SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 3 Nomenclature and Functions, pages 125 to 132
Pages 125 to 132 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213
Page 125
3 Nomenclature and Functions z Example: CJ1W-PD025 POWER Indicator Lit when 5 V are being output from the Power Supply Unit. PD025 POWER
3-5 Power Supply Units
External connection terminals DC24V+ INPUT
DC input LG GR NC
NC
3 3-5-2 Components z Example: CJ1W-PD022 PD022
External connection terminals DC input
POWER
POWER Indicator Lit when 5 V are being output from the Power Supply Unit.
DC24V INPUT
+
NC
NC
GR NC NC
AC Input Supply 100 to 240 VAC (allowable: 85 to 264 VAC). Note The CJ1W-PA205R, CJ1W-PA205C, and CJ1W-PA202 have a wide input range, so they do not have voltage switching terminals.
DC Input Supply 24 VDC. Model
Allowable power supply voltage fluctuation range
CJ1W-PD025
19.2 to 28.8 VDC (±20%)
CJ1W-PD022
21.6 to 26.4 VDC (±10%)
LG Ground to a resistance of 100 Ω or less to increase noise resistance and avoid electric shock.
GR Ground to a resistance of 100 Ω or less to avoid electric shock.
CJ2 CPU Unit Hardware User’s Manual
3-25
Page 126
3 Nomenclature and Functions
RUN Output (CJ1W-PA205R Only) The internal contact turns ON when the CJ2 CPU Unit is operating (RUN or MONITOR mode). The Power Supply Unit must be in the CPU Rack to use this output.
Alarm Output (CJ1W-PA205C Only) The alarm output is used to notify when Power Supply Unit replacement is required. The output is normally ON. The output turns OFF when the time until replacement is 6 months or less.
3-26
CJ2 CPU Unit Hardware User’s Manual
Page 127
3 Nomenclature and Functions
3-5-3
Selecting a Power Supply Unit After determining what power supply voltage is required, whether power output terminals and a RUN output are required, and whether replacement notification is required, calculate the current and power requirements for each Rack. 3-5 Power Supply Units
Condition 1: Current Requirements There are two voltage groups for internal power consumption: 5 VDC and 24 VDC. For details on the current consumption of individual Units, refer to 2-1-4 Configuration Units.
z Current Consumption at 5 VDC The following table shows the current that can be supplied to Units (including the CJ2 CPU Unit) that use 5-VDC power. Model
Maximum current at 5 VDC 5.0 A
CJ1W-PA202
2.8 A
CJ1W-PD025
5.0 A
CJ1W-PD022
2.0 A z Current Consumption at 24 VDC The following table shows the current that can be supplied to Units that use 24-VDC power supply. Maximum current at 24 VDC
CJ1W-PA205R/205C
0.8 A
CJ1W-PA202
0.4 A
CJ1W-PD025
0.8 A
CJ1W-PD022
0.4 A
Condition 2: Power Requirements The following table shows the maximum total power that can be supplied at 5 VDC and 24 VDC. Model
Maximum total power output
CJ1W-PA205R/205C
25 W
CJ1W-PA202
14 W
CJ1W-PD025
25 W
CJ1W-PD022
19.6 W
For details on the current consumption of individual Units, refer to 2-1-2 CPU Rack, 2-1-3 Expansion Racks, and 2-1-4 Configuration Units. Refer to 2-1-5 Calculating Unit Current Consumption for an example of calculating the current consumption.
CJ2 CPU Unit Hardware User’s Manual
3-27
3-5-3 Selecting a Power Supply Unit
CJ1W-PA205R/205C
Model
3
Page 128
3 Nomenclature and Functions
3-6
CJ-series Basic I/O Units
3-6-1
Basic I/O Units with Terminal Blocks
Part Names and Functions z Eight/sixteen-point Units (18-point Terminal Blocks) Model number label I/O indicators
Connector Connect to the connector on the next Unit.
Terminal block for I/O wiring, 18P × 1
ERR 0
1
8
9 10 11 12 13 14 15
2 3
4 5
6
7
Note The CJ1W-OD202, CJ1W-OD204, and CJ1W-OD212 also have an ERR indicator for the load short-circuit alarm.
Interrupt Input Units z Functions Interrupt Input Units are used to execute interrupt programs on the rising or falling edge of an input signal. When the specified interrupt input turns ON (or OFF), execution of the cyclic program in the CPU Unit is interrupted and an I/O interrupt task (task number 100 to 131) is executed. When execution of the I/O interrupt task has been completed, the cyclic program is again executed starting from the instruction after which it was interrupted. CPU Unit
Interrupt Input Unit
1 cyclic task MSKS
Input (rising or falling edge)
3-28
Immediate interrupt
I/O interrupt task is executed when the input turns ON (or OFF).
I/O interrupt task
CJ2 CPU Unit Hardware User’s Manual
Page 129
3 Nomenclature and Functions z Application Precautions • Interrupt Input Units must be mounted in the locations described below.
Example: CJ2H-CPU6@-EIP 0
Power Supply Unit
1
2
3
4
5
6
7
8
9
CPU Unit
3-6 CJ-series Basic I/O Units
When using a CJ2H-CPU6@-EIP CPU Unit, all Interrupt Input Units must be connected in any of the four positions immediately to the right of the CPU Unit, i.e., slots 0 to 3 on the CPU Rack. When using a CJ2H-CPU6@ CPU Unit or CJ2M-CPU@@ Unit, all Interrupt Input Units must be connected in any of the five positions immediately to the right of the CPU Unit, i.e., slots 0 to 4 on the CPU Rack. If an Interrupt Input Unit is connected in any other position on the CPU Rack or anywhere on an Expansion Rack, and I/O setting error (fatal) will occur.
3 Cannot be used.
• The Interrupt Input Units must be connected in the slot ranges specified above even when the I/O tables are edited using the CX-Programmer. If the Interrupt Input Units are not connected in the correct positions, an error will occur when the I/O tables are generated from the CX-Programmer. A401.10 will turn ON to indicate an I/O setting error and A405.08 will turn ON to indicate that an Interrupt Input Unit is in the wrong position. Note Even if a Unit is physically in one of the correct positions, a Dummy Unit can be registered in the I/O tables, causing a Unit to be defined in a position different from its physical position.
• There are limits to the number of Interrupt Input Units that can be mounted. If these limits are exceeded, a too many I/O points error (fatal error) will occur. • The input response time cannot be changed for the CJ1W-INT01, and the related portions of the Basic I/O Unit input time constants in the PLC Setup, and the setting status in A220 to A259 will not be valid.
z Input Signal Width Input signals must meet the following conditions.
ON
Unit CJ1W-INT01
OFF
ON time
OFF time
0.05 ms min.
0.5 ms min.
CJ2 CPU Unit Hardware User’s Manual
3-29
3-6-1 Basic I/O Units with Terminal Blocks
Connect here.
Page 130
3 Nomenclature and Functions
3-6-2
Thirty-two/Sixty-four-point Basic I/O Units with Connectors Units are available with either Fujitsu-compatible connectors (CJ1W-@D@@1) or MIL connectors (CJ1W-@D@@2/3/4).
Part Names z Thirty-two-point Units (Models with 40-point Fujitsu Connector or MIL Connector) Model number Indicator Switch ID 2 3 1
1
ID 2 3 2
I/O indicators
2
Changes the 16 I/O displayed on the I/O indicators. I/O wiring connector (40-pin × 1)
Setting 1 Setting 2
Unit with Fujitsu-compatible Connector
Word m or m+1
MIL connector Fujitsu connector Bottom of connector Wd m (Row A on connector) Wd m+1 (Row B on connector) Top of connector
Unit with MIL Connector Connector Connected to the connector on the next Unit.
ERR 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Note: Only the CJ1W-OD232 has an ERR indicator for the load short-circuit alarm.
z Thirty-two-point Units with 2 × 24-pin Fujitsu-compatible Connectors or 2 × 20-pin MIL Connectors Model number MD231
I/O indicators
MD232
I/O wiring connector (24-pin x 2) Unit with Fujitsu-compatible Connector Word m Word m+1
3-30
0 8 0 8
1 2 3 4 5 6 7 9 10 11 12 13 14 15 1 2 3 4 5 6 7 9 10 11 12 13 14 15
Unit with MIL Connector Connector Connected to the connector on the next Unit.
CJ2 CPU Unit Hardware User’s Manual
Page 131
3 Nomenclature and Functions z Sixty-four-point Units (Models with Two 40-point Fujitsu Connectors or MIL Connector) Indicator Switch 1
3-6 CJ-series Basic I/O Units
Model number 2
Changes the 32 I/O displayed on the I/O indicators. ID 2 6 1
I/O indicators
ID 2 6 1
Setting 1 Setting 2
Wd m and m+1: CN1 Wd m+2 and m+3: CN2
I/O wiring connector (40-pin × 2)
Unit with Fujitsu-compatible Connector
Unit with MIL Connector
3 Connector Connected to the connector on the next Unit.
I
Word m+1 or m+3
II
0 8 0 8
3-6-2 Thirty-two/Sixty-four-point Basic I/O Units with Connectors
Word m or m+2
1 2 3 4 5 6 7 9 1 01 11 21 31 41 5 1 2 3 4 5 6 7 9 1 01 11 21 31 41 5
CJ2 CPU Unit Hardware User’s Manual
3-31
Page 132
3 Nomenclature and Functions
3-7
I/O Control Units and I/O Interface Units An I/O Control Unit and I/O Interface Units are used to connect Expansion Racks to expand the system.
3-7-1
Component Names CJ1W-IC101 I/O Control Unit
CJ1W-II101 I/O Interface Unit II101
IC101
OU T
Output connector for I/O Connecting Cable
Output connector for I/O Connecting Cable
OUT
IN
Input connector for I/O Connecting Cable
Precautions for Correct Use Attached the enclosed cover to the I/O Connecting Cable connector on the I/O Interface Unit when it is not being used to protect it from dust.
3-7-2
System Configuration Power Supply Unit
CPU Unit
CJ1W-IC101 I/O Control Unit
CPU Rack
Power Supply Unit
I/O Connecting Cable
The I/O Control Unit is connected directly to the CJ2 CPU Unit. If it is not immediately to the right of the CPU Unit, correct operation may not be possible. The I/O Interface Unit is connected directly to the Power Supply Unit. If it is not immediately to the right of the Power Supply Unit, correct operation may not be possible.
CJ1W-II101 I/O Interface Unit
Expansion Rack Power Supply Unit
3-32
I/O Connecting Cable CJ1W-II101 I/O Interface Unit
CJ2 CPU Unit Hardware User’s Manual