Page 273

Appendices

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.) *1

Number of Circuits

32 (16 points/common, 2 circuits)

Number of Simultaneously ON Points

75% (12 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustration.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. 200 mA max.

Weight

70 g max.

Accessories

None Allocated CIO word

Signal name

Wd m

IN0 to IN15

Number of Simultaneously ON Points vs. Ambient Temperature Characteristic

COM0 COM0

SW

Circuit Configuration Input indicator 5.6 kΩ

32 points at 40°C 32 points at 48°C

35 30 25 20

Input voltage: 24 VDC Input voltage: 26.4 VDC 12 points/common at 55°C 10 points/common at 55°C

15 10 5 0 0

10

20

30

40

50

60 (°C)

Ambient Temperature 560 Ω

IN0 to IN15

1000 pF

Connect or row B

Wd m+1

Internal circuits

560 Ω

Connect or row A

1000 pF

5.6 kΩ

Number of simultaneously ON points

Internal Current Consumption

Signal Connec- Signal name tor pin name

Allocated CIO word

A-1 Specifications of Basic I/O Units

COM1 COM1

Allocated CIO word

24 VDC NC

NC

Wd m+1

Wd m

24 VDC

App

Terminal Connections

Wd m+1

Wd m

• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM0), and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM1), and set the same polarity for both pins. *1 The ON response time will be 15 µs maximum and OFF response time will be 90 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.

CJ2 CPU Unit Hardware User’s Manual

A-11

A-1-2 Basic I/O Units

1 2 COM1 3 4 IN15 IN7 5 6 IN14 IN6 7 8 IN13 IN5 9 10 IN12 IN4 11 12 IN11 IN3 13 14 IN10 IN2 15 16 IN9 17 18 IN1 IN8 19 20 IN0 NC NC 21 22 COM0 COM0 23 24 IN15 25 26 IN7 IN14 27 28 IN6 IN13 29 30 IN5 IN12 31 32 IN4 IN11 33 34 IN3 IN10 35 36 IN2 IN9 37 38 IN1 IN8 39 40 IN0

COM1

Page 274

Appendices z CJ1W-ID261 DC Input Unit (24 VDC, 64 Points)

A-12

Model

CJ1W-ID261

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA typical (at 24 VDC)

ON Voltage/ON Current

19.0 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

Number of Circuits

64 (16 points/common, 4 circuits)

Number of Simultaneously ON Points

50% (16 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustrations.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

None

Circuit Configuration

Allocated Signal CIO word name IN0 to Wd m Connect IN15 or row A COM0 COM0 CN1 IN0 Wd to Connect m+1 IN15 or row B COM1 COM1 IN0 Wd to Connect m+2 IN15 or row A COM2 COM2 CN2 IN0 Wd to Connect m+3 IN15 or row B COM3 COM3

5.6 kΩ

SW Input indicator 5.6 kΩ

Indicator switching circuit Internal circuits

Accessories

560 Ω

110 g max.

1000 pF

Weight

560 Ω

90 mA max.

1000 pF

Internal Current Consumption

Number of simultaneously ON points

64-point DC Input Unit with Fujitsu Connector

Internal circuits

Name

Number of Simultaneously ON Points vs. Ambient Temperature Characteristic 64 points at 64 points at 47°C 64 points at 35°C 25°C

70

Input voltage: 20.4 VDC

60 50

12 points/common (total: 45 points) at 55°C 8 points/common at 55°C

Input voltage: 24 VDC Input voltage: 26.4 VDC

40 30 20 10 0 0

10

20

30

40

50

8 points/common (total: 26 points max.) at 55°C 60 (°C)

Ambient Temperature

CJ2 CPU Unit Hardware User’s Manual

Page 275

Appendices

NC COM1 name

B20 A20 B19 A19 B18 A18

Allocated CIO word

Allocated CIO word

IN0 IN1 NC IN2 COM0

B17 A17 IN15

IN15

B16 A16 IN14

IN14

B15 A15 IN13

Wd m+1

IN13

IN12

B13 A13 IN11

IN11

24 VDC

IN8 COM1

IN7 COM2

IN10

B11 A11 B10 A10 B9 A9

IN8 IN9 IN9 IN8 IN10 COM0

B8 A8 IN7

IN7

B7 A7 IN6

IN6

B6 A6 IN5

IN5

B5 A5 IN4

B4 A4 IN3

B3 A3 IN2 IN1 IN0

B2 A2 B1 A1

24 VDC

IN4

IN11 IN12 IN13

Wd m

24 VDC

IN5 IN6

Wd m+2

IN9

Wd m+1

IN4

B12 A12 IN10

Terminal Connections

IN3

Wd m

B14 A14 IN12

Signal name

NC

IN14 IN15

IN3 COM2

IN2 NC

IN1 NC

IN0

• The input power polarity can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM0) of CN1, and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM1) of CN1, and set the same polarity for both pins.

Connec- Signal tor pin name

A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20

Allocated CIO word

IN0 IN1 IN2 IN3 IN4 IN5

24 VDC

Wd m+3

NC

CN2

Wd m+2

Signal name

Connec- Signal tor pin

IN6 IN7 COM3

IN8 IN9 IN10 IN11 IN12

Wd m+3

CN1 Allocated CIO word

IN13 IN14 IN15 COM3 NC NC

• The input power polarity can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM2) of CN2, and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM3) of CN2, and set the same polarity for both pins.

Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.

z CJ1W-ID262 DC Input Unit (24 VDC, 64 Points) 64-point DC Input Unit with MIL Connector

Model

CJ1W-ID262

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA typical (at 24 VDC)

ON Voltage/ON Current

19.0 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

OFF Response Time

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

Number of Circuits

64 (16 points/common, 4 circuits)

Number of Simultaneously ON Points

50% (8 points/common) simultaneously ON (at 24 VDC) (Refer to the following illustrations.)

Insulation Resistance

20 MΩ between external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

CJ2 CPU Unit Hardware User’s Manual

A-1-2 Basic I/O Units

Internal Current Consumption

App

Name

A-1 Specifications of Basic I/O Units

*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays.

90 mA max.

A-13

Page 276

Appendices

Weight

110 g max.

Accessories

None Number of Simultaneously ON Points vs. Ambient Temperature Characteristic

Internal circuits

CN2

Indicator switching circuit

5.6 kΩ 1000 pF

Circuit Configuration

SW Input indicator

Number of simultaneously ON points

1000 pF

IN0 to IN15 COM0 COM0 IN0 to Wd m+1 IN15 COM1 COM1 IN0 to Wd m+2 IN15 COM2 COM2 IN0 to Wd m+3 IN15 COM3 COM3

560 Ω

5.6 kΩ

Wd m

CN1

Internal circuits

Signal name

560 Ω

Allocated CIO word

64 points at 35°C 64 points at 47°C

64 points at 25°C

70

Input voltage: 20.4 VDC

60 50

30

Input voltage: 26.4 VDC

20

8 points/common (total: 26 points max.) at 55°C

10 0 0

10

20

30

40

50

60 (°C)

Ambient Temperature

CN1 Allocated CIO word

12 points/common (total: 45 points) at 55°C 8 points/common at 55°C

Input voltage: 24 VDC

40

CN2 Allocated CIO word

Signal Connec- Signal name tor pin name

Allocated CIO word

Signal name

Connec- Signal tor pin name

Allocated CIO word

24 VDC

IN6 IN7

COM0 NC IN0 IN1 IN2

Terminal Connections

Wd m+1

IN3 IN4 IN5 IN6 IN7

COM1 NC

IN10

34 33

IN11

32 31

IN12

30 29

IN13

28 27

IN14

26 25

IN15

24 23 22 21 20 19

2

3

4

IN15

5

6

IN7

IN14

7

8

IN6

IN13 IN12 IN11 IN10 IN9

COM0

IN8

NC

NC

IN8

NC

1

COM2

9 10 11 12 13 14 15 16 17 18 19 20

COM3

IN5 IN4 IN3 IN2 IN1 IN0

21 22 NC 23 24

COM2

18 17

IN9

16 15

IN10

IN15

25 26

IN7

14 13

IN11

IN14

27 28

IN6

12 11

IN12

IN13

29 30

IN5

10 9

IN13

8

7

IN14

6

5

IN15

4

3

2

1

COM1

IN12 IN11 IN10

24 VDC

IN9 IN8

NC

Wd m+3

IN5

36 35

NC COM3

24 VDC

31 32 33 34 35 36 37 38 39 40

IN4 IN3 IN2

Wd m+2

IN4

IN9

Wd m+3

Wd m

IN3

38 37

Wd m+2

IN2

IN8

Wd m

IN1

40 39

Wd m+1

IN0

IN1 IN0

24 VDC

• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM0) of CN1, and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM1) of CN1, and set the same polarity for both pins.

• The input power polarity can be connected in either direction. • Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins. • Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins.

*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.

A-14

CJ2 CPU Unit Hardware User’s Manual

Page 277

Appendices z CJ1W-IA201 AC Input Unit (200 VAC, 8 Points) Name

8-point AC Input Unit with Terminal Block

Model

CJ1W-IA201

Rated Input Voltage

200 to 240 VAC 50/60 Hz

Rated Input Voltage Range

170 to 264 VAC

Input Impedance

21 kΩ (50 Hz), 18 kΩ (60 Hz)

Input Current

9 mA typical (at 200 VAC, 50 Hz), 11 mA typical (at 200 VAC, 60 Hz)

ON Voltage/ON Current

120 VAC min./4 mA min.

OFF Voltage/OFF Current

40 VAC max./2 mA max.

ON Response Time

18.0 ms max. (PLC Setup default setting: 8 ms)*1

OFF Response Time

48.0 ms max. (PLC Setup default setting: 8 ms)*1

Number of Circuits

8 (8 points/common, 1 circuit)

Number of Simultaneously ON Points

100% (8 points/common) simultaneously ON

Insulation Resistance

20 MΩ between external terminals and the GR terminal (500 VDC)

Dielectric Strength

2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

80 mA max.

Weight

130 g max.

Accessories

None A-1 Specifications of Basic I/O Units

Signal name

Circuit Configuration

IN0 to IN7

1 MΩ

0.15 µF

220 Ω

COM

Internal circuits

Input indicator 820 Ω

*2

Connector pin

NC

A0

Signal name IN0

B0 NC

A1

IN1

B1 NC

A2

NC

A3

NC

A4

IN2

Terminal Connections

App

B2 IN3

B3 IN4

200 to 240 VAC

B4 NC

A5

NC

A6

IN6

B6 NC

A7

IN7

B7 NC

A8

COM

B8

*1 The Input ON and OFF response times for Basic I/O Units can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, or 32 ms in the PLC Setup. When the response times have been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 40 ms maximum due to internal element delays. *2 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

CJ2 CPU Unit Hardware User’s Manual

A-15

A-1-2 Basic I/O Units

IN5

B5

Page 278

Appendices z CJ1W-IA111 AC Input Unit (100 VAC, 16 points) Name

16-point AC Input Unit with Terminal Block

Model

CJ1W-IA111

Rated input voltage

100 to 120 VAC 50/60 Hz*2

Rated Input Voltage Range

85 to 132 VAC

Input Impedance

14.5 kΩ (50 Hz), 12 kΩ (60 Hz)

Input Current

7 mA typical (at 100 VAC, 50 Hz), 8 mA typical (at 100 VAC, 60 Hz)

ON Voltage/ON Current

70 VAC min./4 mA min

OFF Voltage/OFF Current

20 VAC max./2 mA max

ON Response Time

18 ms max. (PLC Setup default setting: 8 ms)*1

OFF Response Time

48 ms max. (PLC Setup default setting: 8 ms)*1

Number of Circuits

16 (16 points/common, 1 circuit)

Number of Inputs ON Simultaneously 100% simultaneously ON (16 points/common) Insulation Resistance

20 MΩ between external terminals and the GR terminal (500 VDC)

Dielectric Strength

2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

90 mA max.

Weight

130 g max.

Accessories

None Signal name Input indicator 470 Ω IN0 to IN15

0.22 µF

Internal circuits

Circuit Layout

1 MΩ

270 Ω

COM

*3

Signal name

IN0 IN2 IN4 IN6

Terminal Connections

Connector pin

A0

IN1 B0

A1

IN3 B1

A2

IN5 B2

A3 A4

IN12

IN9 B4

A5

IN11 B5

A6

IN13 B6

IN14

IN15

A7 COM

100 to 120 VAC

IN7 B3

IN8 IN10

Signal name

B7 A8

COM B8

*1 The Input ON and OFF response times for Basic I/O Units can be set to 0 ms, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, or 32 ms in the PLC Setup. When the response times have been set to 0 ms, the ON response time will be 10 ms maximum and the OFF response time will be 40 ms maximum due to internal element delays. *2 Use an input voltage of 90 VAC or higher when connecting 2-wire sensors. *3 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

A-16

CJ2 CPU Unit Hardware User’s Manual

Page 279

Appendices z CJ1W-INT01 Interrupt Input Unit (16 Points) Name

16-point Interrupt Input Unit with Terminal Block

Model

CJ1W-INT01

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

3.3 kΩ

Input Current

7 mA typical (at 24 VDC)

ON Voltage/ON Current

14.4 VDC min./3 mA min.

OFF Voltage/OFF Current 5 VDC max./1 mA max. ON Response Time

0.05 ms max.

OFF Response Time

0.5 ms max.

Number of Circuits

16 (16 points/common, 1 circuit)

Number of Simultaneously ON Points

100% (16 points/common) simultaneously ON (24 VDC)

Insulation Resistance

20 MΩ between external terminals and GR terminal (at 100 VDC)

Dielectric Strength

1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA max. 80 mA max.

Weight

110 g max.

Accessories

None Signal name 3.3 kΩ

IN15

470 Ω

1000 pF to

Internal circuits

IN0

COM Input indicator

COM

Circuit Configuration

16 points at 45°C

18

OFF

16 14

12 points at 55°C

Input voltage: 26.4 VDC

12

0.5 ms min.

ON 0.05 ms min.

10 8 6

2 0

0

10

20

30

40

50

60 (°C)

Ambient Temperature

CJ2 CPU Unit Hardware User’s Manual

A-17

A-1-2 Basic I/O Units

4

*1 With the CJ2JH-CPU6@-EIP CPU Units, the Unit must be mounted as one of the four Units immediately next to the CPU Unit.

App

Number of simultaneously ON points

Temperature characteristics for simultaneously ON points

• Up to two Interrupt Input Units can be mounted to the CPU Rack, but they must be connected as one the five Unit*1 immediately next to the CPU Unit. If an Interrupt Input Unit is connected in any other position, an I/O setting error will occur. • Set the pulse width of signals input to the Interrupt Input Unit so they satisfy the following conditions.

A-1 Specifications of Basic I/O Units

Internal Current Consumption

Page 280

Appendices

*1

Signal name

IN0 IN2 IN4 IN6 IN8

Terminal Connections

IN10 IN12 IN14 COM

Connector pin

A0 B0 A1 B1 A2 B2 A3 B3 A4

Signal name

IN1 IN3 IN5 24 VDC

IN7 IN9

B4 A5

IN11 B5

A6

IN13 B6 IN15

A7 B7 A8

COM B8

• The polarity can be connected in either direction. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

z CJ1W-IDP01 Quick-response Input Unit (16 Points)

A-18

Name

16-point Quick-response Input Unit with Terminal Block

Model

CJ1W-IDP01

Rated Input Voltage

24 VDC

Rated Input Voltage Range

20.4 to 26.4 VDC

Input Impedance

3.3 kΩ

Input Current

7 mA typical (at 24 VDC)

ON Voltage/ON Current

14.4 VDC min./3 mA min.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time

0.05 ms max.

OFF Response Time

0.5 ms max.

Number of Circuits

16 (16 points/common, 1 circuit)

Number of Simultaneously ON Points

100% (16 points/common) simultaneously ON (24 VDC)

Insulation Resistance

20 MΩ between external terminals and GR terminal (at 100 VDC)

Dielectric Strength

1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

80 mA max.

Weight

110 g max.

Accessories

None

CJ2 CPU Unit Hardware User’s Manual

Page 281

Appendices

Signal name 3.3 kΩ

IN15

470 Ω

1000 pF to

Internal circuits

IN0

COM Input indicator

COM

Number of simultaneously ON points -- 16 points at 45°C Ambient temperature characteristics

Circuit Configuration Number of simultaneously ON points

18 16

12 points at 55°C

14

Input voltage: 26.4 VDC

12 10 8 6 4 2 0

0

10

20

30

40

50

60 (°C)

Ambient Temperature *1

Signal name

Connector pin

Signal name

IN0

A0

IN1

B0

IN2

A1

IN3

B1

IN4

A2

IN5 IN7

B3

IN8

IN9

A4 B4

IN10

A5

IN11

B5

IN12

A6

IN13

B6

IN14

A7

IN15

B7

COM

COM

A8 B8

• The input power supply polarity can be connected in either direction.

• With quick-response inputs, pulse inputs shorter than the CPU Unit's cycle time can be read by the CPU Unit.

App

• The pulse width (ON time) that can be read by the Quick-response Input Unit is 0.05 ms.

A-1 Specifications of Basic I/O Units

A3

Terminal Connections

24 VDC

B2

IN6

• Inputs read by the internal circuits are cleared when inputs are refreshed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-19

Page 282

Appendices

Basic Output Units z CJ1W-OC201 Contact Output Unit (Independent Relays, 8 Points) Name

8-point Contact Output Unit with Terminal Block (Independent Relays)

Model

CJ1W-OC201

Max. Switching Capacity

2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (16 A/Unit)

Min. Switching Capacity

1 mA 5 VDC

Relays

NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced. Electrical: 150,000 operations (24 VDC, resistive load)/100,000 operations (240 VAC, cosφ = 0.4, inductive load)

Service Life of Relay

Mechanical: 20,000,000 operations Service life will vary depending on the connected load. Refer to page A-57 for information on service life according to the load.

ON Response Time

15 ms max.

OFF Response Time

15 ms max.

Number of Circuits

8 independent contacts

Insulation Resistance

20 MΩ between external terminals and the GR terminal (500 VDC)

Dielectric Strength

2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

90 mA 5 VDC max. 48 mA 24 VDC max. (6 mA × No. of ON points)

Weight

140 g max. Signal name

Circuit Configuration

Internal circuits

OUT

OUTc

Output indicator

Signal name OUT0 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6

Terminal Connections

OUT7 NC

*1

Connector pin

A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8

Signal name OUTC0 OUTC1 OUTC2 OUTC3 OUTC4 OUTC5 OUTC6 OUTC7

L L L L L L L L

NC

2 A 250 VAC, 2 A 24 VDC max.

• The input power supply polarity can be connected in either direction. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

A-20

CJ2 CPU Unit Hardware User’s Manual