Page 263
pp Appendices The appendices provide Unit specifications, Unit dimensions, details on fatal and nonfatal errors, information on connecting to serial ports on the CPU Unit, the procedure for installing the USB driver on a personal computer, and information on load short-circuit protection and line disconnection detection.
A-1 Specifications of Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 A-1-1 A-1-2 A-1-3 A-1-4
Overview of Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5 Precautions on Contact Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-57 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-59
A-2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-94 CJ2H CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-94 CJ2M CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-95 Power Supply Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-96 Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-98 I/O Control Unit and I/O Interface Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-101 I/O Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-101 Pulse I/O Modules (CJ2M CPU Unit Only) . . . . . . . . . . . . . . . . . . . . . . . . . A-101 Serial Option Boards (CJ2M-CPU3@ Only) . . . . . . . . . . . . . . . . . . . . . . . . . A-102
A-3 Fatal and Non-fatal Error Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-103 A-3-1 A-3-2
Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-103 Non-fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-108
A-4 Connecting to a Serial Port on the CPU Unit . . . . . . . . . . . . . . . . . . . . . . A-111 A-4-1 A-4-2 A-4-3
Serial Port Interface Types and Specifications . . . . . . . . . . . . . . . . . . . . . . A-111 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-117 Applicable Connectors and Recommended Cables . . . . . . . . . . . . . . . . . . A-132
A-5 Installing the USB Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-139 A-6 Load Short-circuit Protection and Line Disconnection Detection for Basic I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-149 A-6-1 A-6-2
Load Short-circuit Protection and Line Disconnection Detection for CJ1W-OD202 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-149 Load Short-circuit Protection for CJ1W-OD204/OD212/OD232/MD232 . . . A-151
A-7 Relay Output Noise Reduction Methods . . . . . . . . . . . . . . . . . . . . . . . . . A-153 A-8 Functions Supported for Unit Versions . . . . . . . . . . . . . . . . . . . . . . . . . . A-155
CJ2 CPU Unit Hardware User’s Manual
A-1
App
A-2-1 A-2-2 A-2-3 A-2-4 A-2-5 A-2-6 A-2-7 A-2-8
Page 264
Appendices
A-1
Specifications of Basic I/O Units
A-1-1
Overview of Units
Basic I/O Units z Basic Input Units Type of Unit Basic Input Units
Name DC Input Units
Specifications
Model
Terminal block, 12 to 24 VDC
8 inputs
CJ1W-ID201
Terminal block, 24 VDC,
16 inputs
CJ1W-ID211
Fujitsu-compatible connector, 24 VDC 32 inputs MIL connector, 24 VDC
32 inputs
Page *1
A-5 A-6
CJ1W-ID212
A-7
CJ1W-ID231
A-8
CJ1W-ID232
A-9
CJ1W-ID233
A-10
Fujitsu-compatible connector, 24 VDC 64 inputs
CJ1W-ID261
A-12
MIL connector, 24 VDC
64 inputs
CJ1W-ID262
A-13
AC Input Units
Terminal block, 200 to 240 VAC
8 inputs
CJ1W-IA201*1
A-15
Terminal block, 100 to 120 VAC
16 inputs
CJ1W-IA111
A-16
Interrupt Input Unit
Terminal block, 24 VDC
16 inputs
CJ1W-INT01
A-17
Quick-response Input Unit
Terminal block, 24 VDC
16 inputs
CJ1W-IDP01
A-18
*1 Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
A-2
CJ2 CPU Unit Hardware User’s Manual
Page 265
Appendices z Basic Output Units Type of Unit
Name
Basic Output Units
Relay Output Units
Triac Output Unit Transistor Output Units
Sinking outputs
Sourcing outputs
Specifications
Model
Page A-20
Terminal block, 250 VAC/24 VDC, 2 A, 8 independent contacts
8 outputs
CJ1W-OC201
Terminal block, 250 VAC/24 VDC, 2 A
16 outputs
CJ1W-OC211
A-21
Terminal block, 250 VAC/24 VDC, 0.6 A
8 outputs
CJ1W-OA201*1
A-22
Terminal block, 12 to 24 VDC, 2 A
8 outputs
CJ1W-OD201*1
A-23
Terminal block, 12 to 24 VDC, 0.5 A
8 outputs
CJ1W-OD203*1
A-24
Terminal block, 12 to 24 VDC, 0.5 A
16 outputs
CJ1W-OD211
A-25
Terminal block, 24 VDC, 0.5 A
16 outputs
CJ1W-OD213
A-26
Fujitsu-compatible connector, 12 to 24 VDC, 0.5 A
32 outputs
CJ1W-OD231
A-27
MIL connector, 12 to 24 VDC, 0.5 A
32 outputs
CJ1W-OD233
A-29
MIL connector, 24 VDC, 0.5 A
32 outputs
CJ1W-OD234
A-31
Fujitsu-compatible connector, 12 to 24 VDC, 0.3 A
64 outputs
CJ1W-OD261
A-33
MIL connector, 12 to 24 VDC, 0.3 A
64 outputs
CJ1W-OD263
Terminal block, 24 VDC, 2 A, load short-circuit protection, line disconnection detection
8 outputs
*1
A-35 A-37
Terminal block, 24 VDC, 0.5 A, load short-cir- 8 outputs cuit protection
CJ1W-OD204*1
A-39
Terminal block, 24 VDC, 0.5 A, load short-cir- 16 outputs cuit protection
CJ1W-OD212
A-40
MIL connector, 24 VDC, 0.5 A, load short-circuit protection
32 outputs
CJ1W-OD232
A-41
MIL connector, 12 to 24 VDC, 0.3 A
64 outputs
CJ1W-OD262
A-43
CJ1W-OD202
*1 Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
A-1 Specifications of Basic I/O Units
*1
App A-1-1 Overview of Units
CJ2 CPU Unit Hardware User’s Manual
A-3
Page 266
Appendices z Basic Mixed I/O Units Type of Unit Mixed I/O Units
Name 24-VDC Inputs/Transistor Output Units
Specifications Sinking output
Fujitsu-compatible connector
16 inputs
Inputs: 24 VDC
16 outputs
Model
Page
CJ1W-MD231
A-45
CJ1W-MD233
A-47
CJ1W-MD261
A-49
CJ1W-MD263
A-51
CJ1W-MD232
A-53
CJ1W-MD563
A-55
Outputs: 12 to 24 VDC, 0.5 A MIL connector Inputs: 24 VDC Outputs: 12 to 24 VDC, 0.5 A Fujitsu-compatible connector
32 inputs
Inputs: 24 VDC
32 outputs
Outputs: 12 to 24 VDC, 0.3 A MIL connector Inputs: 24 VDC Outputs: 12 to 24 VDC, 0.3 A Sourcing output
MIL connector
16 inputs
Input: 24 VDC
16 outputs
Outputs: 24 VDC, 0.5 A, load short-circuit protection TTL I/O Units
Inputs: 5 VDC
32 inputs
Outputs: 5 VDC, 35 mA
32 outputs
Precautions on Contact Output Units
A-57
Load short-circuit protection and line disconnection detection for CJ1W-OD202
A-149
Load short-circuit protection for CJ1W-OD204/OD212/OD232/MD232
A-151
Note For details on the connectors included with the Unit, refer to the information provided under Accessories in the tables for Basic I/O Units in the following pages.
Reading Terminal Connection Diagrams • I/O terminals in terminal connection diagrams are shown as viewed from the front panel of the Unit. • Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on all Units. • A0 to A20 and B0 to B20 are printed on the Units.
A-4
CJ2 CPU Unit Hardware User’s Manual
Page 267
Appendices
A-1-2
Basic I/O Units
Basic Input Units with Terminal Blocks z CJ1W-ID201 DC Input Unit (12 to 24-VDC, 8 Points) 8-point DC Input Unit with Terminal Block
Model
CJ1W-ID201
Rated Input Voltage
12 to 24 VDC
Rated Input Voltage Range
10.2 to 26.4 VDC
Input Impedance
2.4 kΩ
Input Current
10 mA typical (at 24 VDC)
ON Voltage/ON Current
8.8 VDC min./3 mA min.
OFF Voltage/OFF Current
3 VDC max./1 mA max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 ms in the PLC Setup.)*1
OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 ms using PLC Setup)*1
Number of Circuits
8 independent circuits
Number of Simultaneously ON Points
100% simultaneously ON
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
80 mA max.
Weight
110 g max. Signal name
2.4 kΩ
Internal circuits
560 Ω
1000 pF
IN0
COM0 Input indicator to
A-1-2 Basic I/O Units
Internal circuits
1000 pF
2.4 kΩ
App
IN7
560 Ω
Circuit Configuration
COM7 Input indicator
*2
Terminal Connections
Signal Connec- Signal name tor pin name C0 A0 IN0 B0 C1 A1 IN1 B1 C2 A2 IN2 B2 C3 A3 IN3 B3 C4 A4 IN4 B4 C5 A5 IN5 B5 C6 A6 IN6 B6 C7 A7 IN7 B7 NC A8 B8 NC
12 to 24 VDC
Polarity of the input power supply can be connected in either direction. CJ2 CPU Unit Hardware User’s Manual
A-1 Specifications of Basic I/O Units
Name
A-5
Page 268
Appendices
*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response time are set to 0 ms due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
z CJ1W-ID211 DC Input Unit (24 VDC, 16 Points) Name
16-point DC Input Unit with Terminal Block
Model
CJ1W-ID211
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
3.3 kΩ
Input Current
7 mA typical (at 24 VDC)
ON Voltage/ON Current
14.4 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 ms in the PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 ms using PLC Setup)*1
Number of Circuits
16 (16 points/common, 1 circuit)
Number of Simultaneously ON Points
100% simultaneously ON (at 24 VDC) (Refer to the following illustration.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
80 mA max.
Weight
110 g max. Temperature characteristics for simultaneously ON points
470 Ω
3.3 kΩ to
Circuit Configuration
1000 pF
COM Input indicator
COM
Internal circuits
IN0 IN15
16 points at 45°C.
18
No. of simultaneously ON points
Signal name
16
12 points at 55°C.
14
Input voltage: 26.4 VDC
12 10 8 6 4 2 0
0
10
20
30
40
50
60 (°C)
Ambient temperature
Signal name
IN0 IN2 IN4 IN6
Terminal Connections
IN8 IN10 IN12 IN14 COM
*2
Connector pin
A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8
Signal name
IN1 IN3 IN5 IN7 IN9
24 VDC
IN11 IN13 IN15 COM
• Polarity of the input power supply can be connected in either direction.
*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response time are set to 0 ms due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
A-6
CJ2 CPU Unit Hardware User’s Manual
Page 269
Appendices z CJ1W-ID212 DC Input Unit (24 VDC, 16 Points) Name
16-point DC Input Unit with Terminal Block
Model
CJ1W-ID212
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
3.3 kΩ
Input Current
7 mA typical (at 24 VDC)
ON Voltage/ON Current
14.4 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 ms in the PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 ms using PLC Setup)*1
Number of Circuits
16 (16 points/common, 1 circuit)
Number of Simultaneously ON Points
100% simultaneously ON (at 24 VDC) (Refer to the following illustration.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
130 mA max.
Weight
110 g max. Temperature characteristics for simultaneously ON points to
Circuit Configuration
1000 pF
COM Input indicator
COM
Internal circuits
IN0 IN15
16 points at 45°C.
18 16
12 points at 55°C.
14
Input voltage: 26.4 VDC
12 10 8 6 4 2 0
0
10
20
30
40
50
60 (°C)
Ambient temperature
Signal name
IN0 IN2
IN6
Terminal Connections
IN8
IN12 IN14 COM
B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8
IN1 IN3 IN5 IN7 IN9
24 VDC
A-1-2 Basic I/O Units
IN10
A0
Signal name
App
IN4
*2
Connector pin
IN11 IN13 IN15 COM
• Polarity of the input power supply can be connected in either direction.
*1 The ON response time will be 15 µs maximum and OFF response time will be 90 µs maximum even if the response time are set to 0 ms due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
CJ2 CPU Unit Hardware User’s Manual
A-1 Specifications of Basic I/O Units
470 Ω
3.3 kΩ
No. of simultaneously ON points
Signal name
A-7
Page 270
Appendices z CJ1W-ID231 DC Input Unit (24 VDC, 32 Points) 32-point DC Input Unit with Fujitsu Connector
Model
CJ1W-ID231
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
5.6 kΩ
Input Current
4.1 mA typical (at 24 VDC)
ON Voltage/ON Current
19.0 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
Number of Circuits
32 (16 points/common, 2 circuits)
Number of Simultaneously ON Points
75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
90 mA max.
Weight
70 g max.
Accessories
None Allocated CIO word
Signal name
COM0 COM0
SW
Circuit Configuration Input indicator
32 points at 40°C
35
32 points at 48°C
30 25 20 15
Input voltage: 24 VDC Input voltage: 26.4 VDC 12 points/ common at 55°C 10 points/ common at 55°C
10 5 0 10
20
30
40
50
60 (°C)
560 Ω
Ambient Temperature 1000 pF
Connect or row B
Wd m+1
Number of Simultaneously ON Points vs. Ambient Temperature Characteristic
0
5.6 kΩ IN0 to IN15
Internal circuits
Connect or row A
IN0 to IN15
560 Ω
Wd m
1000 pF
5.6 kΩ
Number of simultaneously ON points
Name
COM1 COM1
A-8
CJ2 CPU Unit Hardware User’s Manual
Page 271
Appendices
Signal Connec- Signal name tor pin name
Allocated CIO word
IN0 IN1 IN2 IN3
Wd m
IN4
24 VDC
IN5 IN6 IN7 COM0 IN8 IN9 IN10 IN11
Terminal Connections
Wd m
IN12 IN13 IN14 IN15 COM0 NC NC
A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20
Allocated CIO word
IN0 IN1 IN2 IN3
Wd m+1
IN4 IN5
24 VDC
IN6 IN7 COM1 IN8 IN9 IN10 IN11
Wd m+1 IN12 IN13 IN14 IN15 COM1 NC NC
• The input power polarity can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM0), and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM1), and set the same polarity for both pins. *1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor.
• Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
z CJ1W-ID232 DC Input Unit (24 VDC, 32 Points) Model
CJ1W-ID232
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
5.6 kΩ
Input Current
4.1 mA typical (at 24 VDC)
ON Voltage/ON Current
19.0 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.) *1
Number of Circuits
32 (16 points/common, 2 circuits)
Number of Simultaneously ON Points
75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
90 mA max.
Weight
70 g max.
Accessories
None
CJ2 CPU Unit Hardware User’s Manual
A-1-2 Basic I/O Units
32-point DC Input Unit with MIL Connector
App
Name
A-1 Specifications of Basic I/O Units
• Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V).
A-9
Page 272
Appendices
Number of Simultaneously ON Points vs. Ambient Temperature Characteristic
Signal name Number of simultaneously ON points
Allocated CIO word
COM0 COM0
SW
Circuit Configuration Input indicator
Internal circuits
Connect or row A
IN0 to IN15
560 Ω
Wd m
1000 pF
5.6 kΩ
5.6 kΩ
30 25 20
Input voltage: 24 VDC Input voltage: 26.4 VDC 12 points/common at 55°C 10 points/common at 55°C
15 10 5 0 0
10
20
30
40
50
60 (°C)
560 Ω
Ambient Temperature 1000 pF
Connect or row B
Wd m+1
IN0 to IN15
32 points at 40°C 32 points at 48°C
35
COM1 COM1
Signal Connec- Signal name tor pin name
Allocated CIO word
Allocated CIO word
24 VDC NC
NC
1 2 COM1 3 4 IN15 IN7 5 6 IN14 IN6 7 8 IN13 IN5 9 10 IN12 IN4 11 12 IN11 IN3 13 14 IN10 IN2 15 16 IN9 17 18 IN1 IN8 19 20 IN0 NC NC 21 22 COM0 COM0 23 24 IN15 25 26 IN7 IN14 27 28 IN6 IN13 29 30 IN5 IN12 31 32 IN4 IN11 33 34 IN3 IN10 35 36 IN2 IN9 37 38 IN1 IN8 39 40 IN0
COM1
Wd m+1
Terminal Connections Wd m
24 VDC
Wd m+1
Wd m
• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM0), and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM1), and set the same polarity for both pins. *1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
z CJ1W-ID233 DC Input Unit (24 VDC, 32 Points)
A-10
Name
32-point DC Input Unit with MIL Connector
Model
CJ1W-ID233
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
5.6 kΩ
Input Current
4.1 mA typical (at 24 VDC)
ON Voltage/ON Current
19.0 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
CJ2 CPU Unit Hardware User’s Manual