6 Troubleshooting

Option Board Errors An Option Board error will occur if the Option Board is removed while the power is being supplied. POWER Lit.

RUN

ERR/ALM

Lit.

Flashing.

Error flag A315.13

Error code

Error information

00D1

---

A402.00 z Recovery Processing Flow Option Board error occurs.

Check the location of the error.

Restart the PLC. 6-1 CPU Unit Errors

Recovered? No Check the Unit connections.

Yes

Replace the Option Board.

6

Restart the PLC.

z Error Causes and Remedies Suspected cause of error

Confirmation method

Remedy

Prevention of recurrence

The Option Board was removed while the system was operating.

Check the mating of the Option Board connector.

Reconnect.

Option Board failure

If restarting does not clear the error, check whether the error is cleared by replacing the Option Board.

Replace the Option Board. Same as at the left.

CJ2 CPU Unit Hardware User’s Manual

Check for vibration and shock.

6-19

6-1-7 Handling Errors

Restart the System.

Page 216

6 Troubleshooting

Battery Error (Non-fatal Error) A battery error occurs when the battery voltage drops. POWER Lit.

RUN

ERR/ALM

Lit.

Flashing.

Error flag A402.04

Error code

Error information

00F7

--- z Recovery Processing Flow Battery error occurs. Check the battery connections. Normal?

Yes

No Reconnect

Replace the battery.

Restart the System.

z Error Causes and Remedies Suspected cause of error

6-20

Prevention of recurrence

Confirmation method

Remedy

A connector is disconnected.

Check the connection at the connector.

Reconnect the connector.

Check for vibration and shock.

Battery voltage is low.

Check whether the error is cleared by replacing the battery.

Replace the battery.

Periodically replace the battery.

For details, refer to 7-2 Replacing the Battery.

CJ2 CPU Unit Hardware User’s Manual

Page 217

6 Troubleshooting

CPU Bus Unit Error (Non-fatal Error) A CPU Bus Unit error occurs when there is an error in the data conversion between the CPU Unit and a CPU Bus Unit. POWER Lit.

RUN

ERR/ALM

Lit.

Flashing.

Error flag A402.07

Error code

Error information

0200 to 020F

A417*

* The bit corresponding to the unit number where the error occurred turns ON. (Bits 00 to 15 correspond to unit numbers 0 to F.)

z Recovery Processing Flow CPU Bus Unit error occurs. Check the location where the error occurred.

Use the I/O table verification procedure (refer to 6-1-5 I/O Table Verification) to check where the error occurred.

Is the error cleared?

6-1 CPU Unit Errors

Turn the power OFF and back ON.

Restart the PLC

No

Yes

Check the Unit connections

6

Replace the Unit where the error occurred.

6-1-7 Handling Errors

Restart the PLC.

Restart the System.

z Error Causes and Remedies Suspected cause of error

Confirmation method

An error specific to the Unit

Refer to the manual for the particular Unit.

Same as at the left.

Same as at the left.

Faulty connection at Unit (at a connector)

Check the insertion at the connector. Restart the Unit and check whether the error is cleared.

Tighten the screws.

Check for vibration and shock.

Unit failure

If restarting the Unit does not clear the error, check whether the error is cleared by replacing the Unit.

Replace the applicable Unit.

Same as at the left.

Noise

Restart the CPU Unit and check whether the error occurs again.

Take measures against noise. (Investigate the path of entry.)

Same as at the left.

• Data corruption in bus signals

Remedy

Prevention of recurrence

• FG • Power lines

CJ2 CPU Unit Hardware User’s Manual

6-21

Page 218

6 Troubleshooting

Special I/O Unit Error (Non-fatal Error) A Special I/O Unit error occurs when there is an error in the data conversion between the CPU Unit and a Special I/O Unit. POWER Lit.

RUN

ERR/ALM

Lit.

Flashing.

Error flag A402.06

Error code

Error information

0300 to 035F or 03FF

A418 to A423 *

* The bit corresponding to the unit number where the error occurred turns ON.

z Recovery Processing Flow Special I/O Unit error occurs. Restart the Special I/O Unit.

Reset, or turn the power OFF and back ON.

Is the error cleared? No Yes

Check the Unit connections.

Replace the Special I/O Unit.

Restart the Special I/O Unit.

Restart the System.

z Error Causes and Remedies Suspected cause of error

Confirmation method

An error specific to the Unit

Refer to the manual for the particular Unit.

Same as at the left.

Same as at the left.

Faulty connection at Unit (at a connector)

Check the insertion at the connector. Restart the Unit and check whether the error is cleared.

Tighten the screws.

Check for vibration and shock.

Unit failure

If restarting the Unit does not clear the error, check whether the error is cleared by replacing the Unit.

Replace the applicable Unit.

Same as at the left.

Noise

Restart the CPU Unit and check whether the error occurs again after this.

Take measures against noise. (Investigate the path of entry.)

Same as at the left.

• Data corruption in bus signals

Prevention of recurrence

Remedy

• FG • Power lines

6-22

CJ2 CPU Unit Hardware User’s Manual

Page 219

6 Troubleshooting

Special I/O Unit Setting Error (Non-fatal Error) A Special I/O Unit setting error will occur if a Unit registered in the registered I/O tables does not agree with the Unit actually connected in the PLC. A Special I/O Unit setting error will also occur if a Unit set as a Synchronous Unit in the synchronous operation parameter settings is not actually connected in the PLC or does not support synchronous unit operation. POWER Lit.

RUN Lit.

ERR/ALM

Error flag

Error code

Flashing.

A402.02

0500 to 055F

Error information A428 to A433*

* The bit corresponding to the Unit for which the error occurred will turn ON.

z Recovery Processing Flow Special I/O Unit setting error occurs. 6-1 CPU Unit Errors

Synchronous unit operation being used?

No

Yes Check if error is caused by synchronous unit operation settings. (A428 to A433 will tell you which Unit caused the error.)

6 6-1-7 Handling Errors

Perform the recovery procedure.

Operation recovered?

No

Yes Check if error is caused by registered I/O settings. (A428 to A433 will tell you which Unit caused the error.)

Perform the recovery procedure.

Restart the system.

CJ2 CPU Unit Hardware User’s Manual

6-23

Page 220

6 Troubleshooting z Error Causes and Remedies for Synchronous Unit Operation Settings Suspected cause of error

Confirmation method

Prevention of recurrence

Remedy

A Unit set in the synchronous unit operation settings does not support synchronous unit operation.

Check the operation manual for the Unit.

Transfer the settings again.

Same as at the left.

A Unit set in the synchronous unit operation settings does not exist in the PLC.

Check the Units in the PLC.

Transfer the settings again.

Same as at the left.

A Unit set in the synchronous unit operation settings does not exist on the CPU Rack (i.e., it is on an Expansion Rack).

Check the Units in the PLC.

Move the Synchronous Unit to the CPU Rack.

Same as at the left.

If I/O tables have been registered, change the registered I/O tables.

z Error Causes and Remedies for Registered I/O Table Settings Suspected cause of error The model of a CPU Bus Unit in the registered I/O tables is different from the model the Unit actually mounted in the PLC.

6-24

Confirmation method Check the Units in the PLC.

Prevention of recurrence

Remedy Correct the I/O table settings.

Same as at the left.

CJ2 CPU Unit Hardware User’s Manual

Page 221

6 Troubleshooting

Troubleshooting Built-in EtherNet/IP Port Errors (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only)

6-2-1

Checking Built-in EtherNet/IP Port Error Status Built-in EtherNet/IP port errors can be checked on the built-in EtherNet/IP port seven-segment display on the front of the CJ2H-CPU6@-EIP or CJ2M-CPU3@ CPU Unit.

Built-in EtherNet/IP port seven-segment display

Precautions for Correct Use • For details on the types of errors related to the built-in EtherNet/IP port, and measures for handling them, refer to the CS/CJ Series EtherNet/IP Units Operation Manual (Cat. No. W465).

6-2 Built-in EtherNet/IP Port Errors and Remedies (CJ2H-CPU6@-EIP Only)

6-2

6 6-2-1 Checking Built-in EtherNet/IP Port Error Status

CJ2 CPU Unit Hardware User’s Manual

6-25

Page 222

6 Troubleshooting

6-2-2

Checking Error Status at the EtherNet/IP Port Seven-segment Display

Built-in EtherNet/IP port seven-segment display

The seven-segment display alternately displays the built-in EtherNet/IP port node address and the following error codes.

z Normal Operation Indications MS Lit green

NS Lit or flashing green

Error

7-segment Built-in EtherNet/IP port node address

Normal z Errors Related to CPU Unit Data Exchange Indications MS

NS

Error

7-segment

Flashing red

Not lit

H1

Duplicate unit number

Flashing red

Not lit

H2

CPU Unit faulty

Lit red

Not lit

H3

Built-in EtherNet/IP port faulty

Flashing red

Not lit

H4

Node address setting error

Flashing red

Not lit

H6

CPU Unit faulty

Flashing red

Not lit

H7

I/O table not registered

Flashing red

---

H8

Simple backup function restore error

Flashing red

---

H9

I/O bus error

Flashing red

---

HA

CPU Unit memory error

Flashing red

Not lit

Hb

CPU Unit event servicing timeout

Flashing red

---

HC

Routing table error

Flashing red

---

Hd

I/O refresh error

Flashing red

---

HE

CPU Unit service monitoring error

Flashing red

---

HF

CPU Unit watchdog timer error z Errors Related to the CPU Unit Indications MS

NS

Error

7-segment

Flashing red

---

HH

CPU Unit Fatal Error

---

---

---

Output OFF Error z Errors Related to the Control Bits Indications MS ---

6-26

NS ---

Error

7-segment C6

Multiple Switches ON

CJ2 CPU Unit Hardware User’s Manual

Page 223

6 Troubleshooting z Errors Related to the Tag Data Links MS

NS

6-2 Built-in EtherNet/IP Port Errors and Remedies (CJ2H-CPU6@-EIP Only)

Indications

Error

7-segment

---

--- d5

Verification Error (target non-existent)

---

--- d6

Connection Failed

---

--- d9

Tag Data Link Error z Errors Related to Memory Access Indications MS

NS

Error

7-segment

Flashing red

---

E9

Memory Access Error

Flashing red

---

E8

Device Parameters Error

Flashing red

---

EA

IP Advanced Settings Error

Flashing red

---

F2

Ethernet Basic Settings Error z Errors Related to the Network Indications MS

NS

Error

7-segment

---

---

E1

Ethernet Link Not Detected

---

---

E3

Server Connection Error

---

Lit red

F0

IP Address Duplication

Flashing red

---

F3

Address mismatch

Flashing red

Not lit

F4

Communications Controller Error

Flashing red

---

C8

Node Address Setting Changed During Operation

6 6-2-2 Checking Error Status at the EtherNet/IP Port Seven-segment Display z Errors Related to Units Indicator MS Lit red

NS Not lit

CJ2 CPU Unit Hardware User’s Manual

Error

7-segment ---

CPU Bus Unit Error

6-27