Page 206
6 Troubleshooting
CPU Errors CPU errors are error that occur in the CPU Unit itself. A CPU error occurs when the WDT (watchdog timer) times out. Programming Devices cannot be connected when a CPU error occurs. POWER Lit.
RUN Not lit.
ERR/ALM Lit.
Error flag None
Error code None
Error information None z Error Causes and Remedies Suspected cause of error Unit failure
Prevention of recurrence
Confirmation method
Remedy
A CPU error has possibly occurred in the following cases.
Replace the CPU Unit.
Same as at the left.
• If the error is not cleared when the CPU Unit is restarted after the recovery measures. • If the error occurs frequently • If the condition improves when the Unit is replaced. A conductive object has gotten inside.
Check for conductive objects.
Clean the inside of the Unit with an air blower or replace the CPU Unit.
Do not do any metal working in the vicinity of the control panel. Close the control panel.
Noise
When the CPU Unit is restarted after the recovery measures, the error will either be cleared or will continue to occur. Check whether errors become less frequent after the Unit is replaced.
Take measures against noise. (Investigate the path of entry.)
Same as at the left.
• The microcomputer inside the CPU Unit is malfunctioning.
• FG • Power lines
Precautions for Correct Use • Always confirm the safety of any related equipment before turning the power supply ON or OFF. • When power supply is interrupted to an Expansion Rack, the CPU Unit will stop program execution and the same operations as are performed when the power supply to the CPU Unit is interrupted will be performed. For example, if the power OFF interrupt task is enabled, it will be executed. If power is then restored to the Expansion Rack, the CPU Unit will perform startup processing. The same operational status as existed before the power interrupt will not necessarily be continued.
6-10
CJ2 CPU Unit Hardware User’s Manual
Page 207
6 Troubleshooting
Communications Error (Peripheral (USB) Port) A communications error will occur if there is an error in communications between the peripheral (USB) Port and a connected device. POWER Lit.
RUN Lit.
ERR/ALM
PRPHL
COMM
Error flag
Error code
Error information
Not lit.
Not lit.
Not lit.
None
None
None z Error Causes and Remedies Suspected cause of error
Confirmation method
The communications cable is disconnected.
Remedy
Perform a visual inspecReconnect the cables. tion and pull on the cables.
Prevention of recurrence During operation, confirm that the connections are secure. Check for vibration or shock.
A communications error will occur if there is an error in communications between the serial (RS-232C) port and a connected device. POWER Lit.
RUN Lit.
ERR/ALM
PRPHL
COMM
Error flag
Error code
Error information
Not lit.
Not lit.
Not lit.
None
None
None
6-1 CPU Unit Errors
Communications Error (Serial Port (RS-232C))
z Error Causes and Remedies Suspected cause of error
Prevention of recurrence
Remedy
Communications settings are incorrect.
• Check whether the DIP switch pin 5 setting and and the serial port settings in the PLC Setup are correct. • If a host computer is connected, check the host computer serial port settings and the program.
• Correctly set DIP switch pin 5 and the serial port settings in the PLC Setup. • Correct the host computer serial port settings and the program.
Same as at the left.
A communications cable is incorrectly connected.
• Check the cable connections.
• Correct the cable connections.
Same as at the left.
Reconnect the cables.
During operation, confirm that the connections are secure. Check for effects of vibration or shock.
A communications Perform a visual inspection cable is disconnected. and pull on the cables.
CJ2 CPU Unit Hardware User’s Manual
6 6-1-7 Handling Errors
Confirmation method
6-11
Page 208
6 Troubleshooting
Cycle Time Exceeded Error (Fatal Error) z Cycle Time Exceeded Error A cycle time exceeded error will occur if the PLC cycle time exceeds the setting for Watch Cycle Time in the PLC Setup. POWER Lit.
RUN Not lit.
ERR/ALM Lit.
Error flag A401.08
Error code
Error information
809F
None z Error Causes and Remedies Suspected cause of error
Confirmation method
Remedy
Prevention of recurrence
An interrupt task with a long processing time was executed.
Check the Max. Interrupt Task Processing Time (A440)*
Divide the interrupt task into sections.
Same as at the left.
An incorrect value (an extremely large number) was set for the number of repeats of FOR(512).
Set up a trap in the ladder program to monitor the number of repeats.
Correct the ladder program.
Same as at the left.
* The maximum processing time for an interrupt task will not be stored in A440 if High-speed interrupt function is enabled in the PLC Setup.
6-12
CJ2 CPU Unit Hardware User’s Manual
Page 209
6 Troubleshooting
I/O Bus Error (Fatal Error) An I/O bus error will occur if there is an error in a data transfer between the CPU Unit and a Unit connected in the Rack. POWER Lit.
RUN
ERR/ALM
Not lit.
Lit.
Error flag A401.10
Error code 80C0 to 80C7 or 80CF
Error information A404*1
*1 The numbers of the slot and Rack where the I/O bus error was detected are stored in word A404. 15
08
07
01
A404 The number of the slot where the error occurred in binary. (If it cannot be determined, “0F” will be stored.) The number of the Rack where the error occurred in binary (If it cannot be determined, “0F” will be stored.)
6-1 CPU Unit Errors z Recovery Processing Flow I/O bus error occurs.
Check the error status.
Check the error code and error information.
Restart the PLC
6-1-7 Handling Errors
Is the error cleared?
6
Turn the power OFF and back ON.
No
Yes Check the I/O Connecting Cable connections between all Racks. Check the Unit installation.
Restart the PLC.
Is the error cleared? Yes No Replace the Unit or the I/O Connecting Cable.
Restart the PLC.
Restart the System.
CJ2 CPU Unit Hardware User’s Manual
6-13
Page 210
6 Troubleshooting z Error Causes and Remedies Suspected cause of error
Prevention of recurrence
Remedy
The I/O Connecting Cable is disconnected.
Perform a visual inspection and pull on the Cables.
Reconnect the cables.
During operation, confirm that the connections are secure. Check for vibration or shock.
Equipment failure
An I/O bus error has possibly occurred in the following cases.
Replace the equipment.
---
• CPU Unit • I/O Connecting Cable (damage to bus interface circuit)
• CPU Unit • I/O Connecting Cable
• If the error is not cleared when the CPU Unit is restarted • If the error occurs frequently • If the condition improves when the Unit is replaced.
A conductive object has gotten inside.
Check for conductive objects.
Clean the inside of the Unit with an air blower or replace the CPU Unit.
Do not do any metal working in the vicinity of the control panel. Close the control panel.
Faulty connector contact (A foreign object has gotten inside.)
Check for foreign objects in the connector.
Replace the Unit or take off the connector and remove the foreign object.
Make sure that the operating environment is free of dirt and dust.
Noise
When the CPU Unit is restarted after the recovery measures, the error will either be cleared or will continue to occur. Check whether errors become less frequent after the Unit is replaced.
Take measures against noise. (Investigate the path of entry.)
Same as at the left.
• Data corruption in bus signals • Malfunctioning in bus interface circuit
6-14
Confirmation method
• FG • Power lines • I/O connecting cable (inductive noise)
CJ2 CPU Unit Hardware User’s Manual
Page 211
6 Troubleshooting
I/O Setting Error (Fatal Error) An I/O setting error will occur if the Units that are actually connected do not match the Unit in the registered I/O tables. POWER Lit.
RUN Not lit.
ERR/ALM Flashing.
Error flag A401.10
Error code
Error information
80E0
--- z Recovery Processing Flow I/O setting error Check the location of the error.
Use the I/O table verification procedure (refer to 6-1-5 I/O Table Verification) to check where the error occurred. Turn the power OFF and back ON.
Restart the PLC.
6-1 CPU Unit Errors
Is the error cleared?
No Check the Unit connections.
Yes
Replace the Unit where the error occurred.
6
Restart the PLC.
z Error Causes and Remedies Suspected cause of error
Confirmation method
Remedy
Prevention of recurrence
Faulty connection at Unit (at a connector)
Check the insertion at the connector. Restart the Unit and check whether the error is cleared.
Tighten the screws.
Same as at the left.
Unit failure
If restarting the Unit does not clear the error, check whether the error is cleared by replacing the Unit.
Replace the applicable Unit.
Same as at the left.
Noise
Restart the CPU Unit and check whether the error continues to occur.
Take measures against noise. (Investigate the path of entry.)
Same as at the left.
• Data corruption in bus signals
• FG • Power lines
CJ2 CPU Unit Hardware User’s Manual
6-15
6-1-7 Handling Errors
Restart the System.
Page 212
6 Troubleshooting
Memory Error (Fatal Error) A memory error will occur if there is a memory error in the CPU Unit or if a checksum error is detected (checksum checked by the PLC with each cycle). The details of the cause of the error will be stored in the error information in the Auxiliary Area. POWER Lit.
RUN
ERR/ALM
Not lit.
Lit.
Error flag A401.15
Error code
Error information
80F1
A403*1
*1 Individual bits in A403 indicate where the memory error occurred.
z Recovery Measures Check the detailed error contents in the error information in the Auxiliary Area, and then implement the following recovery measures. If these measures cannot solve the problem, there is a strong probability that the Unit has failed, so replace the Unit. Error information
Error contents
Recovery measures
A403.00: ON
A checksum error has occurred in the user program memory.
Transfer the user program to the CPU Unit again.
A403.04: ON
A checksum error has occurred in the PLC Setup.
Transfer the PLC Setup to the CPU Unit again.
A403.05: ON
A checksum error has occurred in the reg- Transfer the I/O tables to the CPU Unit istered I/O table. again.
A403.07: ON
A checksum error has occurred in the routing tables.
Transfer the routing tables to the CPU Unit again.
A403.08: ON
A checksum error has occurred in the CPU Bus Unit setup.
Transfer the CPU Bus Unit setup again.
Additional Information Checksums are used to detect illegal rewriting in a specific area of memory by calculating and comparing sums written to memory in advance to sums during operation. When a checksum error is detected by the CJ2 CPU Unit during operation, memory is automatically recovered by automatically reading data from flash memory. If recovery is not possible, an error occurs and operation stops. Use any of the following methods to transfer the data again. • Use the CX-Programmer to download data. • Use the automatic transfer at startup function to download data saved on a Memory Card. For details, refer to the CJ-series CJ2 CPU Unit Software User's Manual (Cat. No. W473). • Use the simple backup function to download data saved on a Memory Card. For details, refer to 8-3 Simple Backup. The CJ2 CPU Unit has built-in flash memory for backup. When the CPU Unit is restarted, data is transferred to memory for calculation and this sometimes enables an error to be cleared.
6-16
CJ2 CPU Unit Hardware User’s Manual
Page 213
6 Troubleshooting z Recovery Processing Flow Memory error
Check the error status. Implement the remedy.
Is the error cleared?
No
Yes
Replace the Unit.
Restart the System.
If the measures described above do not clear the error, take the measures shown in the following table. Suspected cause of error Unit failure • Memory element failure • Memory peripheral circuit failure
Confirmation method
Remedy
A memory error has prob- Replace the CPU Unit. ably occurred in the following cases.
Prevention of recurrence Determined by the cause of the failure.
6
Check for conductive objects.
Clean the inside of the Unit with an air blower or replace the CPU Unit.
Do not do any metal working in the vicinity of the control panel. Close the control panel.
Noise
When the CPU Unit is restarted after the recovery measures, the error will either be cleared or will continue to occur. Check whether errors become less frequent after the Unit is replaced.
Take measures against noise. (Investigate the path of entry.)
Same as at the left.
• Data corruption in memory • Microcomputer malfunctioning • Memory write circuit malfunctioning Software error*1
None
None
• FG • Power lines
None
*1 This refers to errors caused by data corruption. SRAM is used for the CPU Unit user memory. SRAM is affected by cosmic rays (neutrons) and naturally occurring radiation, so data can become corrupted.
6-17
6-1-7 Handling Errors
• If the error is not cleared when the CPU Unit is restarted after the recovery measures • If the error occurs frequently • If the condition improves when the Unit is replaced.
A conductive object has gotten inside.
CJ2 CPU Unit Hardware User’s Manual
6-1 CPU Unit Errors z Error Causes and Remedies
Page 214
6 Troubleshooting
Basic I/O Error (Non-fatal Error) A basic I/O error occurs when there is an error at a Basic I/O Unit. POWER Lit.
RUN
ERR/ALM
Lit.
Flashing.
Error code
Error information
009A
A408*1
Error flag A402.12
*1 Error Information 15
08
07
01
A408 Number of slot where the Unit with the error is mounted in binary. Number of Rack where the Unit with the error is mounted in binary.
z Recovery Processing Flow Basic I/O error occurs.
Check the location of the error.
Replace the Unit.
Check the error information (A408).
Check the cause of the error, and take measures to prevent it from occurring again.
Restart the System.
z Error Causes and Remedies Suspected cause of error
6-18
Prevention of recurrence
Confirmation method
Remedy
A fuse is burned out.
Measure the voltage at the power supply terminals. Check whether 24 V is being supplied. (Check whether the problem is solved by replacing the fuse.)
Replace the fuse.
The external power supply is OFF (disconnected).
Measure the voltage at the power supply terminals. Check whether 24 V is being supplied.
Turn ON the power supply. Investigate the reason that the power was turned OFF.
Other errors specific to Units
Refer to the manual for the particular Unit.
Same as at the left.
Check the maximum switching current.
Same as at the left.
CJ2 CPU Unit Hardware User’s Manual