Page 109
3 Nomenclature and Functions z Status Indicators: MS, NS, COMM, 100M, and 10M
The MS (Module Status) indicator indicates the status of the built-in EtherNet/IP port itself and the NS (Network Status) indicator indicates the status of the network. The COMM, 100M, and 10M indicators indicate the status of Ethernet communications.
Refer to SECTION 6 Troubleshooting for details on using these indicators for troubleshooting. Indicator MS
Name Module Status
Color
Status
Red
Lit
3-1 CPU Units
The MS and NS indicators can be green or red. The COMM, 100M, and 10M indicators are yellow. These indicators can be lit, flashing, or not lit. The following table shows the meaning of these indicator conditions.
Meaning
3
Fatal error
Flashing Recoverable error
Network Status
Lit
Normal
---
Not lit
Power supply OFF
Red
Lit
Fatal error
Flashing Recoverable error Green
Lit
Tag data link and message connections established
Flashing Tag data link and message connections not established COMM
Communication
---
Not lit
Offline or power supply OFF
Yellow
Lit
Transferring data
Not lit
Not transferring data
Lit
100Base-TX link established
Not lit
100Base-TX link not established
Lit
10Base-TX link established
Not lit
10Base-TX link not established
100M
100 Mbps
Yellow
10M
10 Mbps
Yellow z Seven-segment Display
When the power supply to the PLC is turned ON or the CPU Unit is reset, all of the segments will flash twice, and then the IP address set for the built-in EtherNet/IP port will be displayed on the 7segment display from right to left. After the entire IP address is displayed, the lower 8 bits of the IP address (node address) will be displayed in hexadecimal.
CJ2 CPU Unit Hardware User’s Manual
3-9
3-1-2 Built-in EtherNet/IP Section (CJ2H-CPU6@-EIP only)
NS
Green
Page 110
3 Nomenclature and Functions
For example, the display will change as follows if the IP address is 192.168.250.10: The IP address is displayed in decimal, flowing from right to left.
Example: : 192.
: 168.
: 250.
: 10
If the Unit is operating normally, the rightmost digits of the Unit's IP address is displayed in hexadecimal. Flashing: The tag data links are stopped. Lit: The tag data links are operating.
: 0A ( “0A” is the hexadecimal display for the final row, 10, in the IP address of the local Unit.)
If an error occurs, the error code will be displayed alternately with the rightmost byte of the affected device’s IP address. For details on error codes, refer to 6-2-2 Checking Error Status at the EtherNet/IP Port Seven-segment Display. The following examples show the displays for errors. • A d6 error (failure to connect) has occurred in communications with IP address 192.168.250.8. • A d6 error (failure to connect) has occurred in communications with IP address 192.168.250.9. • A d5 error (verification error; target missing) has occurred in communications with IP address 192.168.250.40. • A C6 error (multiple switches ON) and an EA error (EtherNet/IP expansion setting error) have occurred at the built-in EtherNet/IP port (192.168.250.10). Information on errors that occur in communications with the target node, along with the last digits of the Unit’ s IP address, are displayed in hexadecimal.
Example: : Er d6 IP 08
: IP d6 IP 09
: Er d5 IP 40
: Er c6
: Er EA Displays errors that occurred within the Unit.
: IP 0A The last digits of the Unit’ s IP address is displayed in hexadecimal.
3-10
CJ2 CPU Unit Hardware User’s Manual
Page 111
3 Nomenclature and Functions
• There is no priority to the order in which the errors are displayed. All of the errors are displayed repeatedly in sequence. Left/Right Dot LEDs If an error occurs at multiple devices for which the rightmost 8 bits in the IP addresses are the same, this is indicated by the dots on the right side in display on the target devices. The following examples show the displays for multiple errors. • d6 errors (failure to connect) have occurred in communications with IP address 10.0.1.8. • d6 errors (failure to connect) have occurred in communications with IP address 10.0.2.8. 3-1 CPU Units
3
The unit number and node address for the CJ2 CPU Unit built-in EtherNet/IP port are set using the rotary switches. The unit number and node address are allocated in the same way as for a CPU Bus Unit. According to the unit number that is set, words are automatically allocated in the CIO Area and DM Area. For details, refer to the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).
z Setting the Unit Number Set a unique unit number for the CJ2 CPU Unit built-in EtherNet/IP port. The same unit number cannot be used by any other CPU Bus Unit connected to the CJ2 CPU Unit. Use a small screwdriver to make the setting, and be sure not to damage the rotary switch. The unit number is factory-set to 0.
Setting range 0 to F
Precautions for Correct Use • Always turn OFF the PLC’s power supply before setting the unit number. • When setting the unit number for the first time or when changing the setting, create the PLC’s I/O tables.
CJ2 CPU Unit Hardware User’s Manual
3-11
3-1-2 Built-in EtherNet/IP Section (CJ2H-CPU6@-EIP only)
Rotary Switches
Page 112
3 Nomenclature and Functions z Node Address Setting Switches Set a FINS address for the built-in EtherNet/IP port. With the FINS communications service, multiple EtherNet/IP Units (including the CJ2 Unit built-in EtherNet/IP port) connected by Ethernet are identified by their node addresses. Using the node address switches, set a unique node address in hexadecimal. The same node address cannot be used by any other EtherNet/IP Unit or Ethernet Unit connected on the same Ethernet network. As long as it does not duplicate any other address, the node address can be set from 01 to FE (1 to 254 in decimal). Setting range 01 to FE hex (1 to 254 decimal)
Note The node address is factory-set to 01. With the default setting, the values set on these switches become the last two digits of the built-in EtherNet/IP port’s IP address.
The default IP address is 192.168.250.node_address. With the factory-set node address of 01, the default IP address is 192.168.250.1. The node address can be set to any number in the setting range (01 to FE), as long as the same address is not set on another node in the network. Precautions for Correct Use • Always turn OFF the PLC’s power supply before setting the unit number. • When setting the unit number for the first time or when changing the setting, create the PLC’s I/O tables.
Additional Information • If the node address setting is changed during operation, the MS Indicator will flash red.
z Relationship with IP Address When using the automatic generation method (dynamic/static) for IP address conversion, the rightmost byte of the IP address that is set for the built-in EtherNet/IP port must be set to the same value as the node address. If it cannot be set to the same value as the node address, then the address conversion method must be set to the IP address table method or the IP address + automatic generation method. For details, refer to the CS/CJ Series EtherNet/IP Units Operation Manual (Cat. No. W465).
3-12
CJ2 CPU Unit Hardware User’s Manual
Page 113
3 Nomenclature and Functions
3-2
Memory Card
3-2-1
Models and Specifications
Model number
HMC-EF583
HMC-EF283
HMC-EF183
Memory Card capacity
512 Mbytes
256 Mbytes
128 Mbytes
Common specifications
3-2-2
42.8 × 36.4 × 3.3 mm (W × H × T)
Weight
15 g max.
Current consumption
Approx. 30 mA (when used with PLC)
Environmental specifications
Same as general specifications of PLC
No. of writes
100,000 (guaranteed value)
No. of files writable to root directory
511
File system
FAT16
3 3-2-1 Models and Specifications
Factory specifications
Dimensions
Operating Procedures Memory Card Indicators MCPWR (green): Lit when power is being provided to the Memory Card. BUSY (orange): Flashes while the Memory Card is being accessed.
Simple Backup/Memory Card Power Supply Switch This switch has the following two functions. • Simple Backup To back up all CPU Unit data to the Memory Card, press this switch for 3 s when DIP switch pin 7 is set to ON.
PERIPHERAL
• Turning OFF Power to the Memory Card Press this switch to turn OFF the power before removing the Memory Card.
Memory Card Eject Button
Additional Information Simple Backup The simple backup function copies all CPU Unit data (user program, parameters, and I/O memory) to a Memory Card, without having to use a Programming Device. For details, refer to 8-3 Simple Backup.
CJ2 CPU Unit Hardware User’s Manual
3-2 Memory Card
Use the following OMRON-specified Memory Card. Operation may not be correct if memory cards from other companies are used.
3-13
Page 114
3 Nomenclature and Functions
3-2-3
Installing and Removing
Before Using a Memory Card • Observe the following precautions while the Memory Card is being accessed. The Memory Card may become unusable if these precautions are not followed. • Never turn OFF the PLC while the CPU is accessing the Memory Card. • Never remove the Memory Card while the CPU is accessing the Memory Card. Press the Memory Card power supply switch and wait for the BUSY indicator to go OFF before removing the Memory Card. • Never insert the Memory Card facing the wrong way. If the Memory Card is inserted forcibly, it may become unusable. • To delete all the data on the Memory Card by formatting the Memory Card, insert the Memory Card in the CPU Unit and perform the operation from the CX-Programmer.
Installing the Memory Card
1
Pull the top end of the Memory Card cover forward and remove from the Unit.
2 Insert the Memory Card with the label facing to the left. (Insert with the ∆ on the Memory Card label and the ∆ on the CPU Unit facing each other.)
Product label
3 Push the Memory Card securely into the compartment. If the Memory Card is inserted correctly, the Memory Card eject button will be pushed out.
3-14
CJ2 CPU Unit Hardware User’s Manual
Page 115
3 Nomenclature and Functions
Removing the Memory Card
1
Press the Memory Card power supply switch. Memory Card power supply switch
3-2 Memory Card
3 3-2-3 Installing and Removing
2 Press the Memory Card eject button after the BUSY indicator is no longer lit. The Memory Card will be ejected from the compartment. BUSY indicator
Memory Card eject button
3 Pull out the Memory Card. 4 Install the Memory Card cover when a Memory Card is not being used.
CJ2 CPU Unit Hardware User’s Manual
3-15
Page 116
3 Nomenclature and Functions
Installing the Memory Card into a Personal Computer HMC-AP001 Memory Card Adapter
Memory Card Personal computer PC card slot
3-16
CJ2 CPU Unit Hardware User’s Manual