6 Troubleshooting
6-3
Non-CPU Unit Errors and Remedies
6-3-1
Error Causes and Remedies
Input Units No. 1
Symptom Not all inputs turn ON or indicators are not lit.
Cause
Remedy
Power is not supplied to Input Unit.
Supply the appropriate external input power.
Supply voltage is low.
Adjust supply voltage to within rated range.
Terminal block mounting screws are loose.
Tighten screws.
Faulty contact of terminal block connector.
Replace terminal block connector.
2
Not all inputs turn ON (indicator lit).
Input circuit is faulty.
Replace Unit.
3
Not all inputs turn OFF.
Input circuit is faulty.
Replace Unit.
4
Specific bit does not turn ON.
Input device is faulty.
Replace input devices.
Input wiring disconnected.
Check input wiring
Terminal block screws are loose.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
Too short ON time of external input.
Adjust input device.
Faulty input circuit
Replace Unit.
Input bit number is used for output instruction.
Correct program.
Input circuit is faulty.
Replace Unit.
Input bit number is used for output instruction.
Correct program.
External input voltage is low or unstable.
Adjust external input voltage to within rated range.
Malfunction due to noise.
Take protective measures against noise, such as:
5
6
Specific bit does not turn OFF.
Input irregularly turns ON/OFF.
• Install surge suppressor. • Install insulation transformer. • Install shielded cables between the Input Unit and the loads.
6-28
Terminal block screws are loose.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
CJ2 CPU Unit Hardware User’s Manual
Page 225
6 Troubleshooting
No. 7
Symptom Error occurs in units of 8 points or 16 points, i.e., for the same common.
8
Input indicator is not lit in normal operation.
Cause
Remedy
Common terminal screws are loose.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
Faulty data bus
Replace Unit.
Faulty CPU
Replace CPU.
Faulty indicator or indicator circuit.
Replace Unit.
No. 1
Symptom Not all outputs turn ON.
Cause
Remedy
Load is not supplied with power.
Supply power.
Load voltage is low.
Adjust voltage to within rated range.
Terminal block screws are loose.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
An overcurrent (possibly caused by a short at the load) resulted in a blown fuse in the Output Unit. (Some Output Units provide an indicator for blown fuses.)
Replace fuse.
6
Faulty I/O bus connector contact. Replace Unit. Replace Unit.
If the INH indicator is lit, the Output OFF Bit (A500.15) is ON.
Turn A500.15 OFF. Replace Unit.
2
Not all outputs turn OFF.
Output circuit is faulty.
3
Output of a specific bit number does not turn ON or indicator is not lit.
Output ON time too short Correct program to increase the because of a mistake in program- time that the output is ON. ming.
4
5
6
Output of a specific bit number does not turn ON (indicator lit).
Bit status controlled by multiple instructions.
Correct program so that each output bit is controlled by only one instruction.
Faulty output circuit.
Replace Unit.
Faulty output device.
Replace output device.
Break in output wiring.
Check output wiring.
Loose terminal block screws.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
Faulty output bit on a Relay Output Unit.
Replace relay.
Faulty output circuit.
Replace Unit.
Output of a specific bit number does not turn OFF (indicator is not lit).
Faulty output bit (Relay Output Units only)
Replace relay.
Bit does not turn OFF due to leakage current or residual voltage.
Replace external load or add dummy resistor.
Output of a specific bit number does not turn OFF (indicator lit).
Bit status controlled by multiple instructions.
Correct program.
Faulty output circuit.
Replace Unit.
CJ2 CPU Unit Hardware User’s Manual
6-29
6-3-1 Error Causes and Remedies
Output circuit is faulty.
6-3 Non-CPU Unit Errors and Remedies
Output Units
Page 226
6 Troubleshooting
No. 7
Symptom Output irregularly turns ON/OFF.
Cause
Remedy
Low or unstable load voltage.
Adjust load voltage to within rated range.
Bit status controlled by multiple instructions.
Correct program so that each output bit is controlled by only one instruction.
Malfunction due to noise.
Protective measures against noise: • Install surge suppressor. • Install insulation transformer. • Use shielded cables between the Output Unit and the loads.
8
Error occurs in units of 8 points or 16 points, i.e., for the same common.
Terminal block screws are loose.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
Loose common terminal screw.
Tighten screws.
Faulty terminal block connector contact.
Replace terminal block connector.
An overcurrent (possibly caused by a short at the load) resulted in a blown fuse in the Output Unit.
Replace fuse.
Faulty data bus.
Replace Unit.
Faulty CPU.
Replace CPU.
9
Output indicator is not lit (operation is normal).
Faulty indicator.
Replace Unit.
10
ERR indicator (load short-circuit alarm) lights and outputs turn OFF.
An external short-circuit or disconnection occurred.
Refer to A-6-1 Load Short-circuit Protection and Line Disconnection Detection for CJ1W-OD202.
z Special I/O Units Refer to the Operation Manual for the Special I/O Unit to troubleshoot any other errors. No. 1
6-30
Symptom
Cause
Remedy
The ERH and RUN indicators on the Special I/O Unit are lit.
Special I/O refreshing is not being performed for the Unit from the CPU Unit (CPU Unit monitoring error).
Change the bit corresponding to the unit number to 0 to enable cyclic refreshing, or make sure that the Unit is refreshed from the program using IORF or FIORF at least once every 11 s.
CJ2 CPU Unit Hardware User’s Manual
Page 227
6 Troubleshooting
CX-Programmer Connections Use the following procedure if the CX-Programmer cannot be connected.
z Connecting via the Peripheral (USB) Port The CX-Programmer cannot connect.
No
Yes
Is the CX-Programmer network type set to USB?
Insert the cable all the way in at both the personal computer and at the CPU Unit.
No
No
Can the CX-Programmer be connected online?
Yes
6-3 Non-CPU Unit Errors and Remedies
Is the USB cable securely connected?
End
Set the CX-Programmer network type to USB.
Yes No
Can the CX-Programmer be connected online?
Yes
6
Replace the USB cable.
6-3-1 Error Causes and Remedies
CJ2 CPU Unit Hardware User’s Manual
6-31
Page 228
6 Troubleshooting z Connection to the EtherNet/IP Port (CJ2H-CPU6@-EIP and CJ2M-CPU3@ Only) The CX-Programmer cannot connect.
Is the Ethernet cable securely connected?
At the personal computer (or the Ethernet switch) and the CPU Unit, firmly insert the cable until the connector locks. Confirm that the LINK indicator lights at the personal computer (or Ethernet switch) and that the 100M (10M) indicator lights at the CPU Unit.
No
Use the ping command from the personal computer to confirm that the communications to the PLC have been established. For details, refer to the EtherNet/IP Unit Operation Manual (Cat. No. W465).
Yes
No
Is an Ethernet switch used between the personal computer and the PLC?
No
Can the CX-Programmer be connected online?
Yes
End
If a personal computer is connected to a PLC using Straight Cable (or Cross Cable), it can occasionally be difficult to make the connection. If this occurs, try using an Ethernet switch between the computer and PLC.
Yes
Use the ping command from the personal computer to confirm that the communications to the PLC is established. For details, refer to the EtherNet/IP Unit Operation Manual (Cat. No. W465).
No
Are unique IP addresses used for the personal computer and the CPU Unit, and are they set for the same domain?
Yes
Can the CX-Programmer be connected online?
Yes
Set the IP address for the personal computer. Either use the default IP address for the CPU Unit or else connect the CX-Programmer and set another IP address.
No Use the ping command from the personal computer to confirm that the communications to the PLC has been established. For details, refer to the EtherNet/IP Unit Operation Manual (Cat. No. W465).
No
Is the CX-Programmer network type set to EtherNet/IP?
Yes
Can the CX-Programmer be connected online?
Yes
Set the CX-Programmer network type to EtherNet/IP.
No No
Can the CX-Programmer be connected online?
Yes
Replace the Ethernet cable and the Ethernet switch.
6-32
CJ2 CPU Unit Hardware User’s Manual
Page 229
6 Troubleshooting z Connecting via the Serial Port The CX-Programmer cannot connect.
Is the RS-232C cable securely connected?
Insert the cable all the way in at both the personal computer and at the CPU Unit.
No
Yes No
No
Yes End 6-3 Non-CPU Unit Errors and Remedies
Is pin 5 of the CPU Unit DIP switch turned ON?
Can the CX-Programmer be connected online?
Set the CX-Programmer network type to Toolbus.
Yes Can the CX-Programmer be connected online?
Yes
No
In the PLC Setup in the CPU Unit, does the serial port setting match the CX-Programmer network type setting?
No
Replace the RS-232C cable.
In the PLC Setup in the CPU Unit, match the serial port setting with the CX-Programmer network type setting.
6 6-3-1 Error Causes and Remedies
Yes
CJ2 CPU Unit Hardware User’s Manual
6-33
Page 230
6 Troubleshooting
6-34
CJ2 CPU Unit Hardware User’s Manual