SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 5 Installation, pages 172 to 180

Pages 172 to 180 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 172

5 Installation z Wiring • Make sure that all Units are connected properly. • Do not remove the protective label from the top of the Unit until wiring has been completed. • This label prevents wire strands and other foreign matter from entering the Unit during wiring procedures. • Remove the label after wiring has been completed to allow air circulation needed for cooling. During wiring

After wiring

OD211

OD211

0

0

8

1 2 3 4 5 6 7 9 10 11 12 13 14 15

8

1

2 3 4 5 6 7 9 10 11 12 13 14 15

Remove the label.

• Wire the Units so that they can be easily replaced. • Make sure that the I/O indicators are not covered by the wiring. • Do not place the wiring for I/O Units in the same duct or raceway as power lines. Inductive noise can cause errors in operation. • Tighten the terminal screws to the torque of 0.5 N·m. 17.5 mm

Screw (M3 screw with self-raising pressure plate)

z Terminal Blocks • The I/O Units are equipped with removable terminal blocks. The lead wires do not have to be removed from the terminal block to remove it from an I/O Unit. • After you complete wiring, check to see if the terminal block is securely locked.

OD211 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Terminal block lever

CJ-series Basic I/O Unit

5-28

CJ2 CPU Unit Hardware User’s Manual

Page 173

5 Installation

5-3-3

Wiring Basic I/O Units with Connectors This section describes wiring for CJ-series Basic I/O Units with connectors (32- and 64-point Units). Depending on the connector, the following methods are used to connect these Units to external I/O devices. • Use an OMRON Connecting Cable (equipped with a special connector) to connect to a Terminal Block or Relay Terminal. • Use a special connector and user-provided cable. Precautions for Safe Use • Be sure not to apply a voltage that exceeds the input voltage for Input Units or the maximum switching capacity for Output Units. • When the power supply has positive and negative terminals, be sure to wire them correctly. Loads connected to Output Units may malfunction if the polarity is reversed.

• When connecting the connector to the I/O Unit, tighten the connector screws to a torque of 0.2 N·m. • Turn ON the power after checking the connector's wiring.

5-3 Wiring

• Use reinforced insulation or double insulation on the DC power supply connected to DC I/O Units when required by EC Directives (low voltage).

• Do not pull the cable. Doing so will damage the cable.

5

• Bending the cable too sharply can damage or break wiring in the cable.

CJ-series Basic I/O Units with 32 or 64 points and Fujitsu connectors have the same connector pin allocations as the C200H High-density I/O Units and CS-series I/O Units with connectors to make them compatible.

Connecting to a Connector-Terminal Block Conversion Unit or I/O Relay Terminal For details on using OMRON Connecting Cables equipped with special connectors to connect Basic I/O Units with connectors to OMRON Connector-Terminal Block Conversion Units or I/O Relay Terminals, refer to A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals.

CJ2 CPU Unit Hardware User’s Manual

5-29

5-3-3 Wiring Basic I/O Units with Connectors

Additional Information

Page 174

5 Installation

Using User-made Cables with Connector z Available Connectors Use the following connectors when assembling a connector and cable. CJ-series 32- and 64-point Basic I/O Units with Fujitsu-compatible Connectors Applicable Units Model

Specifications

Pins

CJ1W-ID231

Input Unit, 24 VDC, 32 inputs

40

CJ1W-ID261

Input Unit, 24 VDC, 64 inputs

CJ1W-OD231

Transistor Output Unit with Sinking Outputs, 32 outputs

CJ1W-OD261

Transistor Output Unit with Sinking Outputs, 64 outputs

CJ1W-MD261

24-VDC Input/Transistor Output Units, 32 Inputs, 32 Outputs

CJ1W-MD231

24-VDC Input/Transistor Output Units, 16 Inputs, 16 Outputs

24

Applicable Cable-side Connectors Connection

Pins

Solder-type

Crimped

Pressure-welded

OMRON set

Fujitsu parts

40

C500-CE404

Socket: FCN-361J040-AU Connector cover: FCN-360C040-J2

24

C500-CE241

Socket: FCN-361J024-AU Connector cover: FCN-360C024-J2

40

C500-CE405

Socket: FCN-363J040 Connector cover: FCN-360C040-J2 Contacts: FCN-363J-AU

24

C500-CE242

Socket: FCN-363J024 Connector cover: FCN-360C024-J2 Contacts: FCN-363J-AU

40

C500-CE403

FCN-367J040-AU/F

24

C500-CE243

FCN-367J024-AU/F

CJ-series 32- and 64-point Basic I/O Units with MIL Connectors Applicable Units Model

Specifications

CJ1W-ID232

Pins

Input Unit, 24 VDC, 32 inputs

40

CJ1W-ID233 CJ1W-ID262

Input Unit, 24 VDC, 64 inputs

CJ1W-OD232

Transistor Output Unit with sourcing outputs, 32 outputs

CJ1W-OD262

Transistor Output Unit with sourcing outputs, 64 outputs

CJ1W-OD233

Transistor Output Unit with sinking outputs, 32 outputs

CJ1W-OD234 CJ1W-OD263

Transistor Output Unit with sinking outputs, 64 outputs

CJ1W-MD263

24-VDC Input/Transistor Output Units, 32 inputs, 32 outputs

CJ1W-MD563

TTL Input/TTL Output Units, 32 inputs, 32 outputs

CJ1W-MD232

24-VDC Input/Transistor Output Units, 16 inputs, 16 outputs

CJ1W-MD233

24-VDC Input/Transistor Output Units, 16 inputs, 16 outputs

20

Applicable Cable-side Connectors Connection Pressure-welded

5-30

Pins

OMRON set

DDK parts

40

XG4M-4030-T

FRC5-A040-3TOS

20

XG4M-2030-T

FRC5-A020-3TOS

CJ2 CPU Unit Hardware User’s Manual

Page 175

5 Installation z Wire Size We recommend using cable with wire gauges of AWG 24 or AWG 28 (0.2 mm2 to 0.08 mm2). Use cable with external wire diameters of 1.61 mm max.

z Wiring Procedure The following wiring procedure is an example for Fujitsu-compatible connectors.

1 Check that each Unit is installed securely. Precautions for Correct Use Do not force the cables.

2 Do not remove the protective label from the top of the Unit until wiring has been completed. This After wiring

Before wiring

ID261 I II

0 8 0 8

ID261 1 2 3 4 5 6 7 9 10 11 12 13 14 15 1 2 3 4 5 6 7 9 10 11 12 13 14 15

I II

0 8 0 8

1 2 3 4 5 6 7 9 10 11 12 13 14 15 1 2 3 4 5 6 7 9 10 11 12 13 14 15

5-3 Wiring label prevents wire strands and other foreign matter from entering the Unit during wiring. (Remove the label after wiring has been completed to allow air circulation needed for cooling.)

Remove label after wiring

5 nals. Cover the solder joint with heat-shrink tubing. Solder-type connector

Heat-shrink tubing Wire (0.2 to 0.13 mm2)

Precautions for Safe Use Double-check to make sure that the Output Unit's power supply leads have not been reversed. If the leads are reversed, the Unit's internal fuse will blow and the Unit will not operate.

CJ2 CPU Unit Hardware User’s Manual

5-31

5-3-3 Wiring Basic I/O Units with Connectors

3 When solder-type connectors are being used, be sure not to accidentally short adjacent termi-

Page 176

5 Installation

4 Assemble the connector (purchased separately). Small screws (3)

Connector cover

Small screws (2) Socket Connector lock screws Cable bracket

Nuts (3)

Nuts (2)

5 Insert the wired connector. ID261 I II

0 8 0 8

1 2 3 4 5 6 7 9 10 11 12 13 14 15 1 2 3 4 5 6 7 9 10 11 12 13 14 15

Connector Basic I/O Unit Basic I/O Unit

Connector

6 Remove the protective label after wiring has been completed to allow air circulation needed for cooling. After wiring

ID261

Connector lock screws

I II

0 8 0 8

1 2 3 4 5 6 7 9 10 11 12 13 14 15 1 2 3 4 5 6 7 9 10 11 12 13 14 15

Remove label after wiring.

Tighten the connector lock screws to a torque of 0.2 N·m.

5-32

CJ2 CPU Unit Hardware User’s Manual

Page 177

5 Installation

5-3-4

Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals OMRON Connecting Cable can be used to connect Basic I/O Units with Connectors to OMRON Connector-Terminal Block Conversion Units or to OMRON I/O Relay Terminals. For details, refer to A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals.

z Connection Examples Connector-Terminal Block Conversion Unit

I/O Relay Terminals Basic I/O Unit

Basic I/O Unit

Connecting Cable

Connecting Cable Connector-Terminal Block Conversion Unit

I/O Relay Terminal

40 or 60 terminals

Connecting Pulse I/O Modules to External I/O Devices (CJ2M CPU Unit Only)

• Use an OMRON Cable with Connectors to connect to a Connector-Terminal Block Conversion Unit or Servo Relay Unit. • Make a cable with an MIL Connector (including using Servo General-purpose Control Cables).

z Using OMRON Cables with Connectors to Connect to Connector-Terminal Block Conversion Units or Servo Relay Units For details on using OMRON Cables with Connectors to connect Pulse I/O Modules to OMRON Connector-Terminal Block Conversion Units or Servo Relay Units, refer to the CJ2M CPU Unit Pulse I/O Module User's Manual (Cat. No. W486). Connection Example for Connector-Terminal Block Conversion Unit

Connection Example for Servo Relay Unit Pulse I/O Module

Pulse I/O Module

Pulse I/O Module to Servo Relay Unit Connecting Cable Servo Relay Unit to Servo Drive Connecting Cable

Connecting Cable Connector-Terminal Block Conversion Unit

Servo Drive

Servo Relay Unit z User-made Cables with Connectors Applicable Pulse I/O Modules Model

Specifications

Pins

CJ2M-MD211

Sinking outputs, MIL connector, 10 inputs, 6 outputs

40

CJ2M-MD212

Sourcing outputs, MIL connector, 10 inputs, 6 outputs

40

CJ2 CPU Unit Hardware User’s Manual

5-33

5 5-3-4 Connecting to Connector-Terminal Block Conversion Units or I/O Relay Terminals

Depending on the connector, the following methods are used to connect these Pulse I/O Modules to external I/O devices.

5-3 Wiring

5-3-5

Page 178

5 Installation

Applicable Cable-side Connectors Connection method Pressure-welded

5-34

Pins 40

OMRON set XG4M-4030-T

DDK Ltd. FRC5-A040-3TOS

CJ2 CPU Unit Hardware User’s Manual

Page 179

5 Installation

5-3-6

Connecting I/O Devices

Input Devices Use the following information for reference when selecting or connecting input devices.

z DC Input Units The following types of DC input devices can be connected. Contact output IN

DC Input Unit

COM

IN Sensor Power Supply

5-3 Wiring

Two-wire DC output

DC Input Unit

COM

5

IN

Output 7 mA

5-3-6 Connecting I/O Devices

NPN open-collector output Sensor Power Supply DC Input Unit

COM

0V NPN current output Current regulator

DC Input Unit

Output

IN

7 mA Sensor Power 0 V Supply

COM

PNP current output Sensor Power Supply Output 7 mA 0V

DC Input Unit IN COM

Voltage output COM Output

IN DC Input Unit

0 V Sensor Power Supply

• The circuit below should NOT be used for I/O devices having a voltage output. Voltage output

Sensor Power Supply Output

0V

CJ2 CPU Unit Hardware User’s Manual

DC Input Unit IN COM

5-35

Page 180

5 Installation z AC Input Units Contact output IN AC Input Unit COM

AC Switching IN Proximity switch main circuit

AC Input Unit COM

Precautions for Safe Use When using a reed switch as the input contact for an AC Input Unit, use a switch with an allowable current of 1 A or greater. If reed switches with smaller allowable currents are used, the contacts may fuse due to surge currents.

z Precautions when Connecting a Two-wire DC Sensor When using a two-wire sensor with a 12-VDC or 24-VDC input device, check that the following conditions have been met. Failure to meet these conditions may result in operating errors. • Relation between voltage when the PLC is ON and the sensor residual voltage: VON ≤ VCC − VR • Relation between voltage when the PLC is ON and sensor control output (load current): IOUT (min) ≤ ION ≤ IOUT (max.) ION = (VCC − VR − 1.5 [PLC internal residual voltage])/RIN When ION is smaller than IOUT (min), connect a bleeder resistor R. The bleeder resistor constant can be calculated as follows: R ≤ (VCC − VR)/(IOUT (min.) − ION) Power W ≥ (VCC − VR)2/R × 4 [allowable margin] VCC: Power voltage VR: Sensor output residual current ION: PLC ON current IOUT: Sensor control current (load current) RIN: PLC input impedance

5-36