The text of a manual · part 20 of 48

SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 5 Installation, pages 163 to 171

Pages 163 to 171 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 163

5 Installation

Precautions for Correct Use • When using an I/O Connecting Cable with a locking connector, be sure that the connector is firmly locked in place before using it. • Always turn OFF the power supply to the PLC before connecting a cable. • An I/O bus error will occur and the PLC will stop if an I/O Connecting Cable's connector separates from the Rack. Be sure that the connectors are secure. • A 63-mm hole will be required if the I/O Connecting Cable must pass through a hole when connecting an Expansion Rack. • Do not bend the I/O Connecting cable past its natural bending radius or pull in it with excessive force. • The cables can withstand a pulling force up to 49 N (11 lbs), so be sure that they are not pulled too forcefully. • The I/O Connecting Cables mustn't be bent too severely. The minimum bending radii are shown in the following diagram. 5-2 Installation

R

R = 69 mm min.

Cable outer diameter: 8.6 mm

5

CJ1W-II101 I/O Interface Unit

II101

OUT

IN

Output connector cover

CJ2 CPU Unit Hardware User’s Manual

5-19

5-2-6 Connecting CJ-series Expansion Racks

• Always attach the cover to the output connector (left side) on the last I/O Interface Unit on the last Expansion Rack to protect it from dust.

Page 164

5 Installation

5-3

Wiring

5-3-1

Power Supply Wiring

AC Power Supply Units z CJ1W-PA205R Power Supply Unit PA205R

M4 self-raising screw terminals

POWER

AC power supply L1

Isolation transformer 1:1

AC power supply 100 to 240 V

RUN output ON when CPU Unit is in RUN or MONITOR mode. OFF when CPU Unit is in PROGRAM mode or stopped for a fatal error.

AC100-240V INPUT L2/N

RUN OUTPUT AC240V DC24V

Power supply

Additional Information The RUN output function is enabled only when mounted to a CPU Rack.

z AC Power Source • Supply 100 to 240 VAC. • Keep voltage fluctuations within the specified range: Supply voltage 100 to 240 VAC

Allowable voltage fluctuations 85 to 264 VAC

• If one power supply phase of the equipment is grounded, connect the grounded phase side to the L2/N terminal.

z Isolation Transformer The PLC's internal noise isolation circuits are sufficient to control typical noise in power supply lines, but noise between the PLC and ground can be significantly reduced by connecting a 1-to-1 isolation transformer. Do not ground the secondary coil of the transformer.

z Power Supply Capacity The power consumption will be 100 VA max. per Rack for the CJ1W-PA205R/PA205C and 50 VA for the CJ1W-PA202, but there will be a surge current of at least 5 times the max. current when power is turned ON.

z RUN Output The RUN output is provided only on the CJ1W-PA25R Power Supply Unit. This output is ON whenever the CPU Unit is operating in RUN or MONITOR mode; it is OFF when the CPU Unit is in PROGRAM mode or a fatal error has occurred (including execution of the FALS(007) instruction).

5-20

CJ2 CPU Unit Hardware User’s Manual

Page 165

5 Installation

The RUN output can be used to control external systems, such as in an emergency stop circuit that turns off the power supply to external systems when the PLC is not operating. (Refer to 5-1 Fail-safe Circuits for more details on the emergency stop circuit.) Item

CJ1W-PA205R

Contact form

SPST-NO

Maximum switching capacity

240 VAC: 2 A for resistive loads 120 VAC: 0.5 A for inductive loads 24 VDC:2 A for resistive loads 24 VDC:2 A for inductive loads z Crimp Terminals The terminals on the Power Supply Unit are M4, self-raising terminals with screws. Precautions for Correct Use • Use crimp terminals for wiring. 5-3 Wiring

• Do not connect bare stranded wires directly to terminals. • Tighten the terminal block screws to the torque of 1.2 N·m. • Use round-type crimp terminals (M4) having the dimensions shown below. • Crimp Terminals for AC Power Supplies

5

7 mm max.

5-3-1 Power Supply Wiring

20 mm max. M4 self-raising terminals

Torque to 1.2 N •m

! Caution Tighten the AC power supply terminal screws to a torque of 1.2 N·m. Loose screws may result in short-circuit, malfunction, or fire.

Precautions for Safe Use • Supply power to all of the Power Supply Units from the same source. • Do not remove the protective label from the top of the Unit until wiring has been completed. This label prevents wire strands and other foreign matter from entering the Unit during wiring procedures. • Do not forget to remove the label from the top of the Power Supply Unit after wiring the Unit. The label will block air circulation needed for cooling.

CJ2 CPU Unit Hardware User’s Manual

5-21

Page 166

5 Installation

DC Power Supplies z CJ1W-PD025 Power Supply Unit Screw terminals (M4 head with self-raising pressure plate)

PD025 POWER

DC24V+ INPUT

DC power supply

NC

NC z DC Power Source Supply 24 VDC. Keep voltage fluctuations within the specified range. Model

Allowable voltage fluctuation range

CJ1W-PD025

19.2 to 28.8 VDC (±20%)

CJ1W-PD022

21.6 to 26.4 VDC (±10%)

z Power Supply Capacity The maximum power consumption is 50 W (CJ1W-PD025)/35 W (CJ1W-PD022) per Rack, but there will be a surge current of about five times that level when the power is turned ON.

z Precautions when Using CJ1W-PD022 Non-insulated Power Supply Units

! Caution When connecting a personal computers or other peripheral devices to a PLC to which a noninsulated Power Supply Unit (CJ1W-PD022) is mounted, either ground the 0 V side of the external power supply or do not ground the external power supply at all ground. A short-circuit will occur in the external power supply if incorrect grounding methods are used. Never ground the 24 V side, as shown below. Wiring in Which the 24-V Power Supply Will Short Non-insulated

24 V DC power supply 0V

FG

5-22

Peripheral cable

0V

Power Supply Unit

CPU Unit

0V

Peripheral device (e.g., personal computer)

FG

CJ2 CPU Unit Hardware User’s Manual

Page 167

5 Installation z Crimp Terminals The terminals on the Power Supply Unit are M4, self-raising terminals with screws. Precautions for Correct Use • Use crimp terminals for wiring. • Do not connect bare stranded wires directly to terminals. • Tighten the terminal block screws to the torque of 1.2 N·m. • Use crimp terminals (M4) having the dimensions shown below. Crimp Terminals for DC Power Supplies 7 mm max.

7 mm max.

Precautions for Safe Use • Supply power to all of the Power Supply Units from the same source. • Do not remove the protective label from the top of the Unit until wiring has been completed. This label prevents wire strands and other foreign matter from entering the Unit during wiring procedures. • Do not forget to remove the label from the top of the Power Supply Unit after wiring the Unit. The label will block air circulation needed for cooling.

PA205R POWER

L1

L2/N

RUN OUTPUT AC240V DC24V

LG (Noise-filter neutral terminal) Ground this terminal to less than 100 Ω to improve noise resistance and prevent electric shock. GR (Ground terminal) Ground this terminal to less than 100 Ω to prevent electric shock.

• To help prevent electrical shock, ground the ground terminal (GR: ) with a ground resistance of less than 100 Ω using a 14-gauge wire (minimum cross-sectional area of 2 mm2). • The line ground terminal (LG: ) is a noise-filtered neutral terminal. If noise is a significant source of errors or electrical shocks are a problem, connect the line ground terminal to the ground terminal and ground both with a ground resistance of less than 100 Ω. • If the LG and GR terminals are connected, ground to a resistance of 100 Ω or less to prevent electric shock. • The ground wire should not be more than 20 m long. • The CJ-series PLCs are designed to be mounted so that they are isolated (separated) from the mounting surface to protect them from the effects of noise in the installation environment (e.g., the control panel). • Do not share the PLC’s ground with other equipment or ground the PLC to the metal structure of a building. The configuration shown in the following diagram may worsen operation.

CJ2 CPU Unit Hardware User’s Manual

5 5-3-1 Power Supply Wiring

Grounding

AC100-240V INPUT

5-3 Wiring

• Be sure not to reverse the positive and negative leads when wiring the power supply terminals.

5-23

Page 168

5 Installation z Crimp Terminals The terminals on the Power Supply Unit are M4, self-raising terminals with screws. Precautions for Correct Use • Use crimp terminals for wiring. • Do not connect bare stranded wires directly to terminals. • Tighten the terminal block screws to the torque of 1.2 N·m. • Use crimp terminals (M4) having the dimensions shown below.

z Crimp Terminals for DC Power Supply 7 mm max.

7 mm max.

Alarm Output An alarm output is provided on Power Supply Units with a replacement notification function. Connect the alarm output to a PLC's Input Unit or external LED indicator to enable notification when Power Supply Unit replacement is required.

z CJ1W-PA205C Power Supply Unit CJ1W-PA205C POWER

AC100-240V INPUT L1

TEST L2/N ALARM OUTPUT DC30V, 50mA NORMAL:ON ALARM:OFF

L

NC NC

24 VDC power supply

Alarm output (replacement notification output) ON when replacing the Power Supply Unit is not required for at least 6 months.

z Output Specifications • ON (normal): Power Supply Unit replacement not required for at least 6 months. • OFF: Power Supply Unit replacement required within 6 months. • Transistor open-collector outputs • Maximum switching capacity: 30 VDC max., 50 mA max. • ON: Residual voltage of 2 V max., OFF: Leakage current of 0.1 mA max.

5-24

CJ2 CPU Unit Hardware User’s Manual

Page 169

5 Installation z Wiring The following wire gauges are recommended. Recommended wire size

Use

AWG 22 to 18 (0.32 to 0.82 mm2)

Connecting to PLC terminal block models

AWG 28 to 24 (0.08 to 0.2 mm2)

Connecting to PLC connector models

Pushing strength (clamping operation)

Pulling strength (holding force)

Length of stripped section

30 N max.

30 N min.

7 to 10 mm

10 N min.

z PLC Input Unit Wiring Example Connect the positive terminals of the 24-VDC power supply to the Input Unit common (COM) terminals. CJ1W-PA205C

CPU Unit

IN Unit CJ1W-ID2@@

CJ1W-PA205C

5-3 Wiring

POWER

AC100-240V INPUT

IN0

L1

TEST

L2/N ALARM OUTPUT DC30V, 50mA NORMAL:ON ALARM OFF

L IN(N)

NC

IN(N+1)

NC

COM

5

24-VDC power supply

CJ1W-PA205C

CPU Unit

IN Unit CJ1W-ID2@@

CJ1W-PA205C POWER

AC100-240V INPUT

IN0

L1

TEST

L2/N ALARM OUTPUT DC30V, 50mA NORMAL:ON ALARM OFF

L IN(N)

NC NC

IN(N+1) COM

24-VDC power supply

CJ2 CPU Unit Hardware User’s Manual

5-25

5-3-1 Power Supply Wiring

Connect the negative terminal of the 24-VDC power supply to the Input Unit common (COM) terminal.

Page 170

5 Installation z External Display Device Connection Example The alarm output (replacement notification output) is an NC contact. Therefore, wire the alarm output using an NC contact or other means to turn ON an error indicator or LED display as shown in the following diagram. CJ1W-PA205C POWER

AC100-240V INPUT L1

TEST

L2/N ALARM OUTPUT DC30V, 50mA NORMAL:ON ALARM OFF

L

NC

Power supply

NC

24-VDC power supply

Relay (NC contacts)

OL

Note The OL display will also light if the PLC's power supply fails.

Precautions for Safe Use • Separate the alarm output cables from power lines and high-voltage lines. • Do not apply a voltage or connect a load to the alarm output that exceeds the rated voltage or load.

5-26

CJ2 CPU Unit Hardware User’s Manual

Page 171

5 Installation

5-3-2

Wiring CJ-series Basic I/O Units with Terminal Blocks

Precautions for Wiring I/O Units z I/O Unit Specifications Double-check the specifications for the I/O Units. In particular, do not apply a voltage that exceeds the input voltage for Input Units or the maximum switching capacity for Output Units. Doing so may result in breakdown, damage, or fire. When the power supply has positive and negative terminals, be sure to wire them correctly.

z Electric Wires • The following wire gauges are recommended. Terminal Block Connector 18-terminal

Wire Size AWG 22 to 18 (0.32 to 0.82 mm2) 5-3 Wiring

• The current capacity of electric wire depends on factors such as the ambient temperature and insulation thickness as well as the gauge of the conductor.

z Crimp Terminals

5

The terminals on the I/O Unit are M3, self-raising terminals with screws.

5-3-2 Wiring CJ-series Basic I/O Units with Terminal Blocks

Precautions for Correct Use • Use crimp terminals for wiring. • Do not connect bare stranded wires directly to terminals. • Tighten the terminal block screws to the torque of 0.5 N·m. • Use crimp terminals (M3) having the dimensions shown below. 6.2 mm max.

CJ2 CPU Unit Hardware User’s Manual

6.2 mm max.

5-27