Page 273
Appendices
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.) *1
Number of Circuits
32 (16 points/common, 2 circuits)
Number of Simultaneously ON Points
75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. 200 mA max.
Weight
70 g max.
Accessories
None Allocated CIO word
Signal name
Wd m
IN0 to IN15
Number of Simultaneously ON Points vs. Ambient Temperature Characteristic
COM0 COM0
SW
Circuit Configuration Input indicator 5.6 kΩ
32 points at 40°C 32 points at 48°C
35 30 25 20
Input voltage: 24 VDC Input voltage: 26.4 VDC 12 points/common at 55°C 10 points/common at 55°C
15 10 5 0 0
10
20
30
40
50
60 (°C)
Ambient Temperature 560 Ω
IN0 to IN15
1000 pF
Connect or row B
Wd m+1
Internal circuits
560 Ω
Connect or row A
1000 pF
5.6 kΩ
Number of simultaneously ON points
Internal Current Consumption
Signal Connec- Signal name tor pin name
Allocated CIO word
A-1 Specifications of Basic I/O Units
COM1 COM1
Allocated CIO word
24 VDC NC
NC
Wd m+1
Wd m
24 VDC
App
Terminal Connections
Wd m+1
Wd m
• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM0), and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM1), and set the same polarity for both pins. *1 The ON response time will be 15 µs maximum and OFF response time will be 90 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
CJ2 CPU Unit Hardware User’s Manual
A-11
A-1-2 Basic I/O Units
1 2 COM1 3 4 IN15 IN7 5 6 IN14 IN6 7 8 IN13 IN5 9 10 IN12 IN4 11 12 IN11 IN3 13 14 IN10 IN2 15 16 IN9 17 18 IN1 IN8 19 20 IN0 NC NC 21 22 COM0 COM0 23 24 IN15 25 26 IN7 IN14 27 28 IN6 IN13 29 30 IN5 IN12 31 32 IN4 IN11 33 34 IN3 IN10 35 36 IN2 IN9 37 38 IN1 IN8 39 40 IN0
COM1
Page 274
Appendices z CJ1W-ID261 DC Input Unit (24 VDC, 64 Points)
A-12
Model
CJ1W-ID261
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
5.6 kΩ
Input Current
4.1 mA typical (at 24 VDC)
ON Voltage/ON Current
19.0 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
Number of Circuits
64 (16 points/common, 4 circuits)
Number of Simultaneously ON Points
50% (16 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustrations.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
None
Circuit Configuration
Allocated Signal CIO word name IN0 to Wd m Connect IN15 or row A COM0 COM0 CN1 IN0 Wd to Connect m+1 IN15 or row B COM1 COM1 IN0 Wd to Connect m+2 IN15 or row A COM2 COM2 CN2 IN0 Wd to Connect m+3 IN15 or row B COM3 COM3
5.6 kΩ
SW Input indicator 5.6 kΩ
Indicator switching circuit Internal circuits
Accessories
560 Ω
110 g max.
1000 pF
Weight
560 Ω
90 mA max.
1000 pF
Internal Current Consumption
Number of simultaneously ON points
64-point DC Input Unit with Fujitsu Connector
Internal circuits
Name
Number of Simultaneously ON Points vs. Ambient Temperature Characteristic 64 points at 64 points at 47°C 64 points at 35°C 25°C
70
Input voltage: 20.4 VDC
60 50
12 points/common (total: 45 points) at 55°C 8 points/common at 55°C
Input voltage: 24 VDC Input voltage: 26.4 VDC
40 30 20 10 0 0
10
20
30
40
50
8 points/common (total: 26 points max.) at 55°C 60 (°C)
Ambient Temperature
CJ2 CPU Unit Hardware User’s Manual
Page 275
Appendices
NC COM1 name
B20 A20 B19 A19 B18 A18
Allocated CIO word
Allocated CIO word
IN0 IN1 NC IN2 COM0
B17 A17 IN15
IN15
B16 A16 IN14
IN14
B15 A15 IN13
Wd m+1
IN13
IN12
B13 A13 IN11
IN11
24 VDC
IN8 COM1
IN7 COM2
IN10
B11 A11 B10 A10 B9 A9
IN8 IN9 IN9 IN8 IN10 COM0
B8 A8 IN7
IN7
B7 A7 IN6
IN6
B6 A6 IN5
IN5
B5 A5 IN4
B4 A4 IN3
B3 A3 IN2 IN1 IN0
B2 A2 B1 A1
24 VDC
IN4
IN11 IN12 IN13
Wd m
24 VDC
IN5 IN6
Wd m+2
IN9
Wd m+1
IN4
B12 A12 IN10
Terminal Connections
IN3
Wd m
B14 A14 IN12
Signal name
NC
IN14 IN15
IN3 COM2
IN2 NC
IN1 NC
IN0
• The input power polarity can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM0) of CN1, and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM1) of CN1, and set the same polarity for both pins.
Connec- Signal tor pin name
A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20
Allocated CIO word
IN0 IN1 IN2 IN3 IN4 IN5
24 VDC
Wd m+3
NC
CN2
Wd m+2
Signal name
Connec- Signal tor pin
IN6 IN7 COM3
IN8 IN9 IN10 IN11 IN12
Wd m+3
CN1 Allocated CIO word
IN13 IN14 IN15 COM3 NC NC
• The input power polarity can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM2) of CN2, and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM3) of CN2, and set the same polarity for both pins.
Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
z CJ1W-ID262 DC Input Unit (24 VDC, 64 Points) 64-point DC Input Unit with MIL Connector
Model
CJ1W-ID262
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
5.6 kΩ
Input Current
4.1 mA typical (at 24 VDC)
ON Voltage/ON Current
19.0 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
OFF Response Time
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
Number of Circuits
64 (16 points/common, 4 circuits)
Number of Simultaneously ON Points
50% (8 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustrations.)
Insulation Resistance
20 MΩ between external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
CJ2 CPU Unit Hardware User’s Manual
A-1-2 Basic I/O Units
Internal Current Consumption
App
Name
A-1 Specifications of Basic I/O Units
*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays.
90 mA max.
A-13
Page 276
Appendices
Weight
110 g max.
Accessories
None Number of Simultaneously ON Points vs. Ambient Temperature Characteristic
Internal circuits
CN2
Indicator switching circuit
5.6 kΩ 1000 pF
Circuit Configuration
SW Input indicator
Number of simultaneously ON points
1000 pF
IN0 to IN15 COM0 COM0 IN0 to Wd m+1 IN15 COM1 COM1 IN0 to Wd m+2 IN15 COM2 COM2 IN0 to Wd m+3 IN15 COM3 COM3
560 Ω
5.6 kΩ
Wd m
CN1
Internal circuits
Signal name
560 Ω
Allocated CIO word
64 points at 35°C 64 points at 47°C
64 points at 25°C
70
Input voltage: 20.4 VDC
60 50
30
Input voltage: 26.4 VDC
20
8 points/common (total: 26 points max.) at 55°C
10 0 0
10
20
30
40
50
60 (°C)
Ambient Temperature
CN1 Allocated CIO word
12 points/common (total: 45 points) at 55°C 8 points/common at 55°C
Input voltage: 24 VDC
40
CN2 Allocated CIO word
Signal Connec- Signal name tor pin name
Allocated CIO word
Signal name
Connec- Signal tor pin name
Allocated CIO word
24 VDC
IN6 IN7
COM0 NC IN0 IN1 IN2
Terminal Connections
Wd m+1
IN3 IN4 IN5 IN6 IN7
COM1 NC
IN10
34 33
IN11
32 31
IN12
30 29
IN13
28 27
IN14
26 25
IN15
24 23 22 21 20 19
2
3
4
IN15
5
6
IN7
IN14
7
8
IN6
IN13 IN12 IN11 IN10 IN9
COM0
IN8
NC
NC
IN8
NC
1
COM2
9 10 11 12 13 14 15 16 17 18 19 20
COM3
IN5 IN4 IN3 IN2 IN1 IN0
21 22 NC 23 24
COM2
18 17
IN9
16 15
IN10
IN15
25 26
IN7
14 13
IN11
IN14
27 28
IN6
12 11
IN12
IN13
29 30
IN5
10 9
IN13
8
7
IN14
6
5
IN15
4
3
2
1
COM1
IN12 IN11 IN10
24 VDC
IN9 IN8
NC
Wd m+3
IN5
36 35
NC COM3
24 VDC
31 32 33 34 35 36 37 38 39 40
IN4 IN3 IN2
Wd m+2
IN4
IN9
Wd m+3
Wd m
IN3
38 37
Wd m+2
IN2
IN8
Wd m
IN1
40 39
Wd m+1
IN0
IN1 IN0
24 VDC
• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM0) of CN1, and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM1) of CN1, and set the same polarity for both pins.
• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins.
*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
A-14
CJ2 CPU Unit Hardware User’s Manual
Page 277
Appendices z CJ1W-IA201 AC Input Unit (200 VAC, 8 Points) Name
8-point AC Input Unit with Terminal Block
Model
CJ1W-IA201
Rated Input Voltage
200 to 240 VAC 50/60 Hz
Rated Input Voltage Range
170 to 264 VAC
Input Impedance
21 kΩ (50 Hz), 18 kΩ (60 Hz)
Input Current
9 mA typical (at 200 VAC, 50 Hz), 11 mA typical (at 200 VAC, 60 Hz)
ON Voltage/ON Current
120 VAC min./4 mA min.
OFF Voltage/OFF Current
40 VAC max./2 mA max.
ON Response Time
18.0 ms max. (PLC Setup default setting: 8 ms)*1
OFF Response Time
48.0 ms max. (PLC Setup default setting: 8 ms)*1
Number of Circuits
8 (8 points/common, 1 circuit)
Number of Simultaneously ON Points
100% (8 points/common) simultaneously ON
Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
80 mA max.
Weight
130 g max.
Accessories
None A-1 Specifications of Basic I/O Units
Signal name
Circuit Configuration
IN0 to IN7
1 MΩ
0.15 µF
220 Ω
COM
Internal circuits
Input indicator 820 Ω
*2
Connector pin
NC
A0
Signal name IN0
B0 NC
A1
IN1
B1 NC
A2
NC
A3
NC
A4
IN2
Terminal Connections
App
B2 IN3
B3 IN4
200 to 240 VAC
B4 NC
A5
NC
A6
IN6
B6 NC
A7
IN7
B7 NC
A8
COM
B8
*1 The Input ON and OFF response times for Basic I/O Units can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, or 32 ms in the PLC Setup. When the response times have been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 40 ms maximum due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
CJ2 CPU Unit Hardware User’s Manual
A-15
A-1-2 Basic I/O Units
IN5
B5
Page 278
Appendices z CJ1W-IA111 AC Input Unit (100 VAC, 16 points) Name
16-point AC Input Unit with Terminal Block
Model
CJ1W-IA111
Rated input voltage
100 to 120 VAC 50/60 Hz*2
Rated Input Voltage Range
85 to 132 VAC
Input Impedance
14.5 kΩ (50 Hz), 12 kΩ (60 Hz)
Input Current
7 mA typical (at 100 VAC, 50 Hz), 8 mA typical (at 100 VAC, 60 Hz)
ON Voltage/ON Current
70 VAC min./4 mA min
OFF Voltage/OFF Current
20 VAC max./2 mA max
ON Response Time
18 ms max. (PLC Setup default setting: 8 ms)*1
OFF Response Time
48 ms max. (PLC Setup default setting: 8 ms)*1
Number of Circuits
16 (16 points/common, 1 circuit)
Number of Inputs ON Simultaneously 100% simultaneously ON (16 points/common) Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
90 mA max.
Weight
130 g max.
Accessories
None Signal name Input indicator 470 Ω IN0 to IN15
0.22 µF
Internal circuits
Circuit Layout
1 MΩ
270 Ω
COM
*3
Signal name
IN0 IN2 IN4 IN6
Terminal Connections
Connector pin
A0
IN1 B0
A1
IN3 B1
A2
IN5 B2
A3 A4
IN12
IN9 B4
A5
IN11 B5
A6
IN13 B6
IN14
IN15
A7 COM
100 to 120 VAC
IN7 B3
IN8 IN10
Signal name
B7 A8
COM B8
*1 The Input ON and OFF response times for Basic I/O Units can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, or 32 ms in the PLC Setup. When the response times have been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 40 ms maximum due to internal element delays. *2 Use an input voltage of 90 VAC or higher when connecting 2-wire sensors. *3 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
A-16
CJ2 CPU Unit Hardware User’s Manual
Page 279
Appendices z CJ1W-INT01 Interrupt Input Unit (16 Points) Name
16-point Interrupt Input Unit with Terminal Block
Model
CJ1W-INT01
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
3.3 kΩ
Input Current
7 mA typical (at 24 VDC)
ON Voltage/ON Current
14.4 VDC min./3 mA min.
OFF Voltage/OFF Current 5 VDC max./1 mA max. ON Response Time
0.05 ms max.
OFF Response Time
0.5 ms max.
Number of Circuits
16 (16 points/common, 1 circuit)
Number of Simultaneously ON Points
100% (16 points/common) simultaneously ON (24 VDC)
Insulation Resistance
20 MΩ between external terminals and GR terminal (at 100 VDC)
Dielectric Strength
1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA max. 80 mA max.
Weight
110 g max.
Accessories
None Signal name 3.3 kΩ
IN15
470 Ω
1000 pF to
Internal circuits
IN0
COM Input indicator
COM
Circuit Configuration
16 points at 45°C
18
OFF
16 14
12 points at 55°C
Input voltage: 26.4 VDC
12
0.5 ms min.
ON 0.05 ms min.
10 8 6
2 0
0
10
20
30
40
50
60 (°C)
Ambient Temperature
CJ2 CPU Unit Hardware User’s Manual
A-17
A-1-2 Basic I/O Units
4
*1 With the CJ2JH-CPU6@-EIP CPU Units, the Unit must be mounted as one of the four Units immediately next to the CPU Unit.
App
Number of simultaneously ON points
Temperature characteristics for simultaneously ON points
• Up to two Interrupt Input Units can be mounted to the CPU Rack, but they must be connected as one the five Unit*1 immediately next to the CPU Unit. If an Interrupt Input Unit is connected in any other position, an I/O setting error will occur. • Set the pulse width of signals input to the Interrupt Input Unit so they satisfy the following conditions.
A-1 Specifications of Basic I/O Units
Internal Current Consumption
Page 280
Appendices
*1
Signal name
IN0 IN2 IN4 IN6 IN8
Terminal Connections
IN10 IN12 IN14 COM
Connector pin
A0 B0 A1 B1 A2 B2 A3 B3 A4
Signal name
IN1 IN3 IN5 24 VDC
IN7 IN9
B4 A5
IN11 B5
A6
IN13 B6 IN15
A7 B7 A8
COM B8
• The polarity can be connected in either direction. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
z CJ1W-IDP01 Quick-response Input Unit (16 Points)
A-18
Name
16-point Quick-response Input Unit with Terminal Block
Model
CJ1W-IDP01
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
3.3 kΩ
Input Current
7 mA typical (at 24 VDC)
ON Voltage/ON Current
14.4 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
0.05 ms max.
OFF Response Time
0.5 ms max.
Number of Circuits
16 (16 points/common, 1 circuit)
Number of Simultaneously ON Points
100% (16 points/common) simultaneously ON (24 VDC)
Insulation Resistance
20 MΩ between external terminals and GR terminal (at 100 VDC)
Dielectric Strength
1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
80 mA max.
Weight
110 g max.
Accessories
None
CJ2 CPU Unit Hardware User’s Manual
Page 281
Appendices
Signal name 3.3 kΩ
IN15
470 Ω
1000 pF to
Internal circuits
IN0
COM Input indicator
COM
Number of simultaneously ON points -- 16 points at 45°C Ambient temperature characteristics
Circuit Configuration Number of simultaneously ON points
18 16
12 points at 55°C
14
Input voltage: 26.4 VDC
12 10 8 6 4 2 0
0
10
20
30
40
50
60 (°C)
Ambient Temperature *1
Signal name
Connector pin
Signal name
IN0
A0
IN1
B0
IN2
A1
IN3
B1
IN4
A2
IN5 IN7
B3
IN8
IN9
A4 B4
IN10
A5
IN11
B5
IN12
A6
IN13
B6
IN14
A7
IN15
B7
COM
COM
A8 B8
• The input power supply polarity can be connected in either direction.
• With quick-response inputs, pulse inputs shorter than the CPU Unit's cycle time can be read by the CPU Unit.
App
• The pulse width (ON time) that can be read by the Quick-response Input Unit is 0.05 ms.
A-1 Specifications of Basic I/O Units
A3
Terminal Connections
24 VDC
B2
IN6
• Inputs read by the internal circuits are cleared when inputs are refreshed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
A-1-2 Basic I/O Units
CJ2 CPU Unit Hardware User’s Manual
A-19
Page 282
Appendices
Basic Output Units z CJ1W-OC201 Contact Output Unit (Independent Relays, 8 Points) Name
8-point Contact Output Unit with Terminal Block (Independent Relays)
Model
CJ1W-OC201
Max. Switching Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (16 A/Unit)
Min. Switching Capacity
1 mA 5 VDC
Relays
NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced. Electrical: 150,000 operations (24 VDC, resistive load)/100,000 operations (240 VAC, cosφ = 0.4, inductive load)
Service Life of Relay
Mechanical: 20,000,000 operations Service life will vary depending on the connected load. Refer to page A-57 for information on service life according to the load.
ON Response Time
15 ms max.
OFF Response Time
15 ms max.
Number of Circuits
8 independent contacts
Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
90 mA 5 VDC max. 48 mA 24 VDC max. (6 mA × No. of ON points)
Weight
140 g max. Signal name
Circuit Configuration
Internal circuits
OUT
OUTc
Output indicator
Signal name OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6
Terminal Connections
OUT7 NC
*1
Connector pin
A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8
Signal name OUTC0 OUTC1 OUTC2 OUTC3 OUTC4 OUTC5 OUTC6 OUTC7
L L L L L L L L
NC
2 A 250 VAC, 2 A 24 VDC max.
• The input power supply polarity can be connected in either direction. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
A-20
CJ2 CPU Unit Hardware User’s Manual