Page 181
5 Installation
• Relation between current when the PLC is OFF and sensor leakage current: IOFF ≥ Ileak Connect a bleeder resistor if Ileak is greater than IOFF. Use the following equation to calculate the bleeder resistance constant. R ≤ (RIN × VOFF)/(Ileak × RIN − VOFF) Power W ≥ (VCC − VR)2/R × 4 [allowable margin]
DC Input Unit Two-wire sensor
VR
R
R IN
VCC VR: Sensor output residual current IOUT: Sensor control current (load current) Ileak: Sensor leakage current R: Bleeder resistance
• Precautions on Sensor Surge Current An incorrect input may occur if a sensor is turned ON after the PLC has started up to the point where inputs are possible. Determine the time required for sensor operation to stabilize after the sensor is turned ON and take appropriate measures, such as inserting into the program a timer delay after turning ON the sensor.
In this example, the sensor's power supply voltage is used as the input to CIO 000000 and a 100-ms timer delay (the time required for an OMRON Proximity Sensor to stabilize) is created in the program. After the Completion Flag for the timer turns ON, the sensor input on CIO 000001 will cause output bit CIO 000100 to turn ON. 000000 TIM 0000 #0001 TIM0000 000001 000100
CJ2 CPU Unit Hardware User’s Manual
5-37
5 5-3-6 Wiring with Ethernet Cable (CJ2HCPU6@-EIP only)
z Example
5-3 Wiring
VCC: Power voltage VON: PLC ON voltage VOFF: PLC OFF voltage ION: PLC ON current IOFF: PLC OFF current RIN: PLC input impedance
Page 182
5 Installation
Output Wiring Precautions z Output Short-circuit Protection If a load connected to the output terminals is short-circuited, output components and the printed circuit boards may be damaged. To guard against this, incorporate a fuse in the external circuit. Use a fuse with a capacity of about twice the rated output.
z Transistor Output Residual Voltage A TTL circuit cannot be connected directly to a transistor output because of the transistor's residual voltage. It is necessary to connect a pull-up resistor and a CMOS IC between the two.
z Output Surge Current When connecting a transistor or triac output to an output device having a high surge current (such as an incandescent lamp), steps must be taken to avoid damage to the transistor or triac. Use either of the following methods to reduce the surge current. Method 1 L
OUT CS/CJ-series PLC
+
R COM
Add a resistor that draws about 1/3 of the current consumed by the bulb. Method 2
R OUT
L
+
CS/CJ-series PLC COM Add a control resistor as shown in the following diagram.
5-38
CJ2 CPU Unit Hardware User’s Manual
Page 183
5 Installation
5-3-7
Connecting through an Ethernet Cable (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only)
Precautions Observe the following precautions when using the built-in EtherNet/IP port on the CJ2H-CPU6@-EIP or CJ2M-CPU3@.
z Basic Installation Precautions • Take the greatest care when installing the Ethernet System, being sure to follow ISO 8802-3 specifications. You must obtain a copy of these specifications and be sure you understand them before attempting to install an Ethernet System. • Unless you are already experienced in installing communications systems, we strongly recommend that you employ a professional to install your system.
• When installing an EtherNet/IP network that combines an information system with the control system, and the communications load may be heavy due to tag data links, we recommend configuring the network so that the load does not affect communications. For example, install the tag data links in a segment that is separate from the information network.
5-3 Wiring
• Do not install Ethernet equipment near sources of noise. If a noisy environment is unavoidable, take adequate measures against noise interference, such as installing network components in grounded metal cases or using optical cable in the system.
5 z Precautions on Laying Twisted-pair Cable
• Do not connect the connector shield at the CPU Unit. • If a cable connects two Ethernet switches, connect the shields at only one end. Ethernet switch Connector
Ethernet switch
Connector
Connector
GR
Connector
Connect shield. Connector
Do not connect shield.
GR
EIP Unit STP STP
Connector
Power Supply Unit GR terminal
(Shield) (Shield)
EIP Unit
STP
Connector
Power Supply Unit GR terminal
(Shield)
• Press the cable connector in firmly until it locks into place at both the Ethernet switch and the CPU Unit. • Do not lay the twisted-pair cable together with high-voltage lines. • Do not lay the twisted-pair cable near devices that generate noise. • Do not lay the twisted-pair cable in locations subject to high temperatures or high humidity. • Do not lay the twisted-pair cable in locations subject to excessive dirt and dust or to oil mist or other contaminants.
CJ2 CPU Unit Hardware User’s Manual
5-39
5-3-7 Connecting through an Ethernet Cable (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only)
• Noise resistance may be reduced by ground loops, which can occur due to improper shield connections and grounding. Ground the shield at one location, as shown in the following diagram.
Page 184
5 Installation
Ethernet Connectors The following standards and specifications apply to the connectors for the Ethernet twisted-pair cable. • Electrical specifications: Conform to IEEE802.3 standards. • Connector structure:
RJ45 8-pin Modular Connector (Conforms to ISO 8877)
Connector pin
Signal name
Abbr.
Signal direction
1
Transmission data +
TD+
Output
2
Transmission data −
TD−
Output
3
Reception data +
RD+
Input
4
Not used.
---
---
5
Not used.
---
---
6
Reception data −
RD−
Input
7
Not used.
---
---
8
Not used.
---
---
Hood
Frame ground
FG
---
Connecting the Cable Precautions for Correct Use • Turn OFF the PLC's power supply before connecting or disconnecting twisted-pair cable. • Allow enough space for the bending radius of the twisted-pair cable as shown in below.
35 mm
1 Lay the twisted-pair cable. 2 Connect the cable to the Ethernet switch. Be sure to press in the cable until it locks into place.
5-40
CJ2 CPU Unit Hardware User’s Manual
Page 185
5 Installation
3 Connect the twisted-pair cable to the connector on the built-in EtherNet/IP port at the CPU Unit. Be sure to press the connectors at both the Ethernet switch end and Ethernet end until they lock into place. RJ45 Modular Connector
Built-in EtherNet/IP port
5-3 Wiring
5 5-3-7 Connecting through an Ethernet Cable (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only)
CJ2 CPU Unit Hardware User’s Manual
5-41
Page 186
5 Installation
5-4
Control Panel Installation To ensure system reliability and safety, the system must be designed and configured according to the installation environment (temperature, humidity, vibration, shock, corrosive gases, overcurrent, noise, etc.).
5-4-1
Temperature Panels have been reduced in size due to space-saving and miniaturization in devices and systems, and the temperature inside the panel may be at least 10 to 15°C higher than outside the panel. Implement the following measures against overheating at the installation site and in the panel, and allow a sufficient margin for the temperature.
High Temperatures Use the following cooling methods as required, taking into account the ambient temperature and the amount of heating inside the panel.
z Natural Cooling Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling devices such as fans or coolers. When using this method, observe the following points. • Do not install the PLC at the top of the panel, where hot air tends to stagnate. • To provide ventilation space above and below the PLC, leave sufficient distance from other devices, wiring ducts, etc. • Do not mount the Units in the wrong direction (e.g., vertically or upside down). Doing so may cause abnormal heating in the PLC. • Do not install heat-generating equipment, such as heaters, transformers, and devices with high resistance, directly above the panel. • Do not install the PLC in a location exposed to direct sunlight.
PLC
PLC
Natural Cooling z Forced Ventilation (by Fan at Top of Panel) Fan
PLC
PLC
Air filter
Forced Ventilation Method
5-42
CJ2 CPU Unit Hardware User’s Manual
Page 187
5 Installation z Forced Air Circulation (by Fan in Closed Panel)
Fan PLC
PLC
Forced Air Circulation
Cooler
Control panel
5-4 Control Panel Installation z Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
Room Cooling
5
Low Temperatures
CJ2 CPU Unit Hardware User’s Manual
5-43
5-4-1 Temperature
The PLC will not start normally if the temperature is below 0°C when the power is turned ON. Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures such as installing a low-capacity space heater in the panel. Alternatively, leave the PLC power ON to keep the PLC warm.
Page 188
5 Installation
5-4-2
Humidity Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to shortcircuiting. When there is a possibility of this occurring, take measures against condensation, such as leaving the PLC power ON at night or installing a heater in the control panel to keep it warmer. Control panel Moisture absorber PLC
Power ON Heater
Examples of Measures against Condensation
5-4-3
Vibration and Shock The PLC is tested for conformity with the sine wave vibration test method (IEC 60068-2-6) and the shock test method (IEC 60068-2-27) of the Environmental Testing for Electrotechnical Products. It is designed so that malfunctioning will not occur within the specifications for vibration and shock. If, however, the PLC is to be used in a location in which it will be directly subjected to regular vibration or shock, then implement the following countermeasures: • Either separate the control panel from the source of the vibration or shock, or secure the PLC and the panel with rubber padding to prevent vibration. • Make the building or the floor vibration-resistant. • To prevent shock during operation to devices in the panel, such as electromagnetic contactors, secure either the source of the shock or the PLC with rubber padding.
5-4-4
Atmosphere Using the PLC in any of the following locations can cause defective contact with connectors and corrosion of components. Implement countermeasures such as purging the air as required. • In locations exposed to dust, dirt, salt, metal filings, soot, or organic solvents, use a panel with an airtight structure. Be careful of temperature increases inside the panel. • In locations exposed to corrosive gas, purge the air inside the panel to clear the gas and then pressurize the inside of the panel to prevent gas from entering from outside. • In locations where flammable gas is present, either use an explosion-protected construction or do not use the PLC.
5-44
CJ2 CPU Unit Hardware User’s Manual
Page 189
5 Installation
5-4-5
Electrical Environment When installing or wiring devices, make sure that there will be no danger to people and that noise will not interfere with electrical signals.
PLC Installation Location Install the PLC as far away as possible from high-voltage (600 V or higher) and power devices to ensure safe operation and maintenance. Example of Recommended Equipment Arrangement
5-4 Control Panel Installation
OK
PLC
Control panel
Control panel
High-voltage power panel
Example of Poor Equipment Arrangement
NG
5
PLC
Control panel
Control panel
5-4-5 Electrical Environment
High-voltage power panel
Examples of Equipment Arrangement in Panel with High-voltage Devices
Arrangement of PLC and Units Observe the following points. • Place a Unit that does not generate much noise next to the CPU Unit, such as an Input Unit or Communications Unit.
DC I/O device
AC Unit
AC Unit
DC Unit
DC Unit
Communications Unit
CPU
Power Supply Unit
• The coils and contacts in electromagnetic contactors and relays in an external circuit are sources of noise. Locate them at least 100 mm away from the PLC.
AC I/O device
Terminal block
Example of Arrangement in Panel
CJ2 CPU Unit Hardware User’s Manual
5-45