The text of a manual · part 34 of 48
SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Appendices, pages 283 to 292
Pages 283 to 292 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213
Page 283
Appendices z CJ1W-OC211 Contact Output Unit (16 Points) Name
16-point Contact Output Unit with Terminal Block
Model
CJ1W-OC211
Max. Switching Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit)
Min. Switching Capacity
1 mA 5 VDC
Relays
NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced. Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 operations (240 VAC, cosφ = 0.4, inductive load)
Service Life of Relay
Mechanical: 20,000,000 operations Service life will vary depending on the connected load. Refer to page A-57 for information on service life according to the load.
ON Response Time
15 ms max.
OFF Response Time
15 ms max.
Number of Circuits
16 points/common, 1 circuit
Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
110 mA 5 VDC max. 96 mA 24 VDC max. (6 mA × No. of ON points)
Weight
170 g max. A-1 Specifications of Basic I/O Units
Signal name OUT0 to
Circuit Configuration
Internal circuits
OUT15
COM COM
Output indicator
*1
Signal name OUT0
L
OUT2
L
Terminal Connections
OUT6
L
OUT8 OUT10
L
OUT12
L
OUT14 COM
B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8
OUT1
L
OUT3
L
OUT5
L
OUT7
L
OUT9
L
OUT11
L
OUT13
L
OUT15
L
A-1-2 Basic I/O Units
L L
2 A 250 VAC, 2 A 24 VDC max.
OUT4
A0
Signal name
App
L
Connector pin
COM
*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
CJ2 CPU Unit Hardware User’s Manual
A-21
Page 284
Appendices z CJ1W-OA201 Triac Output Unit (8 Points) Name
8-point Triac Output Unit with Terminal Block
Model
CJ1W-OA201
Max. Switching Capacity
0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit)
Max. Inrush Current
15 A (pulse width: 10 ms max.)
Min. Switching Capacity
50 mA 75 VAC
Leakage Current
1.5 mA (200 VAC) max.
Residual Voltage
1.6 VAC max.
ON Response Time
1 ms max.
OFF Response Time
1/2 of load frequency + 1 ms or less.
Number of Circuits
8 (8 points/common, 1 circuit)
Surge Protector
C.R Absorber + Surge Absorber
Fuses
5 A (1/common, 1 used) The fuse cannot be replaced by the user.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (500 VDC)
Dielectric Strength
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
220 mA max.
Weight
150 g max. Signal name
Internal circuits
Output indicator
Circuit Configuration
OUT0 to OUT7 COM Fuse
*1
NC
Connector pin
Signal name
A0
OUT0
B0 NC
A1
NC
A2
NC
A3
NC
A4
OUT1
B1 OUT2
B2
Terminal Connections
OUT3
B3
B5 A6
NC
A7
OUT6
B6 OUT7
B7 NC
L L L
OUT5
A5
NC
L
OUT4
B4 NC
L
A8
250 VAC max.
L L L
COM
B8
*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
A-22
CJ2 CPU Unit Hardware User’s Manual
Page 285
Appendices z CJ1W-OD201 Transistor Output Unit (8 Points) Name
8-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD201
Rated Voltage
12 to 24 VDC
Operating Load Voltage Range
10.2 to 26.4 VDC
Maximum Load Current
2.0 A/point, 8.0 A/Unit
Maximum Inrush Current
10 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
8 (4 points/common, 2 circuits)
Internal Current Consumption
90 mA max.
Fuse
6.3 A (1/common, 2 used) The fuse cannot be replaced by the user.
External Power Supply
12 to 24 VDC, 10 mA min.
Weight
110 g max. A-1 Specifications of Basic I/O Units
Signal name +V
Circuit Configuration
Internal circuits
OUT0 to OUT3 Fuse COM0
Output indicator
+V OUT4 to OUT7 Fuse COM1
*1
Signal name
Connector pin
Signal name
App
OUT0
A0
L L
B0
OUT2
A1 B1 A2 B2
COM0
A3 B3
NC
A4
Terminal Connections
B4
L L
OUT4
A5 B5
OUT6
A6 B6
NC 12 to 24 VDC COM1
A7 B7 A8 B8
OUT3
L L
A-1-2 Basic I/O Units
NC 12 to 24 VDC
OUT1
NC +V NC OUT5 OUT7
L L
NC
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
CJ2 CPU Unit Hardware User’s Manual
A-23
Page 286
Appendices z CJ1W-OD203 Transistor Output Unit (8 Points) Name
8-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD203
Rated Voltage
12 to 24 VDC
Operating Load Voltage Range
10.2 to 26.4 VDC
Maximum Load Current
0.5 A/point, 4.0 A/Unit
Maximum Inrush Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.8 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
8 (8 points/common, 1 circuit)
Internal Current Consumption
100 mA max.
Fuse
None
External Power Supply
10.2 to 26.4 VDC, 20 mA min.
Weight
110 g max. Signal name
Circuit Configuration
Internal circuits
Output indicator +V OUT0 to OUT7
COM
*1
Signal Connec- Signal name tor pin name
Terminal Connections
L OUT0 A0 OUT1 L B0 L OUT2 A1 OUT3 L B1 OUT4 L A2 OUT5 L B2 L OUT6 A3 OUT7 L B3 NC A4 NC B4 NC A5 NC B5 NC A6 NC B6 NC A7 NC 12 to 24 VDC B7 COM A8 +V B8
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.
A-24
CJ2 CPU Unit Hardware User’s Manual
Page 287
Appendices z CJ1W-OD211 Transistor Output Unit (16 Points) Name
16-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD211
Rated Voltage
12 to 24 VDC
Operating Load Voltage Range
10.2 to 26.4 VDC
Maximum Load Current
0.5 A/point, 5.0 A/Unit
Maximum Inrush Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.8 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
16 (16 points/common, 1 circuit)
Internal Current Consumption
5 VDC 100 mA max.
Fuse
None
External Power Supply
10.2 to 26.4 VDC, 20 mA min.
Weight
110 g max.
Internal circuits
Circuit Configuration
A-1 Specifications of Basic I/O Units
Signal name
Output indicator +V OUT0 to OUT15
COM
*1
Signal name
L L L
OUT2 OUT4 OUT6
L
OUT8
L
OUT10
L
OUT12
L
OUT14 COM
12 to 24 VDC
B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8
OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15
L L L L L L L L
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
CJ2 CPU Unit Hardware User’s Manual
A-25
A-1-2 Basic I/O Units
L
A0
Signal name
App
Terminal Connections
OUT0
Connector pin
Page 288
Appendices z CJ1W-OD213 Transistor Output Unit (16 Points) Name
16-point Transistor Output Unit with Terminal Block (Sinking Outputs)
Model
CJ1W-OD213
Rated Voltage
24 VDC
Operating Load Voltage Range
20.4 to 26.4 VDC
Maximum Load Current
0.5 A/point, 5.0 A/Unit
Maximum Inrush Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
15 µs max.
OFF Response Time
80 µs max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
16 (16 points/common, 1 circuit)
Internal Current Consumption
5 VDC 150 mA max.
Fuse
None
External Power Supply
20.4 to 26.4 VDC, 55 mA min.
Weight
110 g max. Signal name +V OUT0 to
Internal circuits
Circuit Configuration
OUT15
COM Output indicator
*1
Signal name
L L L
Terminal Connections
OUT0 OUT2 OUT4
L
OUT6
L
OUT8
L
OUT10
L
OUT12
L
OUT14 COM
24 VDC
Connector pin
A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8
Signal name
OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15
L L L L L L L L
+V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.
A-26
CJ2 CPU Unit Hardware User’s Manual
Page 289
Appendices z CJ1W-OD231 Transistor Output Unit (32 Points) Name
32-point Transistor Output Unit with Fujitsu Connector (Sinking Outputs)
Model
CJ1W-OD231
Rated Voltage
12 to 24 VDC
Operating Load Voltage Range
10.2 to 26.4 VDC
Maximum Load Current
0.5 A/point, 2.0 A/common, 4.0 A/Unit
Maximum Inrush Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.8 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
32 (16 points/common, 2 circuits)
Internal Current Consumption
5 VDC 140 mA max.
Fuse
None
External Power Supply
10.2 to 26.4 VDC, 30 mA min.
Weight
70 g max.
Accessories
None A-1 Specifications of Basic I/O Units
Signal name
Allocated CIO word
+V
Circuit Configuration
Internal circuits
OUT0 to OUT15
Output indicator
Wd m
Connect or row A
Wd m+1
Connect or row B
COM0 COM0
SW
+V OUT0 to OUT15 COM1 COM1
App A-1-2 Basic I/O Units
CJ2 CPU Unit Hardware User’s Manual
A-27
Page 290
Appendices
Signal Connec- Signal name tor pin name
Allocated CIO word
OUT0
A1
B1
OUT0
OUT1
A2
B2
OUT1
L OUT2 A3
B3
OUT2
L OUT3 A4
B4
OUT3
L OUT4 A5
B5
OUT4
L L
Wd m
12 to 24 VDC
L
OUT5
A6
B6
OUT5
L
OUT6
A7
B7
OUT6
L OUT7 A8
B8
COM0
A9
B9
OUT7
Allocated CIO word L L L L L
12 to 24 VDC
Wd m+1
L L L
COM1
+V A10 B10 +V
L L
OUT8 A11 B11 OUT8 OUT9
A12 B12
OUT9
L L
L OUT10 A13 B13 OUT10 L
Terminal Connections
Wd m
L OUT11 A14 B14 OUT11 L L
OUT12
L
OUT13
L
OUT14
A15 B15 A16 B16 A17 B17
OUT12 OUT13 OUT14
Wd m+1
L L L
L OUT15 A18 B18 OUT15 L COM0 +V
A19 B19 A20 B20
COM1 +V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals A9 and A19 (COM0). • Be sure to wire both terminals B9 and B19 (COM1). • Be sure to wire both terminals A10 and A20 (+V). • Be sure to wire both terminals B10 and B20 (+V).
A-28
CJ2 CPU Unit Hardware User’s Manual
Page 291
Appendices z CJ1W-OD233 Transistor Output Unit (32 Points) Name
32-point Transistor Output Unit with MIL Connector (Sinking Outputs)
Model
CJ1W-OD233
Rated Voltage
12 to 24 VDC
Operating Load Voltage Range
10.2 to 26.4 VDC
Maximum Load Current
0.5 A/point, 2 A/common, 4 A/Unit
Maximum Inrush Current
4.0 A/point, 10 ms max.
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.8 ms max.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits
32 (16 points/common, 2 circuits)
Internal Current Consumption
140 mA max.
Fuse
None
External Power Supply
12 to 24 VDC, 30 mA min.
Weight
70 g max. Signal name
Allocated CIO word
A-1 Specifications of Basic I/O Units
+V
Circuit Configuration
Internal circuits
OUT0 to OUT15
Output indicator
Wd m
COM0 COM0
SW
+V OUT0 to OUT15
Wd m+1
COM1 COM1
App A-1-2 Basic I/O Units
CJ2 CPU Unit Hardware User’s Manual
A-29
Page 292
Appendices
Allocated CIO word
Signal Connec- Signal name tor pin name +V COM1
L L L Wd m+1
L L L L L
L
Terminal Connections
L Wd m
L L L 12 to 24 VDC
L L
2
3
4
OUT15
5
6
OUT14
7
8
OUT13
9 10
OUT12
11 12
OUT11
13 14
OUT10
15 16
OUT9
17 18
OUT8
19 20
+V
21 22
COM0
L
1
23 24
OUT15
25 26
OUT14
27 28
OUT13
29 30
OUT12
31 32
OUT11
33 34
OUT10
35 36
OUT9
37 38
OUT8
39 40
+V COM1 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0
L L L L L L
Wd m+1
12 to 24 VDC
L L
+V COM0 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0
L L L L L
Wd m
Allocated CIO word
L L L
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals 23 and 24 (COM0). • Be sure to wire both terminals 3 and 4 (COM1). • Be sure to wire both terminals 21 and 22 (+V). • Be sure to wire both terminals 1 and 2 (+V).
A-30
CJ2 CPU Unit Hardware User’s Manual