SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 3 Nomenclature and Functions, pages 101 to 108

Pages 101 to 108 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 101

Nomenclature and Functions 3 This section gives the parts of a CJ2 PLC and describes the functions of the parts.

3-1 CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3-1-1 3-1-2

CPU Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Built-in EtherNet/IP Section (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only) . . . 3-8

3-2 Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 3-2-1 3-2-2 3-2-3

Models and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Installing and Removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14

3-3 Pulse I/O Modules (CJ2M CPU Unit Only) . . . . . . . . . . . . . . . . . . . . . . . . . 3-17 3-3-1 3-3-2

Models and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17 Part Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17

3-4 Serial Option Boards (CJ2M-CPU3@ Only) . . . . . . . . . . . . . . . . . . . . . . . . 3-20 3-4-1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20

3-5 Power Supply Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21 3-5-1 3-5-2 3-5-3

Models and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24 Selecting a Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27

3-6 CJ-series Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28 3-6-1 3-6-2

Basic I/O Units with Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28 Thirty-two/Sixty-four-point Basic I/O Units with Connectors . . . . . . . . . . . . . 3-30

3-7 I/O Control Units and I/O Interface Units . . . . . . . . . . . . . . . . . . . . . . . . . . 3-32 3-7-1 3-7-2

CJ2 CPU Unit Hardware User’s Manual

Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-32 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-32

3-1

Page 102

3 Nomenclature and Functions

3-1

CPU Units

3-1-1

CPU Section

Components and Functions CJ2H-CPU6@-EIP

CJ2H-CPU6@ Inside the battery compartment

7

7

8

8 1

1

SYSMAC CJ2H CPU64-EIP

RUN ERR/ALM

PROGRAMMABLE CONTROLLER

NS

COMM BKUP

COMM 100M

RUN ERR/ALM INH PRPHL

PROGRAMMABLE CONTROLLER

COMM BKUP

10M

OPEN

2

SYSMAC CJ2H CPU64-EIP

MS

INH PRPHL

OPEN

2

MCPWR BUSY

3

9

3

PERIPHERAL

4

MCPWR BUSY

PERIPHERAL

5

4 PORT

PORT

5 11 11 6

10

6

12

CJ2M-CPU3@

10

CJ2M-CPU1@ Inside the battery compartment 7

7

8

8 1

1

2

12

2

9

3

3 4

4

5

5

11 6

11 6

10

13

CP1W-CIF01 RS-232C Option Board

3-2

CP1W-CIF11 or CP1W-CIF12 RS-422A/485 Option Board

CJ2 CPU Unit Hardware User’s Manual

Page 103

3 Nomenclature and Functions

3-3

3 3-1-1 CPU Section

CJ2 CPU Unit Hardware User’s Manual

8. LED Indicators (Refer to the next page.) These indicators show the status of the CPU Unit: • Normal operation • Errors • Output OFF status • Communications status for the peripheral (USB) and RS232C ports • Backup status between RAM and built-in flash memory 9. DIP Switch (Refer to a following page.) Sets operations, such as user memory protection, automatic program transfer by Memory Card, serial port communications mode, and simple backup. 10. RS-232C Serial Port (Refer to A-4 Connecting to a Serial Port on the CPU Unit.) Connected to Programming Devices, Host Computers, general-purpose external devices, Programmable Terminals, and other devices. 11. Connector Connected to the next Unit. 12. Built-in EtherNet/IP Section (CJ2H-CPU6@-EIP only) Refer to 3-1-2 Built-in EtherNet/IP Section (CJ2HCPU6@-EIP only) for information on the built-in EtherNet/IP Section. 13. Serial Option Boards (CJ2M-CPU3@ Only) An Option Board can be connected to the slot. • CP1W-CIF01 RS-232C Option Board • RS-422A/485 Option Board (CP1W-CIF11 (Maximum transmission distance: 50 m) or CP1W-CIF12 (Maximum transmission distance: 500 m))

3-1 CPU Units

1. Memory Card Indicators (Refer to 3-2 Memory Card.) Indicates the Memory Card status (access and power supply). 2. Simple Backup/Memory Card Power Supply Switch (Refer to 3-2 Memory Card.) Used to back up Memory Card data or turn OFF the power when removing the Memory Card. 3. Peripheral (USB) Port Connected to Programming Devices, such as the CXProgrammer 4. Memory Card Connector (Refer to 3-2 Memory Card.) Connects the Memory Card to the CPU Unit. 5. Memory Card (Refer to 3-2 Memory Card.) All CPU Unit data can be copied to a Memory Card to back up the data. If a Memory Card Adapter is used, the Memory Card can be mounted in the PCMIA slot in a personal computer. 6. Memory Card Eject Button (Refer to 3-2 Memory Card.) Press the eject button to remove the Memory Card from the CPU Unit. 7. Slider Secures the CPU Unit to the next Unit.

Page 104

3 Nomenclature and Functions

CPU Unit Status Indicators

7-segment display and indicators for EtherNet/IP port (Refer to 3-1-2 Built-in EtherNet/IP Section.) (CJ2H-CPU6@-EIP and CJ2M-CPU3@ only.)

Indicators on front of CPU Unit

The CJ2 CPU Unit status can be checked with the indicators at the top of the front panel of the Unit. The following table describes these indicators. Indicator RUN

ERR/ALM

Color Green

Red

Status

Meaning

ON

Lights when the PLC is operating normally in MONITOR or RUN mode. The program is being executed.

Flashing

System download mode error or DIP switch settings error.

OFF

PLC has stopped operating while in PROGRAM mode, or has stopped operating due to a fatal error, or is downloading data from the system.

ON

A fatal error (including FALS(007) instruction execution) or a hardware error (watchdog timer error) was found in self-diagnosis. The CJ2 CPU Unit will stop operating, and the outputs from all Output Units will turn OFF.

Flashing

A non-fatal error was found (including FAL(006) instruction execution) in the self-diagnosis. The CJ2 CPU Unit will continue operating.

INH

Yellow

OFF

The CJ2 CPU Unit is operating normally.

ON

Output OFF Bit (A500.15) has been turned ON. The outputs from all Output Units will turn OFF.

PRPHL

COMM*1

Yellow

Yellow

OFF

Output OFF Bit (A500.15) has been turned OFF.

Flashing

The CJ2 CPU Unit is communicating (sending or receiving) via the peripheral (USB) port.

OFF

The CJ2 CPU Unit is not communicating via the peripheral (USB) port.

Flashing

The CJ2 CPU Unit is communicating (sending or receiving) via the serial port (RS-232C).

OFF

The CJ2 CPU Unit is not communicating via the serial port (RS-232C).

BKUP

Yellow

ON

User program and parameter area data is being backed up to flash memory in the CPU Unit or being restored from flash memory after the power supply to the PLC was turned ON. *2

OFF

Data is not being written to flash memory.

*1 The CJ2M-CPU3@ does not have this indicator. *2 Do not turn OFF the power supply to the PLC while this indicator is lit.

3-4

CJ2 CPU Unit Hardware User’s Manual

Page 105

3 Nomenclature and Functions

Memory Card Indicators The status of a Memory Card mounted in the CJ2 CPU Unit can be checked with the indicators in the middle of the front panel of the Unit. The following table describes these indicators. Indicator MCPWR

Color Green

Status

Meaning

Lit

Power is being supplied to the Memory Card.

Flashing

Flashes once: Simple backup read, write, or verify normal Flashes five times: Simple backup read malfunction

Not lit BUSY

Yellow

Power is not being supplied to the Memory Card.

Flashing

Memory Card is being accessed.

Not lit

Memory Card is not being accessed.

3-1 CPU Units

Flashes continuously: Simple backup write or verify malfunction

3

OPEN

MCPWR

3-1-1 CPU Section

BUSY

PERIPHERAL

CJ2 CPU Unit Hardware User’s Manual

3-5

Page 106

3 Nomenclature and Functions

DIP Switch

8

7

6

5

4

3

2

1

ON

Pin no. SW1

SW2

Usage Used to prevent programs from being accidentally overwritten from Programming Devices (including the CX-Programmer). Set to ON to read the program (AUTOEXEC.OBJ file) and parameter area (AUTOEXEC.STD file) from the Memory Card to the CPU Unit when power is turned ON.*2

Setting

Not used.

Default

Writing disabled for user program memory.*1

OFF

Writing enabled for user program memory.

ON

The user program is automatically transferred from the Memory Card when power is turned ON.

OFF

The user program is not automatically transferred from the Memory Card when power is turned ON.

---

---

OFF

Used to store the programs in the Memory Card to switch operations, or to automatically transfer programs at startup (Memory Card ROM operation).*3 SW3

Function

ON

OFF

OFF

SW4

Not used.

---

---

OFF

SW5

Set to ON to automatically detect the baud rate of the CX-Programmer (peripheral bus only) when using the serial port (RS-232C).*4, *5

ON

Serial port (RS-232C) communications condition: Automatically detect CX-Programmer (peripheral bus only) baud rate.

OFF

OFF

Serial port (RS-232C) communications condition: According to CX-Programmer communications settings in PLC Setup. (Refer to Table 1.)

Set pin 6 to ON or OFF and use A395.12 in the program to create a user-defined condition without using an Input Unit.

ON

User-defined pin. Turns ON the User DIP Switch Pin Flag (A395.12).

OFF

User-defined pin. Turns OFF the User DIP Switch Pin Flag (A395.12).

SW7

Set the simple backup type. (Refer to Table 2 below.)

---

Specifies the simple backup type.

OFF

SW8

---

Always OFF.

---

OFF

SW6

OFF

*1 The following data cannot be overwritten when pin 1 is ON: • All parts of the user program (programs in all tasks) • All data in the parameter area (such as the PLC Setup and I/O table) When pin 1 is ON, the user program and parameter area will not be cleared when the memory clear operation is performed from a Programming Device. *2 I/O memory files (AUTOEXEC.IOM and ATEXEC@@.IOM) are automatically transferred when power is turned ON if pin 2 is set to ON. Both the program (AUTOEXEC.OBJ) and parameter area (AUTOEXEC.STD) files must be stored on the Memory Card. It is not necessary for the I/O memory files (AUTOEXEC.IOM and ATEXEC@@.IOM) to be stored on the Memory Card. *3 When pin 7 is ON, simple backup reading from the Memory Card is given priority, so even if pin 2 is ON, the user program is not automatically transferred from the Memory Card when power is turned ON. *4 Connecting to the PLC is not possible from the CX-One Support Software using SYSMAC WAY even if pin 5 on the DIP switch is OFF and the PLC Setup is set to the Host Link protocol (i.e., the default setting). *5 With the CJ2M-CPU3@, pin 5 can be set only when a Serial Option Board is mounted.

3-6

CJ2 CPU Unit Hardware User’s Manual

Page 107

3 Nomenclature and Functions

Table 1 Setting

Pin 5 of DIP switch on front panel

Connection 1. Peripheral bus (automatic detection)

PLC Setup (Serial port (RS-232C))*1

ON

---

2. Peripheral bus

OFF (default)

Peripheral bus

3. Host Link*2

OFF (default)

Host Link (default)

OFF (default)

NT Link

5. No-protocol

OFF (default)

No-protocol

6. Serial Gateway

OFF (default)

Serial Gateway

3-1 CPU Units

4. NT Link

*1 Set using the CX-Programmer. *2 Connection is not possible from CX-One Support Software using the SYSMAC WAY protocol.

3

Table 2 DIP Switch

Backing up all PLC data on the Memory Card:

SW7 ON

Memory Card

Required operation Press the Memory Card Power Supply Switch for 3 s.

All PLC data Backup

Restoring all PLC data from the Memory Card:

Turn ON the power to the PLC.*1

Memory Card All PLC data Restore

Comparing the Memory Card and the CPU Unit:

OFF

Press the Memory Card Power Supply Switch for 3 s.

Memory Card All PLC data Compare

*1 This operation is given priority over automatic transfer at startup (pin 2 set to ON). Note After reading data from the Memory Card to the CPU Unit using the simple backup operation, the CPU Unit will remain in PROGRAM mode and no operations in any other mode will be possible. To switch to RUN or MONITOR mode, turn OFF the power, turn OFF pin 7, turn the power back ON, and use a Programming Device to change the operating mode.

CJ2 CPU Unit Hardware User’s Manual

3-7

3-1-2 Built-in EtherNet/IP Section (CJ2H-CPU6@-EIP only)

Simple backup type

Page 108

3 Nomenclature and Functions

3-1-2

Built-in EtherNet/IP Section (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only) This section describes the components related to the EtherNet/IP port section that is built into the CJ2H-CPU6@-EIP and CJ2M-CPU3@. Additional Information The built-in EtherNet/IP port on the CJ2H-CPU6@-EIP provides the same performance and functions as a CJ1W-EIP21 EtherNet/IP Unit. (The performance of the built-in EtherNet/IP port on the CJ2M-CPU3@ is very different.) Set the unit number and node address with the rotary switches on the front panel of the CPU Unit, and set the communications parameters with the Edit Parameters menu command for the Special I/O Unit. For details on the Edit Parameters, refer to 8-2 Setting CPU Bus Units and Special I/O Units in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). For details on specifications and settings for the built-in EtherNet/IP port, refer to the CS/CJ Series EtherNet/IP Units Operation Manual (Cat. No. W465).

Nomenclature and Functions CJ2H-CPU6@-EIP

CJ2M-CPU3@ Display and indicators for built-in EtherNet/IP port

SYSMAC CJ2H CPU64-EIP

MS NS COMM 100M

PROGRAMMABLE CONTROLLER

10M OPEN

Rotary switches

MCPWR BUSY

PERIPH ERAL

PORT

Built-in EtherNet/IP port (Refer to 5-3-6 Wiring with Ethernet Cable.)

Display and Indicators for Built-in EtherNet/IP Port With a CJ2 CPU Unit, Ethernet node status and Ethernet network status can be monitored by checking the display and indicators at the upper right of the front of the CPU Unit.

Seven-segment display and indicators for built-in EtherNet/IP port

3-8

CJ2 CPU Unit Hardware User’s Manual