Page 145
Installation This section describes how to install and wire a CJ2 PLC.
5-1 Fail-safe Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 5-2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 5-2-1 5-2-2 5-2-3 5-2-4 5-2-5 5-2-6
Installation and Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 Installation in a Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 Assembled Appearance and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8 Connecting PLC Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13 DIN Track Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15 Connecting CJ-series Expansion Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20 5-3-1 5-3-2 5-3-3 5-3-4 5-3-5 5-3-6 5-3-7
Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20 Wiring CJ-series Basic I/O Units with Terminal Blocks . . . . . . . . . . . . . . . . . 5-27 Wiring Basic I/O Units with Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29 Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-33 Connecting Pulse I/O Modules to External I/O Devices (CJ2M CPU Unit Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-33 Connecting I/O Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35 Connecting through an Ethernet Cable (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only) . . . . . . . . . . . . . . . . . . . . . . . . 5-39
5-4 Control Panel Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42 5-4-1 5-4-2 5-4-3 5-4-4 5-4-5 5-4-6
CJ2 CPU Unit Hardware User’s Manual
Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42 Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44 Vibration and Shock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44 Atmosphere . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44 Electrical Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-50
5-1
5
Page 146
5 Installation
5-1
Fail-safe Circuits Be sure to set up safety circuits outside of the PLC to prevent dangerous conditions in the event of errors in the PLC or external power supply.
Order of Powering Up the CPU Unit and Controlled System Outputs from Units such as DC Output Units may malfunction momentarily when the power to the PLC is turned ON. This may cause problems in the system if the PLC's power supply is turned ON after the controlled system's power supply. To prevent possible malfunctions, add an external circuit that prevents the power supply to the controlled system from going ON before the power supply to the PLC itself.
Managing CPU Unit Errors When any of the following errors occurs, PLC operation will stop and all outputs from Output Units will be turned OFF. • Operation of the Power Supply Unit's overcurrent protection circuit • A CPU error (watchdog timer error) or CPU on standby • A fatal error (memory error, Memory Card transfer error, I/O bus error, Unit/Rack number duplication error, too many I/O points error, I/O setting error, program error, cycle time exceeded error, or FALS(007) error)*1 Be sure to add any circuits necessary outside of the PLC to ensure the safety of the system in the event of an error that stops PLC operation. *1 When a fatal error occurs, all outputs from Output Units will be turned OFF even if the IOM Hold Bit has been turned ON to protect the contents of I/O memory. (When the IOM Hold Bit is ON, the outputs will retain their previous status after the PLC has been switched from RUN/MONITOR mode to PROGRAM mode.)
Managing Output Malfunctions It is possible for an output to remain ON due to a malfunction in the internal circuitry of the Output Unit, such as a relay or transistor malfunction. Be sure to add any circuits necessary outside of the PLC to ensure the safety of the system in the event that an output fails to go OFF.
5-2
CJ2 CPU Unit Hardware User’s Manual
Page 147
5 Installation
Emergency Stop Circuit The following emergency stop circuit controls the power supply to the controlled system so that power is supplied to the controlled system only when the PLC is operating and the RUN output is ON. An external relay (CR1) is connected to the RUN output from the Power Supply Unit*1 as shown in the following diagram. *1 A RUN output is provided only on the CJ1W-PA205R Power Supply Unit. When a Power Supply Unit without a RUN output is used, program the Always ON Flag (A1) as the execution condition for an output point from an Output Unit.
z Electrical Diagram MCB1 5-1 Fail-safe Circuits
Power supply MCB2 CR1
Controlled system Transformer or noise filter
5
Twisted-pair wires
CJ-series PLC
DC voltage regulator DC input/output
PLC RUN output CR1
Surge suppressor
Interlock Circuits When the PLC controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown in the following example to prevent both the forward and reverse outputs from turning ON at the same time. Interlock circuit 000501
MC2 MC1 Motor clockwise
CJ-series PLC
000502
MC1 MC2 Motor counterclockwise
This circuit prevents outputs MC1 and MC2 from both being ON at the same time even if both CIO 000501 and CIO 000502 are ON, so the motor is protected even if the PLC is programmed improperly or malfunctions.
CJ2 CPU Unit Hardware User’s Manual
5-3
Page 148
5 Installation
5-2
Installation
5-2-1
Installation and Wiring Precautions
Installation in Cabinets or Control Panels When the PLC is being installed in a cabinet or control panel, be sure to provide proper ambient conditions as well as access for operation and maintenance.
z Temperature Control The ambient temperature within the enclosure must be within the operating range of 0 to 55°C. When necessary, take the following steps to maintain the proper temperature. • Provide enough space for good air flow. • Do not install the PLC above equipment that generates a large amount of heat such as heaters, transformers, or high-capacity resistors. • If the ambient temperature exceeds 55°C, install a cooling fan or air conditioner. Fan
Control panel
CJ-series PLC
Louver z Accessibility for Operation and Maintenance • To ensure safe access for operation and maintenance, separate the PLC as much as possible from high-voltage equipment and power machinery. • The PLC will be easiest to install and operate if it is mounted at a height of 1.0 to 1.6 m above the floor.
z Improving Noise Resistance • Do not mount the PLC in a control panel containing high-voltage equipment. • Install the PLC at least 200 mm from power lines. Power lines
200 mm min. CJ-series PLC
200 mm min.
• Ground the mounting plate between the PLC and the mounting surface. • When I/O Connecting Cables are 10 m or longer, connect the control panels in which Racks are mounted with heavier power wires (3 wires at least 2 mm2 in cross-sectional area). 5-4
CJ2 CPU Unit Hardware User’s Manual
Page 149
5 Installation z PLC Orientation • Each Rack must be mounted in an upright position to provide proper cooling.
• Do not install a Rack in any of the following positions.
5-2 Installation
5 5-2-1 Installation and Wiring Precautions
Precautions for Safe Use Always use the standard installation method. A nonstandard installation will decrease heat dissipation, and may delay the replacement notification signal (in particular for Power Supply Units with Replacement Notification (CJ1W-PA205C)), or degrade or damage the internal elements.
CJ2 CPU Unit Hardware User’s Manual
5-5
Page 150
5 Installation
5-2-2
Installation in a Control Panel
Control Panel Installation Dimensions A CJ-series PLC must be mounted inside a control panel on DIN Track. Normally the CPU Rack is installed on top and the Expansion Racks under it. DIN Track
• Consider the width of wiring ducts, wiring, ventilation, and Unit replacement when determining the space between Racks. Additional Information A CJ-series PLC must be mounted on DIN Track. It cannot be mounted with screws. • Whenever possible, route I/O wiring through wiring ducts or raceways. Install the duct so that it is easy to fish wire from the I/O Units through the duct. It is handy to have the duct at the same height as the Racks. Duct 20 mm min.
Unit
DIN Track
20 mm min. Duct
5-6
CJ2 CPU Unit Hardware User’s Manual
Page 151
5 Installation z Wiring Ducts 81.6 to 89 mm
CPU Rack
30 mm
30 mm 40 mm Duct
Expansion Rack
Mounting bracket
Precautions for Correct Use Tighten terminal block screws and cable screws to the following torques.
5-2 Installation
Terminal Screws M4: 1.2 N·m M3: 0.5 N·m Cable Connector Screws M2.6: 0.2 N·m z Routing Wiring Ducts Install the wiring ducts at least 20 mm between the tops of the Racks and any other objects, (e.g., ceiling, wiring ducts, structural supports, devices, etc.) to provide enough space for air circulation and replacement of Units. Output duct
5-2-2 Installation in a Control Panel
Input duct
Power duct 200 mm min.
CPU Rack
Breakers, fuses
Expansion Rack Power equipment such as transformers and magnetic relays
Fuses, relays, timers, etc. (NOT heat-generating equipment, power equipment, etc.)
CJ2 CPU Unit Hardware User’s Manual
Terminal blocks for PLC
5
Terminal blocks for power equipment
5-7
Page 152
5 Installation
5-2-3
Assembled Appearance and Dimensions The CJ-series Units, including the Power Supply Unit, the CPU Unit, and I/O Units, are connected to each other and an End Cover is connected to the right end.
Dimensions (Unit: mm) Power Supply Unit Name
Model number
Power Supply Unit
Specifications
Unit width
CJ1W-PA205R
100 to 240 VAC, 25 W
80 mm
CJ1W-PA205C
100 to 240 VAC, 25 W
80 mm
CJ1W-PA202
100 to 240 VAC, 14 W
45 mm
CJ1W-PD025
24 VDC, 25 W
60 mm
CJ1W-PD022
24 VDC, 19.6 W
27 mm
CPU Unit Name CPU Unit
5-8
Model number
Specifications
CJ2H-CPU68-EIP
I/O points: 2,560 Program capacity: 400 Ksteps
CJ2H-CPU67-EIP
I/O points: 2,560 Program capacity: 250 Ksteps
CJ2H-CPU66-EIP
I/O points: 2,560 Program capacity: 150 Ksteps
CJ2H-CPU65-EIP
I/O points: 2,560 Program capacity: 100 Ksteps
CJ2H-CPU64-EIP
I/O points: 2,560 Program capacity: 50 Ksteps
CJ2H-CPU68
I/O points: 2,560 Program capacity: 400 Ksteps
CJ2H-CPU67
I/O points: 2,560 Program capacity: 250 Ksteps
CJ2H-CPU66
I/O points: 2,560 Program capacity: 150 Ksteps
CJ2H-CPU65
I/O points: 2,560 Program capacity: 100 Ksteps
CJ2H-CPU64
I/O points: 2,560 Program capacity: 50 Ksteps
Unit width 79.8 mm
48.8 mm
CJ2 CPU Unit Hardware User’s Manual
Page 153
5 Installation
Name
Model number
CPU Unit
Specifications I/O points: 2,560 Program capacity: 60 Ksteps
CJ2M-CPU34
I/O points: 2,560 Program capacity: 30 Ksteps
CJ2M-CPU33
I/O points: 2,560 Program capacity: 20 Ksteps
CJ2M-CPU32
I/O points: 2,560 Program capacity: 10 Ksteps
CJ2M-CPU31
I/O points: 2,560 Program capacity: 5 Ksteps
CJ2M-CPU15
I/O points: 2,560 Program capacity: 60 Ksteps
CJ2M-CPU14
I/O points: 2,560 Program capacity: 30 Ksteps
CJ2M-CPU13
I/O points: 2,560 Program capacity: 20 Ksteps
CJ2M-CPU12
I/O points: 2,560 Program capacity: 10 Ksteps
CJ2M-CPU11
I/O points: 2,560 Program capacity: 5 Ksteps
62 mm*
31 mm*
5-2 Installation
CJ2M-CPU35
Unit width
* The width of the CPU Rack will increase by 20 mm for each CJ2M-MD21@ Pulse I/O Module that is connected to the CJ2M CPU Unit.
20-mm-wide Units Name
Model number
I/O Control Unit
CJ1W-IC101
32-point Basic I/O Units
CJ1W-ID231/ID232/ID233
Unit width 20 mm
CJ1W-OD231/OD232/OD233/OD234 B7A Interface Units
CJ1W-B7A22 CJ1W-B7A14 CJ1W-B7A04
CompoBus/S Master Unit
CJ1W-SRM21
Space Unit
CJ1W-SP001
CJ2 CPU Unit Hardware User’s Manual
5 5-2-3 Assembled Appearance and Dimensions
Other than the CPU Units and Power Supply Units, CJ-series Units come in four widths: 20 mm, 31 mm, 51 mm, and 79.8 mm.
5-9