Page 197

Troubleshooting This section describes how to troubleshoot problems that may occur with a CJ2 PLC.

6-1 CPU Unit Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 6-1-1 6-1-2 6-1-3 6-1-4 6-1-5 6-1-6 6-1-7

Errors and Remedies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Checking Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Checking Detailed Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 Reading Error Log Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 I/O Table Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5 Types of Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6 Handling Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7

6-2 Troubleshooting Built-in EtherNet/IP Port Errors (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only) . . . . . . . . . . . . . . . . . . . . . . . 6-25 6-2-1 6-2-2

Checking Built-in EtherNet/IP Port Error Status . . . . . . . . . . . . . . . . . . . . . . 6-25 Checking Error Status at the EtherNet/IP Port Seven-segment Display . . . . 6-26

6-3 Non-CPU Unit Errors and Remedies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28 6-3-1

CJ2 CPU Unit Hardware User’s Manual

Error Causes and Remedies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28

6-1

6

Page 198

6 Troubleshooting

6-1

CPU Unit Errors

6-1-1

Errors and Remedies Use the following procedure when an error occurs. Error occurs.

Check the indicators.

Check the indicators on the front of the CPU Unit and Power Supply Unit, or use the CX-Programmer to read the error status.

Identify the error.

Identify the error from the indicators (refer to 6-1-6 Types of Errors) or use the CX-Programmer to read the error status.

Implement countermeasures.

Take measures to eliminate the error that occurred and to prevent it from occurring again. (Refer to 6-1-7 Handling Errors.)

End

6-1-2

Checking Errors The type of error that occurred can be determined by checking the indicators on the front of the CPU Unit or by using the CX-Programmer. For details on error types, refer to 6-1-6 Types of Errors.

Checking the Indicators Indicators on front of CPU Unit RUN ERR/ALM INH PRPHL COMM BKUP

RUN:

Lit green when the PLC is in RUN or MONITOR mode.

ERR/ALM:

Shows the results of self-diagnosis. Flashing red: Non-fatal error Lit red: Fatal error

INH:

Lit yellow when Output OFF Bit has been turned ON.

PRPHL:

Flashing yellow when the CPU Unit is communicating through the peripheral (USB) port.

COMM*:

Flashing yellow when the CPU Unit is communicating through the RS-232C (USB) port.

BKUP:

Flashing yellow when data is being backed up from RAM to built-in flash memory.

* The CJ2M-CPU3@ does not have this indicator.

POWER:

Power Supply Unit

Lit when 5 V is output from the Power Supply Unit.

Power indicator

6-2

CJ2 CPU Unit Hardware User’s Manual

Page 199

6 Troubleshooting

Checking Error Status with the CX-Programmer Use the following procedure to read the error status.

1 Connect the CX-Programmer online. 2 Double-click Error Log in the project tree in the main window. The PLC Error Window will be displayed.

3 Click the Errors Tab. The current errors will be displayed on the Errors Tab Page.

6-1 CPU Unit Errors

6-1-3

Checking Detailed Status You can check detailed error status using information registered in the Auxiliary Area. The following error details are registered. • Error Flags:

The Auxiliary Area contains flags that indicate the type of error. There are error flags for various types of error.

• Error Code:

6-1-4

The error code assigned to the current error is stored in word A400 regardless of the type of error. If two or more errors occur at the same time, the highest (most serious) error code will be stored in A400.

Reading Error Log Information If the error status could not be checked when the error occurred, it can be checked by reading error log data. The following information is stored in the error log. • Error code (This is the same error code as is stored in word A400.) • Error information • Time of occurrence

CJ2 CPU Unit Hardware User’s Manual

6-3

6-1-3 Checking Detailed Status

• Error Information: The Auxiliary Area contains words that provide detailed information on current errors. Error information is provided for various types of error.

6

Page 200

6 Troubleshooting

Error Log Information A maximum of 20 error records will be stored in the error log. If more than 20 errors occur, the oldest error record (in A100 to A104) will be deleted and the 19 records stored in A105 to A199 will be shifted by one, with the newest record being stored in A195 to A199. Error code

4102

Order of occurrence Error Log Area

1 A100

00F7

2

1

0

2

Error code

A101

Error contents

A102 A103

Minute, second Day, hour

A104

Year, month

A105

009D

4

0

0

F

7

Time of occurrence

Error code

A106

Error contents

A107 A108

Minute, second Day, hour

A109

Year, month

Time of occurrence

20

A195

0

0

9

D

Error code

A196

Error contents

A197 A198

Minute, second Day, hour

A199

Year, month

Time of occurrence

A300 Error log pointer

Checking Error Log Information The following methods can be used to check error log information with the CX-Programmer.

z CX-Programmer PLC Error Window Check the error log by clicking the Error Log Tab in the PLC Errors Window of the PLC.

The error information is displayed here. The error code is displayed here.

The example above shows that unit number 17 has been duplicated for Special I/O Units. • Error code 80E9: Unit number duplication error • Error information: 80 “11”: 11 hex = 17 decimal For details on error codes and error information, refer to A-3 Fatal and Non-fatal Error Details.

z Directly Monitoring the Area where Error Log Information is Stored

1 Connect the CX-Programmer online. 2 Read words A100 to A199. 6-4

CJ2 CPU Unit Hardware User’s Manual

Page 201

6 Troubleshooting

3 Check the error status from the registered data. 6-1-5

I/O Table Verification When an I/O verification error or a CPU standby error occurs, the following procedure can be used to verify the I/O tables to locate where the error occurred. With the CX-Programmer, use the following procedure.

1 Double-click I/O Tables in the project tree in the main window. The I/O Table Window will be displayed.

2 Select Verify from the Options Menu in the I/O Table Window. The I/O table verification results will be displayed.

6-1 CPU Unit Errors

6 6-1-5 I/O Table Verification

CJ2 CPU Unit Hardware User’s Manual

6-5

Page 202

6 Troubleshooting

6-1-6

Types of Errors The type of error that has occurred can be identified by checking the indicators on the front of the CPU Unit and the Power Supply Unit, or by using the CX-Programmer to check the error status. The errors detected by the CPU Unit are listed in the following table. For details on errors that are not detected by the CPU Unit, refer to 6-3 Non-CPU Unit Errors and Remedies.

Error name

POWER

RUN

ERR/ALM

INH

PRPHL

COMM

Error code (stored in A400)

Operation status

Power supply error

OFF

OFF

OFF

OFF

OFF

OFF

---

Operation stops.

CPU Standby

ON

OFF

OFF

---

---

---

---

Operation stops.

---

Operation stops.

ON

OFF

ON

---

---

---

---

Operation stops.

CPU reset CPU error (WDT error)*1 USB port communications error

ON

ON

OFF

---

OFF

---

---

Operation continues.

RS-232C port communications error

ON

ON

OFF

---

---

OFF

---

Operation continues.

ON

OFF

ON

---

---

---

0x809F

Operation stops.

Fatal errors*1*2

Cycle time exceeded error I/O bus error

0x80C0 to 0x80C7, 0x80CE, 0x80CF

I/O setting error

0x80E0

Too many I/O points error

0x80E1

Unit number duplication error

0x80E9

Rack number duplication error

0x80EA

Program error

0x80F0

Memory error

0x80F1

Version error

0x80F2

Memory Card Transfer Error

0x80F4

FALS (007) error

0xC101 to 0xC2FF

Non-fatal errors*2

Duplicated refreshing error

ON

ON

Flashing

---

---

---

0x008B

Basic I/O error

0x009A

PLC Setup error

0x009B

Option Board error

0x00D1

Backup memory error

0x00F1

Tag memory error*3

0x00F2

System work errors

0x00F3

Battery error

0x00F7

CPU Bus Unit error

0x0200 to 0x020F

Special I/O Unit error

0x0300 to 0x035F, 0x03FF

CPU Bus Unit setting error

0x0400 to 0x040F

FAL (006) error

0x4101 to 0x42FF

Special I/O Unit setting error

0x0500 to 0x055F

Operation continues.

*1 The indicator status is the same for CPU errors and fatal errors, but they can be distinguished because a Programming Device can be connected when a fatal error occurs, but not when a CPU error occurs. *2 For details on fatal errors and non-fatal errors, refer to A-3 Fatal and Non-fatal Error Details. *3 CJ2H-CPU6@-EIP only. Note The indicator status shows the status of the errors that have occurred in RUN or MONITOR mode.

6-6

CJ2 CPU Unit Hardware User’s Manual

Page 203

6 Troubleshooting

6-1-7

Handling Errors This section describes the measures to take for the errors that most commonly occur. First check the error status. Then, make a preliminary determination of the cause of the error, confirm the cause, correct the error, and take measures to ensure that it will not occur again. For all other errors, refer to A-3 Fatal and Non-fatal Error Details.

Power Supply Errors A power supply error occurs when a voltage of 5 V is not output from the Power Supply Unit. POWER Not lit.

RUN Not lit.

Suspected cause of error

ERR/ALM Not lit.

Error code

Error information

None

None

Error flag None

Confirmation method

Remedy

Prevention of recurrence

Use a tester to measure the volt- Turn the power ON age at the input terminals of the again. Power Supply Unit.*1

Investigate the reason that the power was turned OFF.

Connection status of power supply selector terminals

• 100 VAC: Use a tester check for shortcircuits. • 200 VAC: Check for disconnections.

Periodically (approximately once a year) tighten the terminal connections.

The voltage is out of the allowable range for the power supply.

Use a tester to measure the volt- Correct the power supage at the input terminals to the ply system for the PLC. Power Supply Unit.*1

Same as at the left.

Power Supply Unit failure

Replace the Power Supply Unit and check operation. (Check whether the POWER indicator is lit.)

Replace the Power Supply Unit.

Depends on the type of error.

Failure at another Unit

Remove in order the Units mounted in the Rack and check the POWER indicator.

Replace the failed Unit. Depends on the type of error.

Reconnect and secure the terminal connections.

6 6-1-7 Handling Errors

*1 The following table shows the allowable power supply ranges for each Power Supply Unit model. Power supply voltage

Allowable power supply voltage fluctuation

CJ1W-PA205R/PA202

100 to 240 VAC

85 to 264 VAC

CJ1W-PD025

24 VDC

19.2 to 28.8 VDC

Model

CJ2 CPU Unit Hardware User’s Manual

6-1 CPU Unit Errors

Power is not being input.

6-7

Page 204

6 Troubleshooting

CPU Standby Errors When a CJ-series PLC is turned ON, the CPU starts cyclic servicing and enters RUN mode only after all Special I/O Units and CPU Bus Units have been detected. If the startup mode is RUN or MONITOR mode, the CPU will remain on standby until all Units have been detected. POWER Lit.

RUN

ERR/ALM

Not lit.

Not lit.

Error flag None

Error code

Error information

None

None z Recovery Processing Flow CPU standby

Check the location of the error.

Use the I/O table verification procedure (refer to 6-1-5 I/O Table Verification) to check the location where the error occurred.

Check the connection status.

Check the connections to the Special I/O Units and CPU Bus Units.

Replace the Unit.

Is the error cleared?

Replace the Unit, or remove the Unit and check whether the error is cleared (to determine that the Unit that was replaced or removed just before the error was cleared was the problem). No

Yes Restart the System.

z Error Causes and Remedies Suspected cause of error

6-8

Confirmation method

Prevention of recurrence

Remedy

Faulty connection at Unit (at a connector)

Check the insertion at the connector. Restart the Unit and check whether the error is cleared.

Tighten the screws.

Same as at the left.

Unit failure

Replace the Unit that is causing the standby (the undetected Unit). If the error is not cleared, remove the Units in order until the status returns to normal.

• Replace the Special I/O Unit or Interrupt Unit for which “$” is displayed when the I/O tables are read. • Replace the failed Unit.

(Determined by the cause of the failure.)

The remote I/O power supply is OFF or there is no terminator for SYSMAC BUS.

Check whether the power is Turn ON the power or set the turned ON. Check the termi- terminators. If the error is not nator settings. cleared, replace the Unit.

---

CJ2 CPU Unit Hardware User’s Manual

Page 205

6 Troubleshooting

Additional Information The CJ2 CPU Units support the following function. • Startup Condition Setting After the power supply is turned ON, it is possible to start operation of the CPU Unit in RUN mode or MONITOR mode even if there is one or more Units that has not completed startup. Select the Start running program when initializing Unit/Inner board recognition Check Box in the PLC Setup. For details, refer to the CJ-series CJ2 CPU Unit Software User's Manual (Cat. No. W473).

CPU Reset The CPU Unit is being reset, and Programming Devices cannot be connected. POWER

Not lit.

ERR/ALM Not lit.

Error code

Error information

None

None

Error flag None z Error Causes and Remedies Confirmation method

Remedy

Power to an Expansion Rack is OFF.

Use a tester to measure the voltage at the input terminals of the Power Supply Unit.*1

Turn ON the power.

The I/O Connecting Cable is incorrectly installed. Check the connections.

Reconnect the cable.

• The IN-OUT connectors are reversed. • The cable does not have good contact at the connectors. • Two or more I/O Control Units are mounted on the CPU Rack, or an I/O Control Unit is mounted to an Expansion Rack.

Prevention of recurrence Investigate the reason that the power was OFF.

6

If the Cable is disconnected, check for vibration and shock.

*1 The following table shows the allowable power supply ranges for each Power Supply Unit. Power supply voltage

Allowable power supply voltage fluctuation

CJ1W-PA205R/PA202

100 to 240 VAC

85 to 264 VAC

CJ1W-PD025

24 VDC

19.2 to 28.8 VDC

Model

Precautions for Correct Use Observe the following points when using Expansion Racks. • Always confirm the safety of any related equipment before turning the power supply ON or OFF. • When the power supply is interrupted to an Expansion Rack, the CPU Unit will stop program execution and the same operations as are performed when the power supply to the CPU Unit is interrupted will be performed. For example, if the power OFF interrupt task is enabled, it will be executed. If power is then restored to the Expansion Rack, the CPU Unit will perform startup processing. The same operational status as existed before the power interrupt will not necessarily be continued.

CJ2 CPU Unit Hardware User’s Manual

6-9

6-1-7 Handling Errors

Suspected cause of error

6-1 CPU Unit Errors

Lit.

RUN