SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 4 Support Software

Pages 133 to 144 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 133

Support Software This section describes the software that is used to program and debug a CJ2 PLC. It also describes how to connect the Programming Device and the PLC.

4-1 Support Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4-1-1

CX-One FA Integrated Tool Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2

4-2 Connection Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 4-2-1 4-2-2 4-2-3

CJ2 CPU Unit Hardware User’s Manual

Connecting by USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 Connecting by RS-232C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 Connecting to Ethernet (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only) . . . . . . 4-9

4-1

4

Page 134

4 Support Software

4-1

Support Software “Support Software” refers to software applications for programming and debugging OMRON Programmable Controllers.

4-1-1

CX-One FA Integrated Tool Package The CX-One provides an integrated package of Support Software for OMRON PLCs and components. It consists of software applications for PLC programming, network settings, touch-panel screen creation, servo control, inverters, temperature control, and other functions.

CX-One Integrated Tool Package Contents

CX-One

● Motion control ● Touch-panel screen creation

● Programming/simulation CX-Position CX-Motion-NCF

CX-Programmer

CX-Motion

CX-Simulator

CX-Motion-MCH

SwitchBox Utility

CX-Designer NV-Designer

PT

Loop Controller Networks between PLCs

CX-Integrator

Devices by other manufacturers

Field network

Serial

Network

CX-Process Face Plate Auto-Builder for NS

Configurator CX-Protocol

● Protocol macro creation

● Network settings

Servo

● PLC-based process control

Inverter

Temperature control CX-Thermo CX-Drive

● Temperature control settings

● Servo/Inverter settings

SSR

4-2

CJ2 CPU Unit Hardware User’s Manual

Page 135

4 Support Software

Application Programming

CX-One Software

Description

CX-Programmer

Basic software for creating and debugging PLC programs.

SwitchBox Utility

Utility software to support PLC debugging operations.

CX-Integrator

Software for starting and setting FA networks, such as Controller Link, DeviceNet, CompoWay/F, Ethernet, and CompoNet. Includes routing table components, data link components, and DeviceNet Configurator functions.

Network Configurator

Software for setting tag data links for the built-in EtherNet/IP port.

Network settings

NV-Designer

Software for creating screen data for touch panel NV-series PTs.

Protocol macro creation

CX-Protocol

Software for creating protocols (protocol macros) for exchanging data with general-purpose external devices connected to Serial Communications Boards/Units and Option Boards.

Simulation

CX-Simulator

Software for simulating PLC operations on a personal computer and debugging programs without requiring a CPU Unit.

CX-Position

Software for creating and monitoring data for Position Control Units.

CX-Motion-NCF

Software for creating and monitoring data for Position Control Units (MECHATROLINK communications models).

CX-Motion-MCH

Software for creating data for Motion Control Units (MECHATROLINK communications models), and for creating and monitoring motion programs.

CX-Motion

Software for creating data for Motion Control Units, and for creating and monitoring motion programs.

CX-Drive

Software for setting and adjusting Inverter and servo data.

CX-Process Tool

Software for creating and debugging function blocks for Loop Controllers (Loop Control Units/Boards, Process CPU Units, and Loop CPU Units).

Face Plate Auto-Builder for NS

Software for automatic generation of screen data (project files) for touch panel NS-series PTs from Loop Controller function block tag information.

Touch-panel screen creation

Motion Control

Servo/Inverter settings PLC-based process control Temperature control settings

Software for setting and adjusting Temperature Controller parameters.

CX-Thermo

CX-Programmer The CX-Programmer is a basic software application for creating and debugging PLC programs. Ladder language Programming

Tasks

Programming functions

ST language SFC language

FBs

Ladder language

ST language

Simulation

CX-Programmer

Monitoring

Debugging and maintenance functions

I/O table creation

System configuration setup

Special I/O Unit and CPU Bus Unit settings

PLC Setup

CJ2 CPU Unit Hardware User’s Manual

CPU Unit parameters

4-3

4 4-1-1 CX-One FA Integrated Tool Package

Software for making FL-net Unit system settings and performing monitoring. Software for creating screen data for touch panel NS-series PTs. 4-1 Support Software

CX-FLnet CX-Designer

Page 136

4 Support Software

CX-Integrator The CX-Integrator is a software application for setting up FA networks, such as Controller Link, DeviceNet, CompoWay/F, Ethernet, and CompoNet. Routing table settings

Network configuration reading

General network settings and monitoring

Network testing

CX-Integrator

Data link settings Controller Link Diagnosis Controller Link diagnosis

DeviceNet settings

CompoWay/F slave settings

Controller Link settings and monitoring

DeviceNet settings

CompoWay/F settings

Network Configurator The Network Configurator is software for setting tag data links using the built-in EtherNet/IP port. Tag data link settings EtherNet/IP network settings and monitoring

Network Configurator Device monitoring

4-4

CJ2 CPU Unit Hardware User’s Manual

Page 137

4 Support Software

4-2

Connection Methods A CJ2 CPU Unit can be directly connected to a personal computer running the CX-One Support Software (e.g., CX-Programmer) by using a USB cable or RS-232C cable. (The CP1W-CIF01 is required to use a RS-232C cable with the CJ2M-CPU3@.) Also, an Ethernet twisted-pair cable can be used for the CJ2H-CPU6@-EIP or CJ2M-CPU3@.

Connecting by USB

Connection Method Using commercially available USB cable, connect CX-One Support Software via a standard peripheral (USB) port at the personal computer.

4

CX-One (e.g., CX-Programmer)

4-2-1 Connecting by USB

B connector A connector

CJ2 CPU Unit

USB port

Commercially available USB cable*1 Peripheral (USB) port (conforming to USB 2.0, B connector)

*1 Commercially available USB cable: 5 m max., for USB 1.1 or 2.0.

Connecting Cable Use the following cable to connect the CJ2 CPU Unit to the computer running the Support Software. Port at Unit Peripheral (USB) port (Conforms to USB 2.0, B connector)

Port at computer

Network type (communications mode)

USB port

12 Mbps, USB 2.0

Model

Length

Commercially available USB cable (A connector - B connector)

5 m max.

Remarks ---

Before Connecting In order to connect the PLC to a personal computer by USB, a USB driver must be installed in the personal computer. The USB driver for USB connections is automatically stored in the following directory in the personal computer when CX-One is installed: C:\Program Files\OMRON\CX-Server\USB\Win2000_XP\inf When the personal computer is connected to the PLC by USB cable, the personal computer automatically recognizes the device and the USB driver installation is started. For details on how to install the USB driver, refer to A-5 Installing the USB Driver.

CJ2 CPU Unit Hardware User’s Manual

4-2 Connection Methods

4-2-1

4-5

Page 138

4 Support Software

CX-Programmer Settings The method for connecting the PLC to the personal computer is set using the CX-Programmer. For details on using the CX-Programmer to set the connection method, refer to the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).

Restrictions on Connecting by USB Based on USB specifications, the following restrictions apply when connecting a personal computer and components. • Only one CJ2 CPU Unit can be connected by USB to a single personal computer. It is not possible to connect multiple CJ2 CPU Units simultaneously. • Do not remove the USB cable while connected online. The application must be offline before the cable is removed. If the cable is removed while connected online, one of the following situations will occur depending on the operating system. • Windows 2000/XP The Support Software online status will not be restored by simply re-inserting the USB cable. Once the Support Software has gone offline, the cable must be re-inserted and the Support Software online connection operation must be repeated. • Windows 98/Me If the USB cable is removed while connected online, a blue error screen may be displayed. If that occurs, the personal computer must be restarted. Additional Information The USB port on a computer can be connected to the PLC serial port (RS-232C) by using CJ1W-CIF31 USB-Serial Conversion Cable. (The USB driver for the CJ1W-CIF31 must be installed.) Refer to A-5 Installing the USB Driver for the installation procedure for the USB driver.

USB A plug connector, male CS1W-CIF31 D-sub connector (9-pin, male)

CJ2 CPU Unit D-sub connector (9-pin, male)

D-sub connector (9-pin, female)

Recommended cable: XW2Z-200S-CV/500S-CV or XW2Z-200S-V/500S-V*1

RS-232C port, D-sub connector (9-pin, female)

*1 Only a Host Link connection is possible.

4-6

CJ2 CPU Unit Hardware User’s Manual

Page 139

4 Support Software

4-2-2

Connecting by RS-232C

Connection Method Using commercially available RS-232C cable, directly connect the CX-One Support Software (e.g., CXProgrammer) via a standard serial port at the personal computer. The network type must be set to the Toolbus. A Host Link connection cannot be used. 4-2 Connection Methods

CX-One (e.g., CX-Programmer)

D-sub connector (9-pin male)

CJ2 CPU Unit

D-sub connector (9-pin male) D-sub connector (9-pin female)

4 4-2-2 Connecting by RS-232C

Recommended cable: XW2Z-200S-CV/500S-CV

Serial port (RS-232C) (9-pin female D-sub connector) or Serial Option Board (for CJ2M-CPU3@) COMM

Additional Information Connecting to the PLC by EtherNet/IP via USB or RS-232C The Support Software can be directly connected by USB or RS-232C to one CJ2 CPU Unit and access other CPU Units on the EtherNet/IP network via the built-in EtherNet/IP ports on the CJ2 CPU Units. For details, refer to the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). Personal computer Access is possible.

USB

CJ2

CJ2

USB Built-in EtherNet/IP port EtherNet/IP

CJ2 CPU Unit Hardware User’s Manual

4-7

Page 140

4 Support Software

Connecting Cable Use the following cable to connect the CJ2 CPU Unit to the computer running the Support Software.

Serial port (RS-232C) (D-sub, 9-pin, female)

Network type (communications mode)

Model

Serial communications

XW2Z-200S-CV

2m

XW2Z-500S-CV

5m

Port at computer

Port at Unit

D-sub, 9-pin, male

Length

Remarks Use a static-resistant connector.

Precautions for Safe Use • When the above cable connector is connected to the PLC serial port (RS-232C), be sure to discharge static electricity by touching grounded metal before touching the cable connector. The XW2Z-@@@S-CV Cable is particularly resistant to static electricity because it uses a static-resistant connector hood (XM2S-0911-E). Even when this Cable is used, however, be sure to discharge static electricity before touching the connector. • Use the specialized cable described above for connecting cable. Using ordinary commercially available RS-232C cable for personal computers may result in damage to external devices and the CPU Unit.

Additional Information It is possible to create RS-232C cable for connecting to the serial port (RS-232C). The connectors shown in the following table are included with the CJ2 CPU Unit as standard equipment for creating cables. For details on creating cables, refer to A-4 Connecting to a Serial Port on the CPU Unit. Name

Model

Specifications

Plug

XM2A-0901

9-pin, male

Hood

XM2S-0911-E

9-pin static-resistant connector with millimeter screws

Use in combination. (One of each is provided as standard equipment with the CPU Unit.)

Setting the Communications Protocol Select the protocol for communications between the PLC and the CX-Programmer. For a SYSMAC WAY (Host Link) connection, turn OFF pin 5 of the DIP switch on the front panel. For a peripheral bus connection (faster than SYSMAC WAY), turn ON pin 5.

CX-Programmer Settings The method for connecting the PLC to the personal computer is set using the CX-Programmer. For details on using the CX-Programmer to set the connection method, refer to the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).

4-8

CJ2 CPU Unit Hardware User’s Manual

Page 141

4 Support Software

4-2-3

Connecting to Ethernet (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only)

Connection Method

CX-One (e.g., CX-Programmer)

Built-in EtherNet/IP port

4-2 Connection Methods

With the CJ2H-CPU6@-EIP or CJ2M-CPU3@, use a commercially available Ethernet 100Base-TX STP twisted-pair cable (straight) to connect the CX-One Support Software (e.g., CX-Programmer) to the built-in EtherNet/IP port through the Ethernet switch. With the CJ2H-CPU6@-EIP, Ethernet twisted-pair cable can also be used to connect to a personal computer. The same type of connection can be made with the CJ2H-CPU6@ or CJ2M-CPU1@ through an EtherNet/IP Unit.

CJ2 CPU Unit

4

Ethernet switch 100Base-TX twisted-pair cable (straight)

Connecting Cable Use the following cable to connect the CJ2 CPU Unit to the computer running the Support Software. Port at Unit Built-in EtherNet/IP port

Port at computer

Network type (communications mode)

Ethernet port

100Base-TX or 10BaseT*1

Model

Length

Commercially available twisted-pair cable*2

100 m (Recommended between Ethernet switch and nodes.)

Commercially available Ethernet switch*2, *3

---

Remarks ---

*1 Use 100Base-TX when using tag data links. *2 The following table shows the devices recommended for use with the built-in EtherNet/IP port. Part

Ethernet switch

Manufacturer

Model number

Inquires

OMRON

W4S1-03B W4S1-05B W4S1-05C

---

Cisco Systems, Inc.

Consult the manufacturer.

Cisco Systems, Inc. Main Corporate HQ

Contec USA, Inc.

Consult the manufacturer.

CONTEC USA Inc.

Phoenix Contact

Consult the manufacturer.

Phoenix Contact USA Customer Service

Hirschmann Automation and Control

Consult the manufacturer.

Hirschmann Automation and Control (US)

F-LINK-E 0.5mm × 4P

Fujikura America, Inc.

100Base-TX Twisted-pair cable

Fujikura EtherNet/IP compliant cable

CJ2 CPU Unit Hardware User’s Manual

---

4-9

4-2-3 Connecting to Ethernet (CJ2H-CPU6@EIP and CJ2M-CPU3@ Only)

100Base-TX twisted-pair cable (straight)

Page 142

4 Support Software

Part

Manufacturer

Model number

Inquires

Connectors (Modular plug)

STP Plug Panduit Corporation

MPS588

Panduit Corporation US Headquarters

Boots

Tsuko Company

MK boot (IV) LV

Tsuko Company Japan Headquarters

*3 Always use an Ethernet switch when using tag data links in the network. If a repeater hub is used for EtherNet/IP tag data links (cyclic communications), the network's communications load will increase, data collisions will occur frequently, and stable communications will be impossible.

Before Connecting To connect using Ethernet, first set the IP address and subnet mask of the computer in advance as shown in the following example. • IP Addresses Example: 192.168.250.2 User-set value (1 to 254) Value for same segment as IP address of built-in EtherNet/IP port

• Subnet Mask Example: 255.255.255.0.200 User-set value (0 to 252) Class C mask

CX-Programmer Settings The method for connecting the PLC to the personal computer is set using the CX-Programmer. For details on using the CX-Programmer to set the connection method, refer to the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).

4-10

CJ2 CPU Unit Hardware User’s Manual

Page 143

4 Support Software

Additional Information • The CX-Programmer can be used for remote programming and monitoring. It can be used to program and monitor not only the PLC to which it is directly connected, but also to program and monitor any PLC connected through a Controller Link or Ethernet network to which the PLC that the CX-Programmer is connected to is a part of. All programming and monitoring functionality for the directly connected PLC is supported for remote programming and monitoring. For details, refer to 11-2 Serial Communications and 11-3 Communications Networks in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). Peripheral (USB) port or RS-232C port

Peripheral bus or Host Link

Remote programming and monitoring

4-2 Connection Methods

CX-Programmer

FINS

Controller Link or Ethernet Network

CX-Programmer

4 Bridge

Ethernet Network

Controller Link Network Controller Link Network Gateway

Precautions for Correct Use Connecting to a Programming Device through the built-in EtherNet/IP port will not be possible if the following errors occur: • I/O bus error • Too many I/O points error • Unit number duplication error • Rack number duplication error • I/O setting error If any of the above errors occurs and connecting to the Programming Device through the built-in EtherNet/IP port is not possible, connect through the USB port.

CJ2 CPU Unit Hardware User’s Manual

4-11

4-2-3 Connecting to Ethernet (CJ2H-CPU6@EIP and CJ2M-CPU3@ Only)

Peripheral bus or Host Link

Page 144

4 Support Software

4-12

CJ2 CPU Unit Hardware User’s Manual