SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 2 Basic System Configuration and Devices, pages 91 to 100

Pages 91 to 100 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 91

2 Basic System Configuration and Devices

Type

CPU Bus Units*1

Name

Specifications

Model

Number of words allocated (CIO 1500 to CIO 1899)

Unit No.

Current consumption (A)

Maximum number of Units*1

5 VDC

24 VDC

Weight

High-speed Analog Input Unit

4 inputs: 80 µs/2 inputs, 160 µs/4 inputs

CJ1W-ADG41*2

25 words

0 to F

16 Units*3

0.65

---

150 g max.

Controller Link Units

Wired data links

CJ1W-CLK23

25 words

0 to F

8 Units

0.35

---

110 g max.

Serial Communications Units

One RS-232C port and one RS-422A/485 port

CJ1W-SCU41-V1

25 words

0 to F

16 Units*3

0.38*4

---

110 g max.

Two RS-232C ports

CJ1W-SCU21-V1

0.28*4

Two RS-422A/485 ports

CJ1W-SCU31-V1

0.38

Two RS-232C ports High-speed models

CJ1W-SCU22

Two RS-422A/485 ports High-speed models

2 160 g max.

CJ1W-SCU32

0.4

120 g max.

One RS-232C port and one RS-422A/485 port High-speed models

CJ1W-SCU42

0.36*4

140 g max.

Ethernet Units

100Base-TX, FINS communications, socket service, FTP server, and mail communications

CJ1W-ETN21

25 words

0 to F

4 Units

0.37

---

100 g max.

EtherNet/IP Unit

Tag data links, FINS communications, CIP message communications, FTP server, etc.

CJ1W-EIP21

25 words

0 to F

*5

0.41

---

94 g max.

FL-net Unit

100Base-TX cyclic transmissions and message transmissions

CJ1W-FLN22

25 words

0 to F

4 Units

0.37

---

100 g max.

DeviceNet Unit

DeviceNet remote I/O, 2,048 points; Both Master and Slave functions, Automatic allocation possible without Configurator

CJ1W-DRM21

25 words*6

0 to F

16 Units*3

0.29

---

118 g max.*7

EtherCAT-compatible Position Control Units*8

2 servo axes

CJ1W-NC281

25 words

0 to F

16 Units*3

0.46

---

110 g max.

4 servo axes

CJ1W-NC481

8 servo axes

CJ1W-NC881

16 servo axes

CJ1W-NCF81

4 servo axes and 64 I/O slaves

CJ1W-NC482

8 servo axes and 64 I/O slaves

CJ1W-NC882

Position Control Units supporting MECHATROLINK-II communications

MECHATROLINK-II, 16 axes max.

CJ1W-NCF71 (-MA)

25 words

0 to F

16 Units*3

0.36

---

95 g max.

Motion Control Units supporting MECHATROLINK-II communications

MECHATROLINK-II, Real axes: 30 max., Virtual axes: 2 max., Special motion control language

CJ1W-MCH71

25 words

0 to F

3 Units/Rack

0.60

---

210 g max.

SYSMAC SPU Unit (Highspeed Storage and Processing Unit)

One CF card type I/II slot (used with OMRON HMC-EF@@@ Memory Card), one Ethernet port

CJ1W-SPU01V2*10

0.56

---

180 g max.

CJ2 CPU Unit Hardware User’s Manual

*9

Not used.

0 to F

16 Units*3

2-21

2-1-4 Configuration Units

0.28*4

16 Units*3

2-1 Basic System Configuration z CJ-series CPU Bus Units

Page 92

2 Basic System Configuration and Devices

*1 Some CJ-series CPU Bus Units are allocated words in the CPU Bus Unit Setup Area. The system must be designed so that the number of words allocated in the CPU Bus Unit Setup Area does not exceed its capacity. Refer to 4-6-2 CPU Bus Unit Setup Area in CJ2 CPU Unit Software User’s Manual (Cat. No. W473). There may also be limits due to the capacity of the Power Supply Unit that you are using or the maximum number of Units to which memory can be allocated in the CPU But Unit Setup Area. *2 If interrupts to the CPU Unit are used, mount the Interrupt Input Unit in one of the following slots on the CPU Rack. • CJ2H-CPU6@-EIP: Slots 0 to 3 • CJ2H-CPU6@ or CJ2M-CPU@@: Slots 0 to 4 *3 Up to 15 Units can be connected for a CJ2H-CPU6@-EIP or CJ2M-CPU3@ CPU Unit. *4 Increases by 0.15 A/Unit when an NT-AL001 RS-232C/RS-422A Link Adapter is used. Increases by 0.04 A/Unit when a CJ1W-CIF11 RS-422A Converter is used. Increases by 0.20 A/Unit when an NV3W-M@20L Programmable Terminal is used. *5 Up to seven Units can be connected for a CJ2H-CPU6@-EIP CPU Unit, up to eight Units can be connected for a CJ2HCPU6@ CPU Unit, and up to two Units can be connected for a CJ2M CPU Unit. *6 Slave I/O are allocated in DeviceNet Area (CIO 3200 to CIO 3799). *7 Includes the weight of accessory connectors. *8 Only OMNUC G5-series Servo Drives with Built-in EtherCAT can be connected. *9 When mounting to a CJ-series CPU Rack or a CJ-series Expansion Rack, one of these Units uses the space of three Units. *10 Use version 2 or higher of the SYSMAC SPU Unit with a CJ2 CPU Unit.

2-1-5

Calculating Unit Current Consumption The amount of current/power that can be supplied to the Units mounted in a Rack is limited by the capacity of the Rack’s Power Supply Unit. Refer to the following tables when designing your system so that the total current consumption of the mounted Units does not exceed the maximum current for each voltage group and the total power consumption does not exceed the maximum for the Power Supply Unit. For details on calculating the current consumption of Units, refer to 2-1-2 CPU Rack, 2-1-3 Expansion Racks, and 2-1-4 Configuration Units.

Maximum Current and Power Supplied by Power Supply Units The following table shows the maximum currents and power that can be supplied by Power Supply Units in CPU Racks and Expansion Racks. Note 1 When calculating current/power consumption in a CPU Rack, be sure to include the power required by the CPU Unit itself, as well as the I/O Control Unit if one or more Expansion Racks is connected. 2 Be sure to include the power required by the I/O Interface Unit when calculating current/power consumption in an Expansion Rack. Max. current consumption Power Supply Unit

2-22

5-V group (internal logic)

24-V group (relays)

24-V group (service)

Max. total power consumption

CJ1W-PA205R

5.0 A

0.8 A

None

25 W

CJ1W-PA205C

5.0 A

0.8 A

None

25 W

CJ1W-PA202

2.8 A

0.4 A

None

14 W

CJ1W-PD025

5.0 A

0.8 A

None

25 W

CJ1W-PD022

2.0 A

0.4 A

None

19.6 W

CJ2 CPU Unit Hardware User’s Manual

Page 93

2 Basic System Configuration and Devices

Example 1: In this example, the following Units are mounted to a CPU Rack with a CJ1W-PA205R Power Supply Unit. Unit

Model

Voltage group

Quantity

5-V

24-V

CPU Unit

CJ2H-CPU68-EIP 1

0.820 A

---

I/O Control Unit

CJ1W-IC101

0.020 A

---

Input Units

CJ1W-ID211

2

0.080 A

---

CJ1W-ID231

2

0.090 A

---

Output Unit

CJ1W-OC201

2

0.090 A

0.048 A

Special I/O Unit

CJ1W-DA041

1

0.120 A

---

CPU Bus Unit

CJ1W-CLK23

1

0.350 A

---

0.820 A + 0.020 A + 0.080 A × 2 + 0.090 A × 2 + 0.090 A × 2 + 0.120 A + 0.350 A

0.048 A × 2

Result

1.83 A (≤5.0 A)

0.096 A (≤0.8 A)

Calculation

2.51 A × 5 V = 9.15 W

0.096 A × 24 V = 2.304 W

Result

9.15 W + 2.30 W = 11.45 W (≤25 W)

1

Power consumption

2

Example 2: In this example, the following Units are mounted to a CJ-series Expansion Rack with a CJ1W-PA205R Power Supply Unit. Unit

Model

Voltage group

Quantity

5-V

24-V

I/O Interface Unit

CJ1W-II101

1

0.130 A

---

Input Unit

CJ1W-ID211

2

0.080 A

---

Output Unit

CJ1W-OD231

8

0.140 A

---

0.130 A + 0.080 A × 2 + 0.140 A × 8

---

1.41 A (≤5.0 A)

---

Calculation

1.41 A × 5 V = 7.05 W

---

Result

7.05 W (≤25 W)

Current consump- Calculation tion Result Power consumption

CJ2 CPU Unit Hardware User’s Manual

2-23

2-1-5 Calculating Unit Current Consumption

Current consump- Calculation tion

2-1 Basic System Configuration

Example Calculations

Page 94

2 Basic System Configuration and Devices

Additional Information Rack Current Consumption and Width Display To display the current consumption and width of Units connected in the CPU Rack or Expansion Rack, select Current Consumption and Width from the Options Menu in the CJ2 CPU Unit I/O Table Window. Power Supply Unit model

Current Current consumption consumption Total power Width consumption at 5 V at 26/24 V

Indicates long-distance expansion

If the capacity of a Power Supply Unit is exceeded, it will be displayed in red.

2-24

CJ2 CPU Unit Hardware User’s Manual

Page 95

2 Basic System Configuration and Devices

Calculating Power Consumption The ambient operating temperature at the control panel for mounting a CJ-series PLC must be no higher than 55°C. This section describes how to calculate the power consumption of a CPU Rack for use in the thermal design of the control panel.

Calculating Power Consumption Use the following equation to calculate the average power consumption (W) of a CJ-series CPU Rack.

W = W_PLC + W_IO_ONOFF

2-1 Basic System Configuration

2-1-6

2

Basic I/O Unit power consumption Basic PLC power consumption

The basic PLC power consumption is calculated based on the overall power consumption of the PLC and the power conversion rate of the Power Supply Unit. W_PLC = W_unit ÷ η • W_unit: Total power consumption of Units mounted to the CPU Rack. For details on the current consumption and voltage of individual Units, refer to 2-1-4 Configuration Units. • η: Power Supply Unit power conversion rate. The rate is 70% for the CJ Series, so use “0.7” in the calculation.

z Basic I/O Unit Power Consumption (W_IO_ONOFF) The Basic I/O Unit power consumption is the total consumption for the Input Units and the Output Units. • Input Units Rated input voltage × Input current × Number of input points • Output Units Residual voltage × Maximum load current × Number of output points Note For the CJ Series, calculate the residual voltage at 0.1 V.

CJ2 CPU Unit Hardware User’s Manual

2-25

2-1-6 Calculating Power Consumption z Basic PLC Power Consumption (W_PLC)

Page 96

2 Basic System Configuration and Devices

Calculation Examples These examples show how to calculate the power consumption (W) for the following system. CPU Rack

Power Supply Unit CJ2H-CPU68-EIP CPU Unit

Units

Model

CJ1W-MAD42 × 2 Special I/O Units CJ1W-ID261 × 2 CJ1W-OD261 × 2 Basic I/O Units

Quantity

5 VDC

Other

CPU Unit

CJ2H-CPU68-EIP

1 Unit

0.82 A

---

Input Units

CJ1W-ID261

2 Units

0.09 A

Rated input voltage: 24 V Input current: 4.1 mA Number of input points: 64

Output Unit

CJ1W-OD261

2 Units

0.17 A

Residual voltage: 0.1 V Maximum load current: 0.3 A Number of output points: 64

Special I/O Units

CJ1W-MAD42

2 Units

0.58 A

--- z Basic PLC Power Consumption (W_PLC) W_PLC = (0.82 + 0.09 × 2 + 0.17 × 2 + 0.58 × 2) A × 5 V ÷ 0.7= 17.86 W z Basic I/O Unit Power Consumption (W_IO_ONOFF) W_IO_ONOFF = 24 V × 0.0041 A x 128 points + 0.1 × 0.3 A × 128 points = 16.43 W z Average Power Consumption (W) W = W_PLC + W_IO_ONOFF = 34.29 W

2-26

CJ2 CPU Unit Hardware User’s Manual

Page 97

2 Basic System Configuration and Devices

Expanded System Configuration This section describes the system configurations that can be connected by using the serial port that is built into the CJ2 CPU Unit, along with Communications Units and other Configuration Units.

2-2-1

Serial Communications This expanded system can be connected via the CJ2 CPU Unit's built-in serial communications port or a Serial Communications Unit. Various protocols, including Host Link and NT Link, can be used with the serial communications port. A particular protocol can be supported by switching the mode of the serial communications port.

Note Protocol macros are supported only for Serial Communications Units. 15 Serial Communications Units max.

CPU Unit SYSMAC CJ2H CPU64-EIP

RUN ERR/ ALM

PROGRAMMABLE CONTROLLER

INH PRPHL COMM BKUP

MS NS COMM 100M 10M

SCU41 RUN

ERC

RDY

ERH

SD1

RD1

SD2

RD2

TERM OFF

ON

WIRE 2

4

TER1

UNIT NO.

OPEN

MCPWR BUSY

PORT1 (RS422 /485)

SCU41 RUN

ERC

RDY

ERH

SD1

RD1

SD2

RD2

TERM OFF

ON

WIRE 2

4

TER1

UNIT NO.

PORT1 (RS422 /485)

SCU41 RUN

ERC

RDY

ERH

SD1

RD1

SD2

RD2

TERM OFF

ON

WIRE 2

4

TER1

Communications Port 1

UNIT NO.

PORT1 (RS422 /485)

PERIPHERAL

Serial port (RS-232C) PORT

PORT2

PORT2

PORT2

Communications Port 2

Precautions for Correct Use A Serial Option Board is required to use a serial communications for the CJ2M-CPU3@. Refer to Serial Option Boards on page 2-7 for information on Serial Option Boards.

CJ2 CPU Unit Hardware User’s Manual

2-27

2 2-2-1 Serial Communications

For details on the serial communications modes that are supported, refer to 11-2 Serial Communications in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).

2-2 Expanded System Configuration

2-2

Page 98

2 Basic System Configuration and Devices

System Configuration Example The host computer or a Programming Device, such as the CX-Programmer, is connected via the serial port on the CPU Unit or, with the CJ2M-CPU3@, on the Serial Option Board. In addition, up to 15 Serial Communications Units can be connected to a single CPU Unit, making it possible to configure a flexible serial communications system by connecting devices with RS-232C or RS-422/485 ports (such as PLCs from other manufacturers, temperature controllers, bar code readers, ID systems, personal computers, board computers, and components). CX-Programmer or host computer PT

NT Link Serial Communications Units CPU Unit

RS-232C

CompoWay/F master

*1

Modbus master

Peripheral Bus (Toolbus)

Host Link slave

*2

Serial PLC Link

*3

CJ2M, CJ1M, CP1H, CP1L, or CP1E CPU Unit

Host Link master

RS-232C

Protocol macro

*4

*4 *4

Device supporting CompoWay/F Device supporting Modbus CPU Unit Host Link slave

No protocol

: Protocol *1 Serial port (RS-232C): A serial port is built into only the CJ2H CPU Units and the CJ2M-CPU1@ CPU Units. *2 Serial Option Board: A Serial Option Board can be mounted only to a CJ2M-CPU3@ CPU Unit.

General-purpose external device (e.g., such as a PLC from other manufacturer, temperature controller, or bar code reader)

*3 Serial PLC Links are supported only by CJ2M CPU Units. *4 This is connected using the Serial Gateway. The Serial Gateway is supported for Serial Communications Units with unit version 1.2 or later.

For details on the protocol modes that can be selected for each port, refer to 11-2-1 Overview of Serial Communications in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). Additional Information Use the Peripheral Bus to connect the CJ2 CPU Unit to the CX-Programmer via serial communications.

2-28

CJ2 CPU Unit Hardware User’s Manual

Page 99

2 Basic System Configuration and Devices

2-2-2

Communications Networks

Communications Network Systems

EtherNet/IP, Ethernet

EtherNet/IP Unit Ethernet Unit *1: The EtherNet/IP port built into the CJ2H-CPU6@-EIP provides the same performance and functions as a CJ1W-EIP21 EtherNet/IP Unit. The EtherNet/IP port built into the CJ2M-CPU3@ provides very different performance. Controller Link Units Built-in EtherNet/IP port*1

2 2-2-2 Communications Networks

Connect via the built-in EtherNet/IP port or a EtherNet/IP Unit or Ethernet Unit connected to the CPU Unit.

Information network

The CJ Series supports the following communications networks. Select the appropriate network according to the applications. For details on communications networks, refer to 11-3 Communications Networks in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).

Configurator

Connect by connecting a Controller Link Unit to the CPU Unit. It is also possible to communicate with a personal computer in which a Controller Link Support Board is installed.

DeviceNet

Control network

Controller Link Support Board

Controller Link

CompoNet Connect by connecting a DeviceNet Unit to the CPU Unit. It is also possible to connect to various types of slaves.

CJ2 CPU Unit Hardware User’s Manual

2-2 Expanded System Configuration

‘

Slaves Connect by connecting a CompoNet Unit. It is also possible to connect to various types of slaves.

2-29

Page 100

2 Basic System Configuration and Devices

Communications Network Overview System

Network EtherNet/IP

Function

Communications

Communications Device

Between Host computer and PLC.

FINS message communications

Built-in EtherNet/IP port on CJ2H-CPU6@-EIP or CJ2MCPU3@, or EtherNet/IP Unit

Between PLCs. Between Host computer and Memory Card installed in CPU Unit.

FTP server

Between PLC and personal computer directly connected to the Network.

FINS message communications

RS-232C → Controller Link

Between Host Link computer and PLC on the Network.

Host Link commands and gateway.

RS-232C cables and Controller Link Unit

EtherNet/IP

Between PLCs.

Tag data links

Built-in EtherNet/IP port on CJ2H-CPU6@-EIP, CJ2MCPU3@ or EtherNet/IP Unit

Controller Link

Between PLCs.

FINS message communications

Controller Link Unit

Information networks Controller Link

Data link (offset, simple settings)

Controller Link Support Board or Controller Link Unit

Data link (offset, simple settings) Control networks

DeviceNet DeviceNet

CompoNet

2-30

Between PLC and Network devices (Slaves).

FINS message communications in an open network.

DeviceNet Master Unit and Configurator

Large-capacity remote I/O (fixed or free allocation) in an open network

DeviceNet Master Unit and Configurator

High-speed, multi-point, multinode remote I/O in an open network

CompoNet Master Unit

CJ2 CPU Unit Hardware User’s Manual