2HCPU6@ CPU Unit, and up to two Units can be connected for a CJ2M CPU Unit. *6 Slave I/O are allocated in DeviceNet Area (CIO 3200 to CIO 3799). *7 Includes the weight of accessory connectors. *8 Only OMNUC G5-series Servo Drives with Built-in EtherCAT can be connected. *9 When mounting to a CJ-series CPU Rack or a CJ-series Expansion Rack, one of these Units uses the space of three Units. *10 Use version 2 or higher of the SYSMAC SPU Unit with a CJ2 CPU Unit.
2-1-5
Calculating Unit Current Consumption The amount of current/power that can be supplied to the Units mounted in a Rack is limited by the capacity of the Rack’s Power Supply Unit. Refer to the following tables when designing your system so that the total current consumption of the mounted Units does not exceed the maximum current for each voltage group and the total power consumption does not exceed the maximum for the Power Supply Unit. For details on calculating the current consumption of Units, refer to 2-1-2 CPU Rack, 2-1-3 Expansion Racks, and 2-1-4 Configuration Units.
Maximum Current and Power Supplied by Power Supply Units The following table shows the maximum currents and power that can be supplied by Power Supply Units in CPU Racks and Expansion Racks. Note 1 When calculating current/power consumption in a CPU Rack, be sure to include the power required by the CPU Unit itself, as well as the I/O Control Unit if one or more Expansion Racks is connected. 2 Be sure to include the power required by the I/O Interface Unit when calculating current/power consumption in an Expansion Rack. Max. current consumption Power Supply Unit
2-22
5-V group (internal logic)
24-V group (relays)
24-V group (service)
Max. total power consumption
CJ1W-PA205R
5.0 A
0.8 A
None
25 W
CJ1W-PA205C
5.0 A
0.8 A
None
25 W
CJ1W-PA202
2.8 A
0.4 A
None
14 W
CJ1W-PD025
5.0 A
0.8 A
None
25 W
CJ1W-PD022
2.0 A
0.4 A
None
19.6 W
CJ2 CPU Unit Hardware User’s Manual
Page 93
2 Basic System Configuration and Devices
Example 1: In this example, the following Units are mounted to a CPU Rack with a CJ1W-PA205R Power Supply Unit. Unit
Model
Voltage group
Quantity
5-V
24-V
CPU Unit
CJ2H-CPU68-EIP 1
0.820 A
---
I/O Control Unit
CJ1W-IC101
0.020 A
---
Input Units
CJ1W-ID211
2
0.080 A
---
CJ1W-ID231
2
0.090 A
---
Output Unit
CJ1W-OC201
2
0.090 A
0.048 A
Special I/O Unit
CJ1W-DA041
1
0.120 A
---
CPU Bus Unit
CJ1W-CLK23
1
0.350 A
---
0.820 A + 0.020 A + 0.080 A × 2 + 0.090 A × 2 + 0.090 A × 2 + 0.120 A + 0.350 A
0.048 A × 2
Result
1.83 A (≤5.0 A)
0.096 A (≤0.8 A)
Calculation
2.51 A × 5 V = 9.15 W
0.096 A × 24 V = 2.304 W
Result
9.15 W + 2.30 W = 11.45 W (≤25 W)
1
Power consumption
2
Example 2: In this example, the following Units are mounted to a CJ-series Expansion Rack with a CJ1W-PA205R Power Supply Unit. Unit
Model
Voltage group
Quantity
5-V
24-V
I/O Interface Unit
CJ1W-II101
1
0.130 A
---
Input Unit
CJ1W-ID211
2
0.080 A
---
Output Unit
CJ1W-OD231
8
0.140 A
---
0.130 A + 0.080 A × 2 + 0.140 A × 8
---
1.41 A (≤5.0 A)
---
Calculation
1.41 A × 5 V = 7.05 W
---
Result
7.05 W (≤25 W)
Current consump- Calculation tion Result Power consumption
CJ2 CPU Unit Hardware User’s Manual
2-23
2-1-5 Calculating Unit Current Consumption
Current consump- Calculation tion
2-1 Basic System Configuration
Example Calculations
Page 94
2 Basic System Configuration and Devices
Additional Information Rack Current Consumption and Width Display To display the current consumption and width of Units connected in the CPU Rack or Expansion Rack, select Current Consumption and Width from the Options Menu in the CJ2 CPU Unit I/O Table Window. Power Supply Unit model
Current Current consumption consumption Total power Width consumption at 5 V at 26/24 V
Indicates long-distance expansion
If the capacity of a Power Supply Unit is exceeded, it will be displayed in red.
2-24
CJ2 CPU Unit Hardware User’s Manual
Page 95
2 Basic System Configuration and Devices
Calculating Power Consumption The ambient operating temperature at the control panel for mounting a CJ-series PLC must be no higher than 55°C. This section describes how to calculate the power consumption of a CPU Rack for use in the thermal design of the control panel.
Calculating Power Consumption Use the following equation to calculate the average power consumption (W) of a CJ-series CPU Rack.
W = W_PLC + W_IO_ONOFF
2-1 Basic System Configuration
2-1-6
2
Basic I/O Unit power consumption Basic PLC power consumption
The basic PLC power consumption is calculated based on the overall power consumption of the PLC and the power conversion rate of the Power Supply Unit. W_PLC = W_unit ÷ η • W_unit: Total power consumption of Units mounted to the CPU Rack. For details on the current consumption and voltage of individual Units, refer to 2-1-4 Configuration Units. • η: Power Supply Unit power conversion rate. The rate is 70% for the CJ Series, so use “0.7” in the calculation.
z Basic I/O Unit Power Consumption (W_IO_ONOFF) The Basic I/O Unit power consumption is the total consumption for the Input Units and the Output Units. • Input Units Rated input voltage × Input current × Number of input points • Output Units Residual voltage × Maximum load current × Number of output points Note For the CJ Series, calculate the residual voltage at 0.1 V.
CJ2 CPU Unit Hardware User’s Manual
2-25
2-1-6 Calculating Power Consumption z Basic PLC Power Consumption (W_PLC)
Page 96
2 Basic System Configuration and Devices
Calculation Examples These examples show how to calculate the power consumption (W) for the following system. CPU Rack
Power Supply Unit CJ2H-CPU68-EIP CPU Unit
Units
Model
CJ1W-MAD42 × 2 Special I/O Units CJ1W-ID261 × 2 CJ1W-OD261 × 2 Basic I/O Units
Quantity
5 VDC
Other
CPU Unit
CJ2H-CPU68-EIP
1 Unit
0.82 A
---
Input Units
CJ1W-ID261
2 Units
0.09 A
Rated input voltage: 24 V Input current: 4.1 mA Number of input points: 64
Output Unit
CJ1W-OD261
2 Units
0.17 A
Residual voltage: 0.1 V Maximum load current: 0.3 A Number of output points: 64
Special I/O Units
CJ1W-MAD42
2 Units
0.58 A
--- z Basic PLC Power Consumption (W_PLC) W_PLC = (0.82 + 0.09 × 2 + 0.17 × 2 + 0.58 × 2) A × 5 V ÷ 0.7= 17.86 W z Basic I/O Unit Power Consumption (W_IO_ONOFF) W_IO_ONOFF = 24 V × 0.0041 A x 128 points + 0.1 × 0.3 A × 128 points = 16.43 W z Average Power Consumption (W) W = W_PLC + W_IO_ONOFF = 34.29 W
2-26
CJ2 CPU Unit Hardware User’s Manual
Page 97
2 Basic System Configuration and Devices
Expanded System Configuration This section describes the system configurations that can be connected by using the serial port that is built into the CJ2 CPU Unit, along with Communications Units and other Configuration Units.
2-2-1
Serial Communications This expanded system can be connected via the CJ2 CPU Unit's built-in serial communications port or a Serial Communications Unit. Various protocols, including Host Link and NT Link, can be used with the serial communications port. A particular protocol can be supported by switching the mode of the serial communications port.
Note Protocol macros are supported only for Serial Communications Units. 15 Serial Communications Units max.
CPU Unit SYSMAC CJ2H CPU64-EIP
RUN ERR/ ALM
PROGRAMMABLE CONTROLLER
INH PRPHL COMM BKUP
MS NS COMM 100M 10M
SCU41 RUN
ERC
RDY
ERH
SD1
RD1
SD2
RD2
TERM OFF
ON
WIRE 2
4
TER1
UNIT NO.
OPEN
MCPWR BUSY
PORT1 (RS422 /485)
SCU41 RUN
ERC
RDY
ERH
SD1
RD1
SD2
RD2
TERM OFF
ON
WIRE 2
4
TER1
UNIT NO.
PORT1 (RS422 /485)
SCU41 RUN
ERC
RDY
ERH
SD1
RD1
SD2
RD2
TERM OFF
ON
WIRE 2
4
TER1
Communications Port 1
UNIT NO.
PORT1 (RS422 /485)
PERIPHERAL
Serial port (RS-232C) PORT
PORT2
PORT2
PORT2
Communications Port 2
Precautions for Correct Use A Serial Option Board is required to use a serial communications for the CJ2M-CPU3@. Refer to Serial Option Boards on page 2-7 for information on Serial Option Boards.
CJ2 CPU Unit Hardware User’s Manual
2-27
2 2-2-1 Serial Communications
For details on the serial communications modes that are supported, refer to 11-2 Serial Communications in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).
2-2 Expanded System Configuration
2-2
Page 98
2 Basic System Configuration and Devices
System Configuration Example The host computer or a Programming Device, such as the CX-Programmer, is connected via the serial port on the CPU Unit or, with the CJ2M-CPU3@, on the Serial Option Board. In addition, up to 15 Serial Communications Units can be connected to a single CPU Unit, making it possible to configure a flexible serial communications system by connecting devices with RS-232C or RS-422/485 ports (such as PLCs from other manufacturers, temperature controllers, bar code readers, ID systems, personal computers, board computers, and components). CX-Programmer or host computer PT
NT Link Serial Communications Units CPU Unit
RS-232C
CompoWay/F master
*1
Modbus master
Peripheral Bus (Toolbus)
Host Link slave
*2
Serial PLC Link
*3
CJ2M, CJ1M, CP1H, CP1L, or CP1E CPU Unit
Host Link master
RS-232C
Protocol macro
*4
*4 *4
Device supporting CompoWay/F Device supporting Modbus CPU Unit Host Link slave
No protocol
: Protocol *1 Serial port (RS-232C): A serial port is built into only the CJ2H CPU Units and the CJ2M-CPU1@ CPU Units. *2 Serial Option Board: A Serial Option Board can be mounted only to a CJ2M-CPU3@ CPU Unit.
General-purpose external device (e.g., such as a PLC from other manufacturer, temperature controller, or bar code reader)
*3 Serial PLC Links are supported only by CJ2M CPU Units. *4 This is connected using the Serial Gateway. The Serial Gateway is supported for Serial Communications Units with unit version 1.2 or later.
For details on the protocol modes that can be selected for each port, refer to 11-2-1 Overview of Serial Communications in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). Additional Information Use the Peripheral Bus to connect the CJ2 CPU Unit to the CX-Programmer via serial communications.
2-28
CJ2 CPU Unit Hardware User’s Manual
Page 99
2 Basic System Configuration and Devices
2-2-2
Communications Networks
Communications Network Systems
EtherNet/IP, Ethernet
EtherNet/IP Unit Ethernet Unit *1: The EtherNet/IP port built into the CJ2H-CPU6@-EIP provides the same performance and functions as a CJ1W-EIP21 EtherNet/IP Unit. The EtherNet/IP port built into the CJ2M-CPU3@ provides very different performance. Controller Link Units Built-in EtherNet/IP port*1
2 2-2-2 Communications Networks
Connect via the built-in EtherNet/IP port or a EtherNet/IP Unit or Ethernet Unit connected to the CPU Unit.
Information network
The CJ Series supports the following communications networks. Select the appropriate network according to the applications. For details on communications networks, refer to 11-3 Communications Networks in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).
Configurator
Connect by connecting a Controller Link Unit to the CPU Unit. It is also possible to communicate with a personal computer in which a Controller Link Support Board is installed.
DeviceNet
Control network
Controller Link Support Board
Controller Link
CompoNet Connect by connecting a DeviceNet Unit to the CPU Unit. It is also possible to connect to various types of slaves.
CJ2 CPU Unit Hardware User’s Manual
2-2 Expanded System Configuration
‘
Slaves Connect by connecting a CompoNet Unit. It is also possible to connect to various types of slaves.
2-29
Page 100
2 Basic System Configuration and Devices
Communications Network Overview System
Network EtherNet/IP
Function
Communications
Communications Device
Between Host computer and PLC.
FINS message communications
Built-in EtherNet/IP port on CJ2H-CPU6@-EIP or CJ2MCPU3@, or EtherNet/IP Unit
Between PLCs. Between Host computer and Memory Card installed in CPU Unit.
FTP server
Between PLC and personal computer directly connected to the Network.
FINS message communications
RS-232C → Controller Link
Between Host Link computer and PLC on the Network.
Host Link commands and gateway.
RS-232C cables and Controller Link Unit
EtherNet/IP
Between PLCs.
Tag data links
Built-in EtherNet/IP port on CJ2H-CPU6@-EIP, CJ2MCPU3@ or EtherNet/IP Unit
Controller Link
Between PLCs.
FINS message communications
Controller Link Unit
Information networks Controller Link
Data link (offset, simple settings)
Controller Link Support Board or Controller Link Unit
Data link (offset, simple settings) Control networks
DeviceNet DeviceNet
CompoNet
2-30
Between PLC and Network devices (Slaves).
FINS message communications in an open network.
DeviceNet Master Unit and Configurator
Large-capacity remote I/O (fixed or free allocation) in an open network
DeviceNet Master Unit and Configurator
High-speed, multi-point, multinode remote I/O in an open network
CompoNet Master Unit