Page 154
5 Installation
31-mm-wide Units Name
Model number
I/O Interface Unit
CJ1W-II101
8-point and 16-point Basic I/O Units
CJ1W-ID201 CJ1W-ID211/212 CJ1W-IA111/201 CJ1W-OD20@ CJ1W-OD211/212/213 CJ1W-OC201/211 CJ1W-OA201
32-point Basic I/O Units
CJ1W-MD231/232/233
64-point Basic I/O Units
CJ1W-ID261 CJ1W-OD261 CJ1W-MD261
Unit width 31 mm
CJ1W-ID262 CJ1W-OD262/263 CJ1W-MD263/563
5-10
Interrupt Input Unit
CJ1W-INT01
Quick-response Input Unit
CJ1W-IDP01
Analog I/O Units
CJ1W-ADG41 CJ1W-AD@@@-V1 CJ1W-AD042 CJ1W-DA@@@ CJ1W-DA042V CJ1W-MAD42
Process I/O Units
CJ1W-AD04U CJ1W-PH41U CJ1W-PTS51/52/15/16 CJ1W-PDC15
Temperature Control Units
CJ1W-TC@@@
Position Control Units (with pulsestring outputs)
CJ1W-NC113/133/213/233/413/433
Position Control Units (with EtherCAT communications)
CJ1W-NC281/481/881/NCF81 CJ1W-NC482/882
MECHATROLINK-II Position Control Unit
CJ1W-NCF71(-MA)
High-speed Counter Unit
CJ1W-CT021
ID Sensor Units
CJ1W-V680C11 CJ1W-V680C12 CJ1W-V600C11 CJ1W-V600C12
Controller Link Unit
CJ1W-CLK23
Serial Communications Units
CJ1W-SCU41-V1 CJ1W-SCU21-V1 CJ1W-SCU31-V1 CJ1W-SCU22/32/42
Ethernet Unit
CJ1W-ETN21
EtherNet/IP Unit
CJ1W-EIP21
DeviceNet Unit
CJ1W-DRM21
CompoNet Master Unit
CJ1W-CRM21
FL-net Unit
CJ1W-FLN22
CJ2 CPU Unit Hardware User’s Manual
Page 155
5 Installation
51-mm-wide Units Name
Model number
SYSMAC SPU Unit (Highspeed Data Storage Unit)
CJ1W-SPU01-V2
Position Control Units
CJ1W-NC214/234
Unit width 51 mm
62-mm-wide Units Name
Model number
Position Control Units
CJ1W-NC414/434
Unit width 62 mm
79.8-mm-wide Units Name
Model number
MECHATROLINK-II Motion Control Unit
CJ1W-MCH71
Unit width 79.8 mm
Power Supply Unit
CPU Unit
5-2 Installation z Design Example for Width W Configuration Units
5 5-2-3 Assembled Appearance and Dimensions
W
Power Supply Unit: CJ1W-PA205R (80 mm) CPU Unit: CJ2H-CPU68-EIP (79.8 mm) Basic I/O Units: CJ1W-ID231 (20 mm) × 2 Special I/O Units: CJ1W-AD081-V1 (31 mm) × 4 CPU Bus Unit: CJ1W-MCH71 (79.8 mm) W = 80 + 79.8 + 20 x 2 + 31 × 4 + 79.8 × 1 + 14.7 (End Cover) = 418.3 mm
CJ2 CPU Unit Hardware User’s Manual
5-11
Page 156
5 Installation
Installation Dimensions (Unit: mm) A 27.5 90
35 27.5
DIN Track
A
PFP-100N2
16 mm
PFP-100N PFP-50N
7.3 mm 7.3 mm
65
Installation Height The installation height of the CJ-series CPU Rack and Expansion Racks varies from 81.6 to 89.0 mm, depending on the I/O Units that are mounted. When a Programming Device (e.g., CX-Programmer) is connected, however, even greater height is required. Allow sufficient depth in the control panel containing the PLC. Approx. 100 to 150 mm
81.6 to 89.0 mm
5-12
CJ2 CPU Unit Hardware User’s Manual
Page 157
5 Installation
5-2-4
Connecting PLC Components The Units that make up a CJ-series PLC can be connected simply by pressing the Units together and locking the sliders by moving them toward the back of the Units. The End Cover is connected in the same way to the Unit on the far right side of the PLC.
1 Join the Units so that the connectors fit exactly. Hook
Hook holes Connector
5-2 Installation
2 The yellow sliders at the top and bottom of each Unit lock the Units together. Move the sliders 5 toward the back of the Units as shown below until they click into place.
5-2-4 Connecting PLC Components
Move the sliders toward the back until they lock into place.
Lock Release
Slider
Precautions for Correct Use If the locking tabs are not secured properly, the connectors may become loose and not function properly. Be sure to slide the locking tabs until they are securely in place.
CJ2 CPU Unit Hardware User’s Manual
5-13
Page 158
5 Installation
3 Attach the End Cover to the Unit on the far right side of the Rack. ● CJ2H CPU Unit CPU Rack
Power Supply Unit
(I/O Control Unit) *1
CPU Unit
I/O Units (10 max.)
End Cover (included with CPU Unit)
*1: Connect the I/O Control Unit directly to the CPU Unit to enable connecting Expansion Racks.
● CJ2M CPU Unit CPU Rack
Power Supply Unit
(Pulse I/O Module) *2
(Pulse I/O Module) *2
CPU Unit
(I/O Control Unit) *1 I/O Units (10 max.)
End Cover (included with CPU Unit)
*1: Connect the I/O Control Unit directly to the CPU Unit to enable connecting Expansion Racks. *2: Up to two Pulse I/O Modules can be connected to the left of the CPU Unit.
Expansion Rack
Power Supply Unit
I/O Interface Unit *3 I/O Units (10 max.)
End Cover (included with I/O Interface Unit)
*3: Connect the I/O Interface Unit directly to the Power Supply Unit.
Additional Information There is no Backplane for the CJ-series. The PLC is constructed by connecting Units together using the connectors on the sides.
Precautions for Correct Use • Always turn OFF the power supply before connecting Units to each other. • Always turn OFF the power supply to the entire system before replacing a Unit. • A maximum of 10 Units can be connected in any one CPU or Expansion Rack. If more than the maximum number of Units are connected, a too many I/O points error (fatal error) will occur and the CJ2 CPU Unit will not operate in either RUN or MONITOR mode. If this occurs, the I/O Overflow Flag (A401.11) will turn ON and A407.13 to A407.15 (I/O Overflow Details 2) will turn ON.
5-14
CJ2 CPU Unit Hardware User’s Manual
Page 159
5 Installation
5-2-5
DIN Track Installation Use the following procedure to install a CJ-series PLC on DIN Track.
1 Release the pins on the backs of the CJ-series Units.
Release DIN Track mounting pins at the bottom of the PLC, as shown below. 1
5-2 Installation
2 Fit the back of the PLC onto the DIN Track by inserting the top of the track and then pressing in
5 5-2-5 DIN Track Installation
DIN Track
2
3 Lock the pins on the backs of the CJ-series Units.
DIN Track mounting pins
CJ2 CPU Unit Hardware User’s Manual
5-15
Page 160
5 Installation
4 Install a DIN Track End Plate on each end of the PLC. To install an End Plate, hook the bottom on the bottom of the track, rotate the Plate to hook the top of the Plate on the top of the track, and then tighten the screw to lock the Plate in place. 2
1
End Plates
DIN Track and Accessories Use the DIN Track and DIN Track End Plates shown below. Secure each DIN Track inside a control panel with at least three screws. • DIN Track Model numbers: PFP-50N (50 cm), PFP-100N (100 cm), PFP-100N2 (100 cm)
Secure the DIN Track to the control panel using M4 screws separated by 210 mm (6 holes) or less and using at least 3 screws. The tightening torque is 1.2 N·m. PFP-100N2 DIN Track
16
Twenty-eight, 25 × 4.5 oblong holes
4.5 30
15
25
10
25
25 1000
10
25
0.3 27
15
24
29.2
1
PFP-100N/50N DIN Track
7.3
1.5
0.15
4.5 35
15
25
10
25
25
1000 (500)*
10
25
15 (5)*
0.3
27
0.15
1
* PFP-50N dimensions are given in parentheses.
• PFP-M DIN Track End Plates (2 required)
5-16
CJ2 CPU Unit Hardware User’s Manual
Page 161
5 Installation
5-2-6
Connecting CJ-series Expansion Racks CS/CJ-series I/O Connecting Cables are used to connect the CPU Rack and Expansion Racks.
z CS/CJ-series I/O Connecting Cables • These connectors are equipped with easy-lock connectors. • Use them to connect the CPU Rack to an Expansion Rack or to connect two Expansion Racks. Model number
Cable length 0.3 m
CS1W-CN713
0.7 m
CS1W-CN223
2m
CS1W-CN323
3m
CS1W-CN523
5m
CS1W-CN133
10 m
CS1W-CN133B2
12 m
• The CJ-series I/O Connecting Cables are used to connect the I/O Control Unit on the CPU Rack to the I/O Interface Unit on an Expansion Rack or to connect the I/O Interface Units on two Expansion Racks.
• The following diagram shows where each I/O Connecting Cable must be connected on each Rack. The Rack will not operate if the cables aren’t connected properly. (The “up” direction is towards the CPU Unit and “down” is away from the CPU Unit.) CPU Unit I/O Control Unit
CPU Rack
Power Supply Unit Down
Expansion Rack
Up
Power Supply Unit I/O Interface Unit Down
CJ2 CPU Unit Hardware User’s Manual
5-17
5 5-2-6 Connecting CJ-series Expansion Racks
• Install the Racks and select I/O Connecting Cables so that the total length of all I/O Connecting Cables does not exceed 12 m.
5-2 Installation
CS1W-CN313
Page 162
5 Installation z Cable Connections The following diagram shows examples of proper Rack connections. Connect the simple lock connectors to the I/O Control Unit on the CJ-series CPU Rack and the I/O Interface Unit on the CJseries Expansion Rack. Power Supply Unit
CPU Unit
I/O Control Unit
CPU Rack
I/O Interface Unit
I/O Connecting Cable
Power Supply Unit
Expansion Rack Total cable length: 12 m max.
I/O Interface Unit
I/O Connecting Cable
Power Supply Unit
Expansion Rack
I/O Interface Unit
I/O Connecting Cable
Power Supply Unit
Expansion Rack
• The top and bottom of the connector are different. Be sure the connector is facing the correct direction before connecting it.
z Connecting the Simple Locking Connectors Press the tabs on the end of the connector and insert the connector until it locks in place. The PLC will not operate properly if the connector isn’t inserted completely. To remove the connector, press the tabs and pull on the connector.
5-18
CJ2 CPU Unit Hardware User’s Manual