The text of a manual · part 15 of 48
SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 3 Nomenclature and Functions, pages 117 to 124
Pages 117 to 124 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213
Page 117
3 Nomenclature and Functions
Pulse I/O Modules (CJ2M CPU Unit Only)
3-3-1
Models and Specifications Type of transistor outputs
Model
3-3 Pulse I/O Modules (CJ2M CPU Unit Only)
3-3
Specifications
CJ2M-MD211
Sinking outputs
1 MIL connector
CJ2M-MD212
Sourcing outputs
• 10 inputs (four interrupt/quick-response inputs or two high-speed counter inputs) • 6 outputs (two pulse outputs or two PWM outputs)
Name
Model
MIL Flat Cable Connector for Pulse I/O Modules
XG4M-4030-T
Specifications 40-pin MIL connector, pressurewelded type (This connector is used by user to make a cable.)
(Refer to the 2-1-2 CPU Rack, 5-3 Wiring, or the CJ2M CPU Unit Pulse I/O Module User's Manual (Cat. No. W486) for details.)
3-3-2
Part Names and Functions
Part Names
I/O indicators Indicate the ON/OFF status of the pulse I/O signals.
Pulse I/O MIL connector (40 pins)
CJ2 CPU Unit Hardware User’s Manual
3-17
3-3-1 Models and Specifications
Note Connectors are not provided with Pulse I/O Modules. Purchase the following Connector, an OMRON Cable with Connectors for Connector-Terminal Block Conversion Units, or an OMRON Cable with Connectors for Servo Relay Units.
3
Page 118
3 Nomenclature and Functions
Connecting Pulse I/O Modules to the CPU Unit Up to two Pulse I/O Modules can be connected to a CJ2M CPU Unit. They must be connected immediately to the left of the CPU Unit. The Pulse I/O Module closest to the CPU Unit is Pulse I/O Module 0 and the other one is Pulse I/O Module 1. One Pulse I/O Module
Pulse I/O Module
CJ2M CPU Unit (Standard or Simple Model)
Connected
Pulse I/O Module 0
Two Pulse I/O Modules Pulse I/O Modules
Connected
CJ2M CPU Unit (Standard or Simple Model)
Connected
Pulse I/O Module 0 Pulse I/O Module 1
Pulse I/O Module Detection The CPU Unit will automatically detect the Pulse I/O Modules that are connected when the power supply is turned ON. The Pulse I/O Modules are therefore not registered in the I/O tables. An error will not occur when power is turned ON even if there is a different number of Pulse I/O Modules connected or different models of Pulse I/O Modules connected.
3-18
CJ2 CPU Unit Hardware User’s Manual
Page 119
3 Nomenclature and Functions
3-3 Pulse I/O Modules (CJ2M CPU Unit Only)
Pulse I/O Module Status Indicators Pulse I/O Module number indicators Indicate the I/O status.
Up to two Pulse I/O Modules can be connected. The indicators on the front panel of a Pulse I/O Module indicate whether the Block is number 0 or number 1 and indicate the I/O status. The following table describes these indicators.
Indicator No. 0
Color Green
No. 1
Green
IN0 to IN9
OUT0 to OUT5
Yellow
Yellow
Status
Meaning
❍
This is the Pulse I/O Module that is connected directly to the CPU Unit. It is Pulse I/O Module number 0.
●
Not connected.
❍
This is the Pulse I/O Module that is connected next to the Power Supply Unit when two Pulse I/O Modules are connected. It is Pulse I/O Module number 1.
●
Not connected.
❍
The allocated input is ON.
●
The allocated input is OFF.
❍
The allocated output is ON.
●
The allocated output is OFF.
Precautions for Correct Use A maximum of two Pulse I/O Modules can be connected. Do not connect more than this. If three or more Pulse I/O Modules are connected, a too many I/O points error (fatal error) will occur. If this error occurs, turn OFF the power supply to the PLC and remove all but two Pulse I/O Modules.
CJ2 CPU Unit Hardware User’s Manual
3-19
3-3-2 Part Names and Functions
❍: Lit, ● :Not lit
3
Page 120
3 Nomenclature and Functions
3-4
Serial Option Boards (CJ2M-CPU3@ Only)
3-4-1
Overview A Serial Option Board can be used with a CJ2M-CPU3@ CPU Unit.
Serial Option Boards
CP1W-CIF01 RS-232C Option Board
CP1W-CIF11 or CP1W-CIF12 RS-422A/485 Option Board z Serial Option Boards Model
Port
Maximum transmission distance
Connection method
CP1W-CIF01
One RS-232C port
15 m
Connector: D-sub, 9-pin female
CP1W-CIF11
One RS-422A/485 port (not isolated)
50 m
Terminal block: Using ferrules
CP1W-CIF12
One RS-422A/485 port (isolated)
500 m
Terminal block: Using ferrules z Mounting an Option Board When mounting an Option Board, first remove the slot cover. Grasp the lock levers at the top and bottom of the cover at the same time to unlock the cover, and then pull the cover out. Then to mount the Option Board, check the alignment and firmly press it in until it snaps into place. Precautions for Correct Use Always turn OFF the power supply to the PLC before mounting or removing an Option Board.
3-20
CJ2 CPU Unit Hardware User’s Manual
Page 121
3 Nomenclature and Functions
3-5
Power Supply Units
3-5-1
Models and Specifications Specifications
Power Supply Unit
CJ1W-PA205R
CJ1W-PA205C
Supply voltage
100 to 240 VAC (wide-range), 50/60 Hz
24 VDC
Operating voltage and frequency ranges
85 to 264 VAC, 47 to 63 Hz
19.2 to 28.8 VDC
21.6 to 26.4 VDC
Power consumption
100 VA max.
50 VA max.
50 W max.
35 W max.
Inrush current*1
At 100 to 120 VAC:
At 100 to 120 VAC:
At 24 VDC:
15 A/8 ms max. for cold start at room temperature 30 A/8 ms max. for cold start at room temperature
20 A/8 ms max. for cold start at room temperature
CJ1W-PD025
CJ1W-PD022
30 A/20 ms max. for cold start at room temperature
At 200 to 240 VAC: 40 A/8 ms max. for cold start at room temperature
Output capacity*7
5.0 A, 5 VDC (including supply to CPU Unit)
2.8 A, 5 VDC (including supply to CPU Unit)
5.0 A, 5 VDC (including supply to CPU Unit)
2.0 A, 5 VDC (including supply to CPU Unit)
0.8 A, 24 VDC
0.4 A, 24 VDC
0.8 A, 24 VDC
0.4 A, 24 VDC
Total: 25 W max.
Total: 14 W max.
Total: 25 W max.
Total: 19.6 W max.
Not provided.
Not provided.
Not provided.
Not provided.
With Alarm output (open collector output)
Not provided.
Not provided.
Not provided.
Output terminal (service supply)
Not provided
RUN output*2
Contact configuration: SPST-NO Switch capacity: 250 VAC, 2 A (resistive load) 120 VAC, 0.5 A (inductive load), 24 VDC, 2A (resistive load) 24 VDC, 2 A (inductive load)
Replacement notification function
Not provided.
30 VDC max., 50 mA max.
CJ2 CPU Unit Hardware User’s Manual
3-21
3 3-5-1 Models and Specifications
At 200 to 240 VAC:
CJ1W-PA202
3-5 Power Supply Units
Item
Page 122
3 Nomenclature and Functions
Item
Specifications
Insulation resistance
20 MΩ min. (at 500 VDC) between AC external and GR terminals*3
• 20 MΩ min. (at 500 VDC) between all external terminals and GR terminal*3, and between all alarm output terminals. • 20 MΩ min. (at 250 VDC) between all alarm output terminals and GR terminal*3.
20 MΩ min. (at 500 VDC) between AC external and GR terminals*3
20 MΩ min. (at 500 VDC) between DC external and GR terminals*3
---*6
Dielectric strength*4
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals*3
• 2,300 VAC, 50/60 Hz for 1 min between all external terminals and GR terminal*3 and between all alarm output terminals with a leakage current of 10 mA max. • 1,000 VAC, 50/60 Hz for 1 min between all alarm output terminals and GR terminal*3 with a leakage current of 10 mA max.
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals*3
1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals*3
---*6
Leakage current: 10 mA max.
Leakage current: 10 mA max.
Leakage current: 10 mA max.
1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals*3 Leakage current: 10 mA max. Noise immunity
2 kV on power supply line (Conforms to IEC61000-4-4.)
Vibration resistance
5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 100 minutes (Time coefficient: 10 minutes × coefficient factor 10 = total time 100 min.) (according to JIS C60068-2-6)
Shock resistance
147 m/s2 3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s2) (according to JIS C60068-2-27)
Ambient operating temperature
0 to 55°C
Ambient operating humidity
10% to 90% (with no condensation)
Atmosphere
Must be free from corrosive gases.
Ambient storage tem- −20 to 75°C perature (excluding battery)
3-22
10% to 90% (with no condensation)*5 −20 to 75°C*5
10% to 90% (with no condensation)
−20 to 75°C (excluding battery)
CJ2 CPU Unit Hardware User’s Manual
Page 123
3 Nomenclature and Functions
*1 The AC and DC values above are given for a cold start, and the AC values are at room temperature. The AC inrush control circuit uses a thermistor element with a low-temperature current control characteristic. If the ambient temperature is high or the PLC is hot-started, the thermistor will not be sufficiently cool, and the inrush current given in the table may be exceeded by up to twice the given value. When selecting fuses or breakers for external circuits, allow sufficient margin in shut-off performance. The DC inrush control circuit uses a capacitor-charging delay circuit. If the power is OFF for only a short time for a hot-start, the capacitor will not sufficiently charge and the inrush current given in the table may be exceeded by up to twice the given value. *3 Disconnect the Power Supply Unit’s LG terminal from the GR terminal when testing insulation and dielectric strength. Testing the insulation and dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU Unit. *4 Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied or turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit. *5 Maintain an ambient storage temperature of −25 to 30°C and relative humidity of 25% to 70% when storing the Unit for longer than 3 months to keep the replacement notification function in optimum working condition.
3-5 Power Supply Units
*2 Supported only when mounted to CPU Rack.
*6 CJ1W-PD022 is not insulated between the primary DC power and secondary DC power. *7 Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an extended period of time exceeding the power supply output capacity or if the outputs are shorted.
3 3-5-1 Models and Specifications
CJ2 CPU Unit Hardware User’s Manual
3-23
Page 124
3 Nomenclature and Functions
3-5-2
Components z Example: CJ1W-PA205R POWER Indicator Lit when 5 V are being output from the Power Supply Unit. PA205R POWER
External connection terminals
L1
AC100-240V INPUT
AC input
L2/N
LG GR RUN OUTPUT AC240V DC24V
RUN output z Example: CJ1W-PA205C Replacement notification display
CJ1W-PA205C External connection terminals
POWER
AC100-240V INPUT
Years
POWER Indicator Lit when 5 V are being output from the Power Supply Unit.
L1
AC input TEST
L2/N
LG
ALARM OUTPUT DC30V,50mA NORMAL:ON ALARM :OFF
GR
L
+
TEST switch The TEST switch can be used to temporarily turn OFF the alarm output that notifies when replacement is needed.
NC
NC
Alarm output (replacement notification output)
z Example: CJ1W-PA202 PA202 POWER
External connection terminals L1
AC input
POWER Indicator Lit when 5 V are being output from the Power Supply Unit.
AC100 -240V INPUT L2/N
LG GR NC
NC
3-24
CJ2 CPU Unit Hardware User’s Manual