Page 215
6 Troubleshooting
Option Board Errors An Option Board error will occur if the Option Board is removed while the power is being supplied. POWER Lit.
RUN
ERR/ALM
Lit.
Flashing.
Error flag A315.13
Error code
Error information
00D1
---
A402.00 z Recovery Processing Flow Option Board error occurs.
Check the location of the error.
Restart the PLC. 6-1 CPU Unit Errors
Recovered? No Check the Unit connections.
Yes
Replace the Option Board.
6
Restart the PLC.
z Error Causes and Remedies Suspected cause of error
Confirmation method
Remedy
Prevention of recurrence
The Option Board was removed while the system was operating.
Check the mating of the Option Board connector.
Reconnect.
Option Board failure
If restarting does not clear the error, check whether the error is cleared by replacing the Option Board.
Replace the Option Board. Same as at the left.
CJ2 CPU Unit Hardware User’s Manual
Check for vibration and shock.
6-19
6-1-7 Handling Errors
Restart the System.
Page 216
6 Troubleshooting
Battery Error (Non-fatal Error) A battery error occurs when the battery voltage drops. POWER Lit.
RUN
ERR/ALM
Lit.
Flashing.
Error flag A402.04
Error code
Error information
00F7
--- z Recovery Processing Flow Battery error occurs. Check the battery connections. Normal?
Yes
No Reconnect
Replace the battery.
Restart the System.
z Error Causes and Remedies Suspected cause of error
6-20
Prevention of recurrence
Confirmation method
Remedy
A connector is disconnected.
Check the connection at the connector.
Reconnect the connector.
Check for vibration and shock.
Battery voltage is low.
Check whether the error is cleared by replacing the battery.
Replace the battery.
Periodically replace the battery.
For details, refer to 7-2 Replacing the Battery.
CJ2 CPU Unit Hardware User’s Manual
Page 217
6 Troubleshooting
CPU Bus Unit Error (Non-fatal Error) A CPU Bus Unit error occurs when there is an error in the data conversion between the CPU Unit and a CPU Bus Unit. POWER Lit.
RUN
ERR/ALM
Lit.
Flashing.
Error flag A402.07
Error code
Error information
0200 to 020F
A417*
* The bit corresponding to the unit number where the error occurred turns ON. (Bits 00 to 15 correspond to unit numbers 0 to F.)
z Recovery Processing Flow CPU Bus Unit error occurs. Check the location where the error occurred.
Use the I/O table verification procedure (refer to 6-1-5 I/O Table Verification) to check where the error occurred.
Is the error cleared?
6-1 CPU Unit Errors
Turn the power OFF and back ON.
Restart the PLC
No
Yes
Check the Unit connections
6
Replace the Unit where the error occurred.
6-1-7 Handling Errors
Restart the PLC.
Restart the System.
z Error Causes and Remedies Suspected cause of error
Confirmation method
An error specific to the Unit
Refer to the manual for the particular Unit.
Same as at the left.
Same as at the left.
Faulty connection at Unit (at a connector)
Check the insertion at the connector. Restart the Unit and check whether the error is cleared.
Tighten the screws.
Check for vibration and shock.
Unit failure
If restarting the Unit does not clear the error, check whether the error is cleared by replacing the Unit.
Replace the applicable Unit.
Same as at the left.
Noise
Restart the CPU Unit and check whether the error occurs again.
Take measures against noise. (Investigate the path of entry.)
Same as at the left.
• Data corruption in bus signals
Remedy
Prevention of recurrence
• FG • Power lines
CJ2 CPU Unit Hardware User’s Manual
6-21
Page 218
6 Troubleshooting
Special I/O Unit Error (Non-fatal Error) A Special I/O Unit error occurs when there is an error in the data conversion between the CPU Unit and a Special I/O Unit. POWER Lit.
RUN
ERR/ALM
Lit.
Flashing.
Error flag A402.06
Error code
Error information
0300 to 035F or 03FF
A418 to A423 *
* The bit corresponding to the unit number where the error occurred turns ON.
z Recovery Processing Flow Special I/O Unit error occurs. Restart the Special I/O Unit.
Reset, or turn the power OFF and back ON.
Is the error cleared? No Yes
Check the Unit connections.
Replace the Special I/O Unit.
Restart the Special I/O Unit.
Restart the System.
z Error Causes and Remedies Suspected cause of error
Confirmation method
An error specific to the Unit
Refer to the manual for the particular Unit.
Same as at the left.
Same as at the left.
Faulty connection at Unit (at a connector)
Check the insertion at the connector. Restart the Unit and check whether the error is cleared.
Tighten the screws.
Check for vibration and shock.
Unit failure
If restarting the Unit does not clear the error, check whether the error is cleared by replacing the Unit.
Replace the applicable Unit.
Same as at the left.
Noise
Restart the CPU Unit and check whether the error occurs again after this.
Take measures against noise. (Investigate the path of entry.)
Same as at the left.
• Data corruption in bus signals
Prevention of recurrence
Remedy
• FG • Power lines
6-22
CJ2 CPU Unit Hardware User’s Manual
Page 219
6 Troubleshooting
Special I/O Unit Setting Error (Non-fatal Error) A Special I/O Unit setting error will occur if a Unit registered in the registered I/O tables does not agree with the Unit actually connected in the PLC. A Special I/O Unit setting error will also occur if a Unit set as a Synchronous Unit in the synchronous operation parameter settings is not actually connected in the PLC or does not support synchronous unit operation. POWER Lit.
RUN Lit.
ERR/ALM
Error flag
Error code
Flashing.
A402.02
0500 to 055F
Error information A428 to A433*
* The bit corresponding to the Unit for which the error occurred will turn ON.
z Recovery Processing Flow Special I/O Unit setting error occurs. 6-1 CPU Unit Errors
Synchronous unit operation being used?
No
Yes Check if error is caused by synchronous unit operation settings. (A428 to A433 will tell you which Unit caused the error.)
6 6-1-7 Handling Errors
Perform the recovery procedure.
Operation recovered?
No
Yes Check if error is caused by registered I/O settings. (A428 to A433 will tell you which Unit caused the error.)
Perform the recovery procedure.
Restart the system.
CJ2 CPU Unit Hardware User’s Manual
6-23
Page 220
6 Troubleshooting z Error Causes and Remedies for Synchronous Unit Operation Settings Suspected cause of error
Confirmation method
Prevention of recurrence
Remedy
A Unit set in the synchronous unit operation settings does not support synchronous unit operation.
Check the operation manual for the Unit.
Transfer the settings again.
Same as at the left.
A Unit set in the synchronous unit operation settings does not exist in the PLC.
Check the Units in the PLC.
Transfer the settings again.
Same as at the left.
A Unit set in the synchronous unit operation settings does not exist on the CPU Rack (i.e., it is on an Expansion Rack).
Check the Units in the PLC.
Move the Synchronous Unit to the CPU Rack.
Same as at the left.
If I/O tables have been registered, change the registered I/O tables.
z Error Causes and Remedies for Registered I/O Table Settings Suspected cause of error The model of a CPU Bus Unit in the registered I/O tables is different from the model the Unit actually mounted in the PLC.
6-24
Confirmation method Check the Units in the PLC.
Prevention of recurrence
Remedy Correct the I/O table settings.
Same as at the left.
CJ2 CPU Unit Hardware User’s Manual
Page 221
6 Troubleshooting
Troubleshooting Built-in EtherNet/IP Port Errors (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only)
6-2-1
Checking Built-in EtherNet/IP Port Error Status Built-in EtherNet/IP port errors can be checked on the built-in EtherNet/IP port seven-segment display on the front of the CJ2H-CPU6@-EIP or CJ2M-CPU3@ CPU Unit.
Built-in EtherNet/IP port seven-segment display
Precautions for Correct Use • For details on the types of errors related to the built-in EtherNet/IP port, and measures for handling them, refer to the CS/CJ Series EtherNet/IP Units Operation Manual (Cat. No. W465).
6-2 Built-in EtherNet/IP Port Errors and Remedies (CJ2H-CPU6@-EIP Only)
6-2
6 6-2-1 Checking Built-in EtherNet/IP Port Error Status
CJ2 CPU Unit Hardware User’s Manual
6-25
Page 222
6 Troubleshooting
6-2-2
Checking Error Status at the EtherNet/IP Port Seven-segment Display
Built-in EtherNet/IP port seven-segment display
The seven-segment display alternately displays the built-in EtherNet/IP port node address and the following error codes.
z Normal Operation Indications MS Lit green
NS Lit or flashing green
Error
7-segment Built-in EtherNet/IP port node address
Normal z Errors Related to CPU Unit Data Exchange Indications MS
NS
Error
7-segment
Flashing red
Not lit
H1
Duplicate unit number
Flashing red
Not lit
H2
CPU Unit faulty
Lit red
Not lit
H3
Built-in EtherNet/IP port faulty
Flashing red
Not lit
H4
Node address setting error
Flashing red
Not lit
H6
CPU Unit faulty
Flashing red
Not lit
H7
I/O table not registered
Flashing red
---
H8
Simple backup function restore error
Flashing red
---
H9
I/O bus error
Flashing red
---
HA
CPU Unit memory error
Flashing red
Not lit
Hb
CPU Unit event servicing timeout
Flashing red
---
HC
Routing table error
Flashing red
---
Hd
I/O refresh error
Flashing red
---
HE
CPU Unit service monitoring error
Flashing red
---
HF
CPU Unit watchdog timer error z Errors Related to the CPU Unit Indications MS
NS
Error
7-segment
Flashing red
---
HH
CPU Unit Fatal Error
---
---
---
Output OFF Error z Errors Related to the Control Bits Indications MS ---
6-26
NS ---
Error
7-segment C6
Multiple Switches ON
CJ2 CPU Unit Hardware User’s Manual
Page 223
6 Troubleshooting z Errors Related to the Tag Data Links MS
NS
6-2 Built-in EtherNet/IP Port Errors and Remedies (CJ2H-CPU6@-EIP Only)
Indications
Error
7-segment
---
--- d5
Verification Error (target non-existent)
---
--- d6
Connection Failed
---
--- d9
Tag Data Link Error z Errors Related to Memory Access Indications MS
NS
Error
7-segment
Flashing red
---
E9
Memory Access Error
Flashing red
---
E8
Device Parameters Error
Flashing red
---
EA
IP Advanced Settings Error
Flashing red
---
F2
Ethernet Basic Settings Error z Errors Related to the Network Indications MS
NS
Error
7-segment
---
---
E1
Ethernet Link Not Detected
---
---
E3
Server Connection Error
---
Lit red
F0
IP Address Duplication
Flashing red
---
F3
Address mismatch
Flashing red
Not lit
F4
Communications Controller Error
Flashing red
---
C8
Node Address Setting Changed During Operation
6 6-2-2 Checking Error Status at the EtherNet/IP Port Seven-segment Display z Errors Related to Units Indicator MS Lit red
NS Not lit
CJ2 CPU Unit Hardware User’s Manual
Error
7-segment ---
CPU Bus Unit Error
6-27