The text of a manual · part 23 of 48
SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Section 5 Installation, pages 190 to 196
Pages 190 to 196 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213
Page 190
5 Installation
Wire Layout for the Power Supply System Observe the following points when wiring the power supply system. • Separate the PLC power supply from the I/O device power supply and install a noise filter near the PLC power supply feed section. • Use an isolating transformer to significantly reduce noise between the PLC and the ground. Install the isolating transformer between the PLC power supply and the noise filter, and do not ground the secondary coil of the transformer. • Keep the wiring between the transformer and the PLC as short as possible, twist the wires well, and keep the wiring separate from high-voltage and power lines.
Power circuits
Power supply for general operations circuits
Power supply for PLC input circuits
Power supply for PLC output circuits
Noise filter
PLC power supply
Outlet (for peripheral devices)
Power Supply System Diagram
Wiring External I/O Signal Lines Observe the following points when wiring external I/O signal lines. • To absorb reverse electromotive force when an inductive load is connected to an output signal, connect a surge suppressor near the inductive load in an AC circuit, and connect a diode near the inductive load in a DC circuit.
Inductive load
PLC DC Input Unit
Diode
Inductive load
Inductive load
PLC Output Unit
Connect a diode in a DC circuit.
PLC Output Unit
Connect a surge suppressor in an AC circuit.
Input Signal Noise Countermeasures
Connect a diode in a DC circuit.
Output Signal Noise Countermeasures
• Never bundle output signal lines with high-voltage or power lines, and do not route them in close proximity or parallel to such lines. If output signal lines must be routed in close proximity to such lines, place them in separate ducts or conduits and be sure to ground the ducts or conduits. I/O cables I/O cables
Power lines
Power lines
Suspended ducts
I/O cables
Floor ducts
Power lines
Conduit
I/O Cable Arrangement
• If the signal lines and power lines cannot be routed in separate ducts, use shielded cable. Connect the shield to the ground terminal at the PLC, and leave it unconnected at the input device. 5-46
CJ2 CPU Unit Hardware User’s Manual
Page 191
5 Installation
• Wire the lines so that common impedance does not occur. Such wiring will increase the number of wires, so use common return circuits. Use thick wires with sufficient allowance for the return circuits, and bundle them with lines of the same signal level. • For long I/O lines, wire the input and output signal lines separately. • Use twisted-pair wires for pilot lamps (and particularly lamps with filaments). • Use countermeasures, such as CR surge absorbers and diodes, for input device and output load device noise sources, as required.
External Wiring z Wiring Routes Each of the following combinations include different signal types, properties, or levels. They will cause the signal-to-noise ratio to drop due to factors such as electrical induction. As a general rule when wiring, either use separate cables or separate wiring routes for these items. Future maintenance operations and changes to the system will also be made easier by carefully organizing the wiring from the start. • Power lines and signal lines
5-4 Control Panel Installation
Wiring, and noise countermeasures in particular, are based on experience, and it is necessary to closely manage wiring based on experience and information in the manuals.
• Input signals and output signals
5
• Analog signals and digital signals • High-level signals and low-level signals
5-4-5 Electrical Environment
• Communications lines and power lines • DC signals and AC signals • High-frequency devices (such as Inverters) and signal lines (communications)
CJ2 CPU Unit Hardware User’s Manual
5-47
Page 192
5 Installation z Wiring Methods Observe the following points when wiring power supply and signal cables. • When routing signal cables with differing characteristics through the same duct, always keep them separated. • As much as possible, avoid routing multiple power supply lines through the same duct. If it cannot be avoided, then construct a partition between them in the duct and ground the partition. Partition
Signal cables (A)
Signal cables (B)
Signal cables (C)
Power supply cables
Signal cables
(a)
(b)
Signal cables Signal cables
Power supply cables
Power supply cables
(c)
(d)
Partitioning Methods for Signal and Power Supply Cables
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single circuit in separate conduits. Power supply
Load
Incorrect Power supply
Load
Correct Power supply
Load
Correct
Parallel Wiring (Single Phase)
5-48
CJ2 CPU Unit Hardware User’s Manual
Page 193
5 Installation
• Power cables and signal cables adversely affect each other. Do not wire them in parallel. • Noise induction may occur if the PLC is installed in a panel that includes high-voltage devices. Whenever possible, wire and install them separately. (Refer to PLC Installation Location on page 45.) • Either install the PLC a minimum of 200 mm from high-voltage lines or power lines, or place the high-voltage lines or power lines in metal tubing and completely ground the metal tubing to 100 Ω or less. Panel with power line Metal tubing
Power line Power line 200 mm
PLC 200 mm
Ground of 100 Ω or less
Example: Separating PLC from Power Lines z Other Precautions • Basic I/O Units have both plus and minus commons, so pay attention to the polarity when wiring.
• SYSMAC H-PCF Optical Fiber Cables Installation Guide (Cat. No. W156) • Optical Ring Controller Link Units Operation Manual (Cat. No. W370)
CJ2 CPU Unit Hardware User’s Manual
5-49
5 5-4-5 Electrical Environment
• Optical fiber cable looks like ordinary communications cable or power cable, but internally it consists of fibers, tension members, other protective materials. It must be handled with care. In particular, optical fiber cable must be installed according to prescribed methods and standards. Do not subject optical fiber cable to severe tensile shock, excessive bending, twisting, or excessive constriction. For details on wiring optical fiber cables, refer to the following manuals.
5-4 Control Panel Installation
PLC
Page 194
5 Installation
5-4-6
Grounding Grounding has the following two purposes. • Protective Grounding Protective grounding is done to ensure safety. It is intended to prevent electrical shock by grounding the electrical potential that is generated by factors such as leakage, induction, or failure. • Functional Grounding Functional grounding is done to protect device and system functions, including prevention of noise from external sources, or prevention of noise from devices or equipment that could have harmful effects on other devices or equipment. Grounding requirements sometimes depend on the situation, based on experimentation. It is important to sufficiently check the particular circumstances before grounding.
Grounding Methods and Precautions z Principles of One-point Grounding For devices to operate properly, the reference potential between the devices must be stabilized. Use one-point grounding so that noise current does not flow to ground lines between the devices.
z Whenever possible, use an independent ground (with the ground pole separated by a minimum of 10 m from any other ground pole). • Ground to 100 Ω or less, and if possible use a separate ground from those of other devices. (Refer to figure (a) in the diagram below.) • If using an independent ground is not possible, then use a common ground as shown in figure (b). Connect to the ground pole of the other device. • Never connect to the same ground as a device that draws a large amount of power, such as a motor or inverter. Ground the devices separately to avoid mutually adverse influences. • To prevent electrical shock, do not connect to ground poles (especially steel frames) to which multiple devices are connected. • Use a ground pole as close to the PLC as possible and keep the ground line as short as possible. PLC
PLC Other device
PLC Other device
Other device
Common ground: Acceptable
Common ground: Incorrect
Ground of 100 Ω or less
Independent grounds: Best
Grounding Methods
5-50
CJ2 CPU Unit Hardware User’s Manual
Page 195
5 Installation z Precautions when Grounding • If the same ground is used for both the signal lines and the enclosure, isolate the channel base (a grounded metal plate inside a control panel) with an insulating material
Independent ground
CS/CJ-series PLCs have an isolated (floating) mounting structure to make it more difficult to be affected by noise from an installation environment, such as a control panel.
Insulating material
Example: Insulating and Grounding an Enclosure
• To prevent influence from leakage current from other electrical devices, electrically isolate the panel in which the PLC is housed from other devices. • If high-frequency equipment is present, then ground not only the high-frequency equipment but also the panel itself in which the PLC is housed. • As shown in the following diagram, when using shielded cable for I/O wiring, connect the shield near the PLC to the enclosure ground terminal. Follow the instructions in the Communications Unit manual for preparing shielded communications cable.
5-4 Control Panel Installation
Channel base
PLC Input Common
5
Output Common
5-4-6 Grounding
Shielded Cable Ground z PLC Ground Terminals The PLC has the following two ground terminals. Protective ground terminal: Always connected to the PLC chassis to prevent electrical shock. Functional ground terminal: Connected to a neutral point in the noise filter to provide a ground when power supply noise causes malfunctioning.
When the functional ground terminal is correctly grounded, it is generally effective in suppressing power supply common noise. Occasionally, however, grounding this terminal will result in picking up more noise, so be careful when using it.
AC side
PLC side
PLC Ground Terminals z Grounding for AC Power Supply Units When wiring to an AC Power Supply Unit, if one power supply phase of the equipment is grounded, always connect the grounded phase to the L2/N terminal. L1 L2/N
CJ2 CPU Unit Hardware User’s Manual
5-51
Page 196
5 Installation
5-52
CJ2 CPU Unit Hardware User’s Manual