Page 263

pp Appendices The appendices provide Unit specifications, Unit dimensions, details on fatal and nonfatal errors, information on connecting to serial ports on the CPU Unit, the procedure for installing the USB driver on a personal computer, and information on load short-circuit protection and line disconnection detection.

A-1 Specifications of Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 A-1-1 A-1-2 A-1-3 A-1-4

Overview of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5 Precautions on Contact Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-57 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-59

A-2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-94 CJ2H CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-94 CJ2M CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-95 Power Supply Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-96 Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-98 I/O Control Unit and I/O Interface Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-101 I/O Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-101 Pulse I/O Modules (CJ2M CPU Unit Only) . . . . . . . . . . . . . . . . . . . . . . . . . A-101 Serial Option Boards (CJ2M-CPU3@ Only) . . . . . . . . . . . . . . . . . . . . . . . . . A-102

A-3 Fatal and Non-fatal Error Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-103 A-3-1 A-3-2

Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-103 Non-fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-108

A-4 Connecting to a Serial Port on the CPU Unit . . . . . . . . . . . . . . . . . . . . . . A-111 A-4-1 A-4-2 A-4-3

Serial Port Interface Types and Specifications . . . . . . . . . . . . . . . . . . . . . . A-111 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-117 Applicable Connectors and Recommended Cables . . . . . . . . . . . . . . . . . . A-132

A-5 Installing the USB Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-139 A-6 Load Short-circuit Protection and Line Disconnection Detection for Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-149 A-6-1 A-6-2

Load Short-circuit Protection and Line Disconnection Detection for CJ1W-OD202 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-149 Load Short-circuit Protection for CJ1W-OD204/OD212/OD232/MD232 . . . A-151

A-7 Relay Output Noise Reduction Methods . . . . . . . . . . . . . . . . . . . . . . . . . A-153 A-8 Functions Supported for Unit Versions . . . . . . . . . . . . . . . . . . . . . . . . . . A-155

CJ2 CPU Unit Hardware User’s Manual

A-1

App

A-2-1 A-2-2 A-2-3 A-2-4 A-2-5 A-2-6 A-2-7 A-2-8

Page 264

Appendices

A-1

Specifications of Basic I/O Units

A-1-1

Overview of Units

Basic I/O Units z Basic Input Units Type of Unit Basic Input Units

Name DC Input Units

Specifications

Model

Terminal block, 12 to 24 VDC

8 inputs

CJ1W-ID201

Terminal block, 24 VDC,

16 inputs

CJ1W-ID211

Fujitsu-compatible connector, 24 VDC 32 inputs MIL connector, 24 VDC

32 inputs

Page *1

A-5 A-6

CJ1W-ID212

A-7

CJ1W-ID231

A-8

CJ1W-ID232

A-9

CJ1W-ID233

A-10

Fujitsu-compatible connector, 24 VDC 64 inputs

CJ1W-ID261

A-12

MIL connector, 24 VDC

64 inputs

CJ1W-ID262

A-13

AC Input Units

Terminal block, 200 to 240 VAC

8 inputs

CJ1W-IA201*1

A-15

Terminal block, 100 to 120 VAC

16 inputs

CJ1W-IA111

A-16

Interrupt Input Unit

Terminal block, 24 VDC

16 inputs

CJ1W-INT01

A-17

Quick-response Input Unit

Terminal block, 24 VDC

16 inputs

CJ1W-IDP01

A-18

*1 Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

A-2

CJ2 CPU Unit Hardware User’s Manual

Page 265

Appendices z Basic Output Units Type of Unit

Name

Basic Output Units

Relay Output Units

Triac Output Unit Transistor Output Units

Sinking outputs

Sourcing outputs

Specifications

Model

Page A-20

Terminal block, 250 VAC/24 VDC, 2 A, 8 independent contacts

8 outputs

CJ1W-OC201

Terminal block, 250 VAC/24 VDC, 2 A

16 outputs

CJ1W-OC211

A-21

Terminal block, 250 VAC/24 VDC, 0.6 A

8 outputs

CJ1W-OA201*1

A-22

Terminal block, 12 to 24 VDC, 2 A

8 outputs

CJ1W-OD201*1

A-23

Terminal block, 12 to 24 VDC, 0.5 A

8 outputs

CJ1W-OD203*1

A-24

Terminal block, 12 to 24 VDC, 0.5 A

16 outputs

CJ1W-OD211

A-25

Terminal block, 24 VDC, 0.5 A

16 outputs

CJ1W-OD213

A-26

Fujitsu-compatible connector, 12 to 24 VDC, 0.5 A

32 outputs

CJ1W-OD231

A-27

MIL connector, 12 to 24 VDC, 0.5 A

32 outputs

CJ1W-OD233

A-29

MIL connector, 24 VDC, 0.5 A

32 outputs

CJ1W-OD234

A-31

Fujitsu-compatible connector, 12 to 24 VDC, 0.3 A

64 outputs

CJ1W-OD261

A-33

MIL connector, 12 to 24 VDC, 0.3 A

64 outputs

CJ1W-OD263

Terminal block, 24 VDC, 2 A, load short-circuit protection, line disconnection detection

8 outputs

*1

A-35 A-37

Terminal block, 24 VDC, 0.5 A, load short-cir- 8 outputs cuit protection

CJ1W-OD204*1

A-39

Terminal block, 24 VDC, 0.5 A, load short-cir- 16 outputs cuit protection

CJ1W-OD212

A-40

MIL connector, 24 VDC, 0.5 A, load short-circuit protection

32 outputs

CJ1W-OD232

A-41

MIL connector, 12 to 24 VDC, 0.3 A

64 outputs

CJ1W-OD262

A-43

CJ1W-OD202

*1 Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

A-1 Specifications of Basic I/O Units

*1

App A-1-1 Overview of Units

CJ2 CPU Unit Hardware User’s Manual

A-3

Page 266

Appendices z Basic Mixed I/O Units Type of Unit Mixed I/O Units

Name 24-VDC Inputs/Transistor Output Units

Specifications Sinking output

Fujitsu-compatible connector

16 inputs

Inputs: 24 VDC

16 outputs

Model

Page

CJ1W-MD231

A-45

CJ1W-MD233

A-47

CJ1W-MD261

A-49

CJ1W-MD263

A-51

CJ1W-MD232

A-53

CJ1W-MD563

A-55

Outputs: 12 to 24 VDC, 0.5 A MIL connector Inputs: 24 VDC Outputs: 12 to 24 VDC, 0.5 A Fujitsu-compatible connector

32 inputs

Inputs: 24 VDC

32 outputs

Outputs: 12 to 24 VDC, 0.3 A MIL connector Inputs: 24 VDC Outputs: 12 to 24 VDC, 0.3 A Sourcing output

MIL connector

16 inputs

Input: 24 VDC

16 outputs

Outputs: 24 VDC, 0.5 A, load short-circuit protection TTL I/O Units

Inputs: 5 VDC

32 inputs

Outputs: 5 VDC, 35 mA

32 outputs

Precautions on Contact Output Units

A-57

Load short-circuit protection and line disconnection detection for CJ1W-OD202

A-149

Load short-circuit protection for CJ1W-OD204/OD212/OD232/MD232

A-151

Note For details on the connectors included with the Unit, refer to the information provided under Accessories in the tables for Basic I/O Units in the following pages.

Reading Terminal Connection Diagrams • I/O terminals in terminal connection diagrams are shown as viewed from the front panel of the Unit. • Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on all Units. • A0 to A20 and B0 to B20 are printed on the Units.

A-4

CJ2 CPU Unit Hardware User’s Manual

Page 267

Appendices

A-1-2

Basic I/O Units

Basic Input Units with Terminal Blocks z CJ1W-ID201 DC Input Unit (12 to 24-VDC, 8 Points) 8-point DC Input Unit with Terminal Block

Model

CJ1W-ID201

Rated Input Voltage

12 to 24 VDC

Rated Input Voltage Range

10.2 to 26.4 VDC

Input Impedance

2.4 kΩ

Input Current

10 mA typical (at 24 VDC)

ON Voltage/ON Current

8.8 VDC min./3 mA min.

OFF Voltage/OFF Current

3 VDC max./1 mA max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 ms in the PLC Setup.)*1

OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 ms using PLC Setup)*1

Number of Circuits

8 independent circuits

Number of Simultaneously ON Points

100% simultaneously ON

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

80 mA max.

Weight

110 g max. Signal name

2.4 kΩ

Internal circuits

560 Ω

1000 pF

IN0

COM0 Input indicator to

A-1-2 Basic I/O Units

Internal circuits

1000 pF

2.4 kΩ

App

IN7

560 Ω

Circuit Configuration

COM7 Input indicator

*2

Terminal Connections

Signal Connec- Signal name tor pin name C0 A0 IN0 B0 C1 A1 IN1 B1 C2 A2 IN2 B2 C3 A3 IN3 B3 C4 A4 IN4 B4 C5 A5 IN5 B5 C6 A6 IN6 B6 C7 A7 IN7 B7 NC A8 B8 NC

12 to 24 VDC

Polarity of the input power supply can be connected in either direction. CJ2 CPU Unit Hardware User’s Manual

A-1 Specifications of Basic I/O Units

Name

A-5

Page 268

Appendices

*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response time are set to 0 ms due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

z CJ1W-ID211 DC Input Unit (24 VDC, 16 Points) Name

16-point DC Input Unit with Terminal Block

Model

CJ1W-ID211

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

3.3 kΩ

Input Current

7 mA typical (at 24 VDC)

ON Voltage/ON Current

14.4 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 ms in the PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 ms using PLC Setup)*1

Number of Circuits

16 (16 points/common, 1 circuit)

Number of Simultaneously ON Points

100% simultaneously ON (at 24 VDC) (Refer to the following illustration.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

80 mA max.

Weight

110 g max. Temperature characteristics for simultaneously ON points

470 Ω

3.3 kΩ to

Circuit Configuration

1000 pF

COM Input indicator

COM

Internal circuits

IN0 IN15

16 points at 45°C.

18

No. of simultaneously ON points

Signal name

16

12 points at 55°C.

14

Input voltage: 26.4 VDC

12 10 8 6 4 2 0

0

10

20

30

40

50

60 (°C)

Ambient temperature

Signal name

IN0 IN2 IN4 IN6

Terminal Connections

IN8 IN10 IN12 IN14 COM

*2

Connector pin

A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8

Signal name

IN1 IN3 IN5 IN7 IN9

24 VDC

IN11 IN13 IN15 COM

• Polarity of the input power supply can be connected in either direction.

*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response time are set to 0 ms due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

A-6

CJ2 CPU Unit Hardware User’s Manual

Page 269

Appendices z CJ1W-ID212 DC Input Unit (24 VDC, 16 Points) Name

16-point DC Input Unit with Terminal Block

Model

CJ1W-ID212

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

3.3 kΩ

Input Current

7 mA typical (at 24 VDC)

ON Voltage/ON Current

14.4 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 ms in the PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 ms using PLC Setup)*1

Number of Circuits

16 (16 points/common, 1 circuit)

Number of Simultaneously ON Points

100% simultaneously ON (at 24 VDC) (Refer to the following illustration.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

130 mA max.

Weight

110 g max. Temperature characteristics for simultaneously ON points to

Circuit Configuration

1000 pF

COM Input indicator

COM

Internal circuits

IN0 IN15

16 points at 45°C.

18 16

12 points at 55°C.

14

Input voltage: 26.4 VDC

12 10 8 6 4 2 0

0

10

20

30

40

50

60 (°C)

Ambient temperature

Signal name

IN0 IN2

IN6

Terminal Connections

IN8

IN12 IN14 COM

B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8

IN1 IN3 IN5 IN7 IN9

24 VDC

A-1-2 Basic I/O Units

IN10

A0

Signal name

App

IN4

*2

Connector pin

IN11 IN13 IN15 COM

• Polarity of the input power supply can be connected in either direction.

*1 The ON response time will be 15 µs maximum and OFF response time will be 90 µs maximum even if the response time are set to 0 ms due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

CJ2 CPU Unit Hardware User’s Manual

A-1 Specifications of Basic I/O Units

470 Ω

3.3 kΩ

No. of simultaneously ON points

Signal name

A-7

Page 270

Appendices z CJ1W-ID231 DC Input Unit (24 VDC, 32 Points) 32-point DC Input Unit with Fujitsu Connector

Model

CJ1W-ID231

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA typical (at 24 VDC)

ON Voltage/ON Current

19.0 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

Number of Circuits

32 (16 points/common, 2 circuits)

Number of Simultaneously ON Points

75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

90 mA max.

Weight

70 g max.

Accessories

None Allocated CIO word

Signal name

COM0 COM0

SW

Circuit Configuration Input indicator

32 points at 40°C

35

32 points at 48°C

30 25 20 15

Input voltage: 24 VDC Input voltage: 26.4 VDC 12 points/ common at 55°C 10 points/ common at 55°C

10 5 0 10

20

30

40

50

60 (°C)

560 Ω

Ambient Temperature 1000 pF

Connect or row B

Wd m+1

Number of Simultaneously ON Points vs. Ambient Temperature Characteristic

0

5.6 kΩ IN0 to IN15

Internal circuits

Connect or row A

IN0 to IN15

560 Ω

Wd m

1000 pF

5.6 kΩ

Number of simultaneously ON points

Name

COM1 COM1

A-8

CJ2 CPU Unit Hardware User’s Manual

Page 271

Appendices

Signal Connec- Signal name tor pin name

Allocated CIO word

IN0 IN1 IN2 IN3

Wd m

IN4

24 VDC

IN5 IN6 IN7 COM0 IN8 IN9 IN10 IN11

Terminal Connections

Wd m

IN12 IN13 IN14 IN15 COM0 NC NC

A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20

Allocated CIO word

IN0 IN1 IN2 IN3

Wd m+1

IN4 IN5

24 VDC

IN6 IN7 COM1 IN8 IN9 IN10 IN11

Wd m+1 IN12 IN13 IN14 IN15 COM1 NC NC

• The input power polarity can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM0), and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM1), and set the same polarity for both pins. *1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor.

• Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.

z CJ1W-ID232 DC Input Unit (24 VDC, 32 Points) Model

CJ1W-ID232

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA typical (at 24 VDC)

ON Voltage/ON Current

19.0 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.) *1

Number of Circuits

32 (16 points/common, 2 circuits)

Number of Simultaneously ON Points

75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

90 mA max.

Weight

70 g max.

Accessories

None

CJ2 CPU Unit Hardware User’s Manual

A-1-2 Basic I/O Units

32-point DC Input Unit with MIL Connector

App

Name

A-1 Specifications of Basic I/O Units

• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V).

A-9

Page 272

Appendices

Number of Simultaneously ON Points vs. Ambient Temperature Characteristic

Signal name Number of simultaneously ON points

Allocated CIO word

COM0 COM0

SW

Circuit Configuration Input indicator

Internal circuits

Connect or row A

IN0 to IN15

560 Ω

Wd m

1000 pF

5.6 kΩ

5.6 kΩ

30 25 20

Input voltage: 24 VDC Input voltage: 26.4 VDC 12 points/common at 55°C 10 points/common at 55°C

15 10 5 0 0

10

20

30

40

50

60 (°C)

560 Ω

Ambient Temperature 1000 pF

Connect or row B

Wd m+1

IN0 to IN15

32 points at 40°C 32 points at 48°C

35

COM1 COM1

Signal Connec- Signal name tor pin name

Allocated CIO word

Allocated CIO word

24 VDC NC

NC

1 2 COM1 3 4 IN15 IN7 5 6 IN14 IN6 7 8 IN13 IN5 9 10 IN12 IN4 11 12 IN11 IN3 13 14 IN10 IN2 15 16 IN9 17 18 IN1 IN8 19 20 IN0 NC NC 21 22 COM0 COM0 23 24 IN15 25 26 IN7 IN14 27 28 IN6 IN13 29 30 IN5 IN12 31 32 IN4 IN11 33 34 IN3 IN10 35 36 IN2 IN9 37 38 IN1 IN8 39 40 IN0

COM1

Wd m+1

Terminal Connections Wd m

24 VDC

Wd m+1

Wd m

• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM0), and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM1), and set the same polarity for both pins. *1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.

z CJ1W-ID233 DC Input Unit (24 VDC, 32 Points)

A-10

Name

32-point DC Input Unit with MIL Connector

Model

CJ1W-ID233

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA typical (at 24 VDC)

ON Voltage/ON Current

19.0 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

CJ2 CPU Unit Hardware User’s Manual