Page 239

7 Inspection and Maintenance

• The value for the Output OFF Bit (A500.15) will become unstable. Moreover, when the Output OFF Bit turns ON, the outputs of all Output Units will turn OFF. To prevent the outputs of all Output Units from turning OFF at startup, take countermeasures such as writing the following program section into the ladder program. First Cycle Flag (A200.11)

RSET A500.15

• Bank 0 will be the EM current bank at startup. • Files will not be held in the EM file memory (EM data converted to flash memory) and the file memory function cannot be used. Make the EM file memory setting again in the PLC Setup, and format the EM file memory.

Setup Method The following flowchart shows the flow of setup operations for the CPU Unit. Power ON

Is it necessary to hold the values of I/O memory data for the next startup?

Yes

Which data is required?

No

CIO/W/TIM CNT/H/DM/EM

7-2 Replacing the Battery

Operation with Battery Normal Operation (Memory Card Not Required) PLC Setup: Detect Low Battery IOM Hold Bit: Hold A500.12 (IOM Hold Bit): ON

CNT/HR/DM/EM

Normal Operation (Memory Card Not Required) PLC Setup: Detect Low Battery

7 Operation without Battery 7-2-2 Operation When Battery Is Exhausted or Not Installed

Are I/O memory initial values required for program execution?

Normal Operation (Memory Card Not Required, and User Program and Parameter Area Data Held in Flash Memory) PLC Setup: Do Not Detect Low Battery

No

Yes

Yes Can the I/O memory initial values be set by the program?

The initial values are set in the user program.

No

Are the DM Area settings (D20000 to D32767) for Special I/O Units and Inner Boards the only initial values that are required?

No

Automatic Transfer at Startup (Memory Card Required) Transferred files: AUTOEXEC.OBJ, AUTOEXEC.STD, AUTOEXEC.IOM PLC Setup: Do Not Detect Low Battery

Yes

DM Area beginning with D00000, or EM Area

Other than the above.

CJ2 CPU Unit Hardware User’s Manual

Automatic Transfer at Startup (Memory Card Required) Transferred files: AUTOEXEC.OBJ, AUTOEXEC.STD, ATEXECDM.IOM, etc. PLC Setup: Do Not Detect Low Battery

Operation is not possible without a Battery.

7-9

Page 240

7 Inspection and Maintenance

7-3

Power Supply Unit Replacement Time Principle of Replacement Notification The Power Supply Unit has a built-in electrolytic capacitor. The electrolytic capacitor is impregnated with electrolytic solution that starts to penetrate the sealing rubber from the time of manufacture. As time elapses, the internal electrolytic solution continues to evaporate, resulting in decreased electrostatic capacity and deterioration in other characteristics. Over time, the characteristic deterioration of the electrolytic capacitor prevents the Power Supply Unit from being utilized to its full capacity. In particular, the speed at which the electrolytic capacitor deteriorates fluctuates greatly with the ambient temperature (generally, a temperature rise of 10°C will double the rate of a reaction, as stated by Arrhenius' law). The CJ1W-PA205C Power Supply Unit with Replacement Notification monitors the internal temperature of the Power Supply Unit while the power is turned ON, and calculates the level of deterioration of the electrolytic capacitor from the operating time and internal temperature. The replacement notification function displays the approximate time until the Power Supply Unit will stop functioning at its full capacity due to the characteristic deterioration of the electrolytic capacitor, based on the calculated level of deterioration. When 6 months are remaining until replacement is required, the alarm output will turn OFF. Note The replacement notification function provides an indication of when the deterioration of the electrolytic capacitor will prevent the power supply functioning at its full capacity. It does not provide information on failures occurring due to other causes.

Power Supply Unit with Replacement Notification Model

Specifications

CJ1W-PA205C

100 to 240 VAC, Output capacity: 5 A at 5 VDC, 0.8 A at 24 VDC, total of 30 W With replacement notification

Power Supply Unit Replacement Notification Module z CJ1W-PA205C Replacement notification display (7-segment, red) CJ1W-PA205C POWER

POWER indicator (green)

TEST ALARM OUTPUT DC30V, 50mA NORMAL:ON ALARM OFF

7-10

L

Alarm output (replacement notification output) test switch Alarm output (replacement notification output) wiring diagram

CJ2 CPU Unit Hardware User’s Manual

Page 241

7 Inspection and Maintenance

Function z Replacement Notification Function Displays The replacement notification of the Power Supply Unit is shown using three 7-segment display characters. • At time of purchase “FUL” is displayed. The display changes to “HLF” as the electrolytic capacitor deteriorates (“HLF” may not be displayed, depending on the operating environment). • When the time until replacement is required drops below 2 years, the display will change corresponding to the operating time from “1.5” to “1.0” to “0.5” to “0.0”/”A02.” When the remaining service life reaches 6 months or less, the display will alternate between “0.0” and “A02” in 2-second intervals. Capacity at time of manufacture

Electrolytic capacitor level

Replacement notification display (7-Segment)

Alarm output (replacement notification output)

2.0 yr

1.5 yr

1.0 yr

Output ON

0.5 yr Output OFF

0 yr Remaining life span

The output turns OFF when the remaining life span reaches 6 months, and the following display is repeatedly alternated.

Note 1 The time remaining until replacement does not include periods when the power is turned OFF.

7-3 Power Supply Unit Replacement Time

Replacement required

2 Until approximately one month of operating time has accumulated, the display will always be “ful” and the alarm output will remain ON (conducting) due to the estimated deterioration speed. 3 The time remaining until replacement will vary the operating and storage conditions, so periodically check the display. 4 Fluctuation in the time remaining until replacement may result in the alarm output repeatedly turning ON and OFF. 5 The precision of the replacement notification function will be adversely affected by applications in which the power is frequently turned ON and OFF. 6 Due to the service life of the electronic components, replace the Power Supply Unit approximately 15 years after purchase, even if the replacement notification display or output has not indicated that replacement is required.

z Alarm Output (Replacement Notification Output) The output remains ON until the remaining service life drops below 6 months and then turns OFF. Note The alarm output will also turn OFF under the following conditions.

• The AC input to the Power Supply Unit is turned OFF. • An error is detected by the self-diagnostic function. • The TEST switch is pressed for at least 3 seconds.

CJ2 CPU Unit Hardware User’s Manual

7-11

7

Page 242

7 Inspection and Maintenance

Additional Information Example of Using the Alarm Output: Monitoring Power Supply Replacement Notification in the System (6 Months or Less Until Replacement Is Required) ON Alarm output OFF Turns OFF when 6 months remains Alarm output

TIM 000 5 s Internal Flag

T000

The Flag is programmed to allow for the delay in the alarm output at system startup. The Flag does not turn ON when the alarm output is ON (normal operation). When the alarm output turns OFF (replacement required), the Flag turns ON, and the replacement notification can be monitored from the system.

z Maintenance Function Using the TEST Switch • Press the TEST switch for at least 3 seconds to display “A02” and force the alarm output OFF. Release the switch to return to normal operating status. The TEST switch is used initially or periodically to check the connection status between the alarm output and external devices. • Press the TEST switch for less than 3 seconds to display the unit version information for the Power Supply Unit. Precautions for Correct Use • Replace the Power Supply Unit within 6 months when the display on the front panel of the Power Supply Unit alternates between 0.0 and A02 or the alarm output automatically turns OFF. • Maintain an ambient storage temperature of −20 to 30°C and humidity of 25% to 70% when storing the product (with the power turned OFF) for longer than 3 months to keep the replacement notification function in optimum working condition. The replacement time is calculated from when the power is turned ON only. The precision of the replacement period will decline if the electrolytic capacitor deteriorates during storage.

Display and Alarm Output Operation z Normal Display: Replacement Notification Display When 6 months or less are remaining until replacement is required, the display will alternate between “0.0” and “A02” (in 2 second intervals), and the alarm output will turn OFF. Remaining service life: 1 year to 6 months

Remaining service life: 6 months max. 2s

Alarm output

7-12

ON

2s

2s

2s

2s

OFF

CJ2 CPU Unit Hardware User’s Manual

Page 243

7 Inspection and Maintenance z Operation When Turning ON the Power The following initial display is shown when the power is turned ON, after which the replacement notification is displayed. The alarm output turns ON approximately 0.2 seconds after the power is turned ON. Power ON

Display start

Initial display (approx. 1.1 s)

0.3 s

0.3 s

0.1 s

0.1 s

0.3 s

Replacement required display

Display Alarm output

OFF

ON

1 s max. 0.2 s max.

When replacement is already required, the alarm display will follow the initial display. The alarm output will turn ON approximately 0.2 seconds after the power is turned ON, and then turn OFF after approximately 5 seconds. Initial display (approx. 1.1 s)

Alarm display

Alarm output OFF

Display Alarm output

OFF

ON

OFF

5 s max.

1 s max. 0.2 s max.

z Operation at Power OFF When the power is turned OFF, the display will turn OFF after the PLC operation stops. The alarm output will turn OFF after the display turns OFF. Power PLC operation interruption stopped Replacement notification display

Notification display

7-3 Power Supply Unit Replacement Time

Display start

Power ON

Alarm output OFF

7

Display Alarm output

Approx. 70 ms*1

ON

OFF

100 VAC: Approx. 2 s 200 VAC: Approx. 7 s *1

*1 The values shown are reference values (calculated for a no-load status on the Power Supply Unit's output).

If replacement is already required, the display will turn OFF after the PLC operation stops. When the display turns OFF, the alarm output will turn ON momentarily and then turn OFF again. Power interruption

PLC operation stopped

Notification display OFF + alarm output ON Alarm output OFF

Alarm display Display Alarm output

OFF

ON

OFF

Approx. 70 ms*1

100 VAC: Approx. 2 s 200 VAC: Approx. 7 s *1

*1 The values shown are reference values (calculated for a no-load status on the Power Supply Unit's output).

CJ2 CPU Unit Hardware User’s Manual

7-13

Page 244

7 Inspection and Maintenance z Operation When TEST Switch Is Pressed The following operation will be performed when the TEST switch on the replacement notification function module is pressed. When the switch is pressed for less than 3 seconds, the unit version will be displayed 3 times at 0.5-second intervals. When the switch is pressed for at least 3 seconds, the alarm output will momentarily turn OFF, and the alarm display A02 will be shown. The operation will return to the normal display and output when the switch is released. Use the TEST switch to check the connection between the replacement notification output and devices. • Operation when TEST switch is pressed for less than 3 seconds. TEST switch

ON 0.5 s

0.5 s

0.5 s

0.5 s

Alarm output

0.5 s

0.5 s

ON

• Operation when TEST switch is pressed for less than 3 seconds. 3s TEST switch

ON

0.5 s

0.5 s

0.5 s

0.5 s

0.5 s

0.5 s

ON

Alarm output

OFF

ON

Precautions for Correct Use Under normal application conditions, the replacement notification function will operate after several years or even tens of years. When using a Power Supply Unit for an extended period of time, periodically check operation with the TEST switch as described above and be sure the alarm output functions properly.

z Self-diagnostic Function Error name

Display

Alarm output status

Error details (cause)

Recovery method

Unit overheated error

OFF

Internal overheating has occurred in the Power Supply Unit as a result of usage under conditions that exceed the specified values, insufficient ventilation, or incorrect installation.*1

Remove the cause of the overheating error.

Unit error

OFF

System error from external noise or hardware malfunction.

Turn ON the input's power supply again. If the Unit does not recover, the error may be caused by a Unit malfunction. Consult with your OMRON representative.

*1 If the error continues for 3 hours or longer, the replacement notification function will be disabled. Even if the cause of the overheating is removed, the display will continue as “Hot,” and the notification output will remain OFF. In this state, the internal parts may deteriorate even if the PLC operation is normal, so replace the Power Supply Unit.

7-14

CJ2 CPU Unit Hardware User’s Manual

Page 245

7 Inspection and Maintenance

Comparison between the CJ1W-PA205C and CJ1W-PA205R Item RUN contact output

CJ1W-PA205C Not supported

Terminal block arrangement

CJ1W-PA205R (for comparison) Supported

CJ1W-PA205R

CJ1W-PA205C 100 to 240 VAC INPUT

L1

L1

AC input

100 to 240 VAC INPUT

AC input

L2/N

L2/N

LG

LG

GR

GR NC

Unconnected terminals

NC

Located on the left side of the Unit.

RUN output (RUN contact)

Located on the right side of the Unit. PA205R

CJ1W-PA205C

POWER

POWER

AC100-240V INPUT

Years

L1 L1

TEST

L2/N

ALARM OUTPUT DC30V,50mA NORMAL:ON ALARM :OFF

L

AC100-240V INPUT L2/N

+

NC RUN OUTPUT AC240V DC24V

NC

Terminal block

Terminal block Alarm output terminals

POWER indicator

On replacement notification module

On hood of Power Supply Unit

Replacement notification

Supported (7-segment display + transistor outputs)

Not supported

CJ2 CPU Unit Hardware User’s Manual

7-3 Power Supply Unit Replacement Time

Terminal block position

RUN OUTPUT 240 VAC 24 VDC 2A RESISTIVE

7

7-15

Page 246

7 Inspection and Maintenance

7-16

CJ2 CPU Unit Hardware User’s Manual