Page 283

Appendices z CJ1W-OC211 Contact Output Unit (16 Points) Name

16-point Contact Output Unit with Terminal Block

Model

CJ1W-OC211

Max. Switching Capacity

2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit)

Min. Switching Capacity

1 mA 5 VDC

Relays

NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced. Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 operations (240 VAC, cosφ = 0.4, inductive load)

Service Life of Relay

Mechanical: 20,000,000 operations Service life will vary depending on the connected load. Refer to page A-57 for information on service life according to the load.

ON Response Time

15 ms max.

OFF Response Time

15 ms max.

Number of Circuits

16 points/common, 1 circuit

Insulation Resistance

20 MΩ between external terminals and the GR terminal (500 VDC)

Dielectric Strength

2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

110 mA 5 VDC max. 96 mA 24 VDC max. (6 mA × No. of ON points)

Weight

170 g max. A-1 Specifications of Basic I/O Units

Signal name OUT0 to

Circuit Configuration

Internal circuits

OUT15

COM COM

Output indicator

*1

Signal name OUT0

L

OUT2

L

Terminal Connections

OUT6

L

OUT8 OUT10

L

OUT12

L

OUT14 COM

B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8

OUT1

L

OUT3

L

OUT5

L

OUT7

L

OUT9

L

OUT11

L

OUT13

L

OUT15

L

A-1-2 Basic I/O Units

L L

2 A 250 VAC, 2 A 24 VDC max.

OUT4

A0

Signal name

App

L

Connector pin

COM

*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

CJ2 CPU Unit Hardware User’s Manual

A-21

Page 284

Appendices z CJ1W-OA201 Triac Output Unit (8 Points) Name

8-point Triac Output Unit with Terminal Block

Model

CJ1W-OA201

Max. Switching Capacity

0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit)

Max. Inrush Current

15 A (pulse width: 10 ms max.)

Min. Switching Capacity

50 mA 75 VAC

Leakage Current

1.5 mA (200 VAC) max.

Residual Voltage

1.6 VAC max.

ON Response Time

1 ms max.

OFF Response Time

1/2 of load frequency + 1 ms or less.

Number of Circuits

8 (8 points/common, 1 circuit)

Surge Protector

C.R Absorber + Surge Absorber

Fuses

5 A (1/common, 1 used) The fuse cannot be replaced by the user.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (500 VDC)

Dielectric Strength

2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

220 mA max.

Weight

150 g max. Signal name

Internal circuits

Output indicator

Circuit Configuration

OUT0 to OUT7 COM Fuse

*1

NC

Connector pin

Signal name

A0

OUT0

B0 NC

A1

NC

A2

NC

A3

NC

A4

OUT1

B1 OUT2

B2

Terminal Connections

OUT3

B3

B5 A6

NC

A7

OUT6

B6 OUT7

B7 NC

L L L

OUT5

A5

NC

L

OUT4

B4 NC

L

A8

250 VAC max.

L L L

COM

B8

*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

A-22

CJ2 CPU Unit Hardware User’s Manual

Page 285

Appendices z CJ1W-OD201 Transistor Output Unit (8 Points) Name

8-point Transistor Output Unit with Terminal Block (Sinking Outputs)

Model

CJ1W-OD201

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

2.0 A/point, 8.0 A/Unit

Maximum Inrush Current

10 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

8 (4 points/common, 2 circuits)

Internal Current Consumption

90 mA max.

Fuse

6.3 A (1/common, 2 used) The fuse cannot be replaced by the user.

External Power Supply

12 to 24 VDC, 10 mA min.

Weight

110 g max. A-1 Specifications of Basic I/O Units

Signal name +V

Circuit Configuration

Internal circuits

OUT0 to OUT3 Fuse COM0

Output indicator

+V OUT4 to OUT7 Fuse COM1

*1

Signal name

Connector pin

Signal name

App

OUT0

A0

L L

B0

OUT2

A1 B1 A2 B2

COM0

A3 B3

NC

A4

Terminal Connections

B4

L L

OUT4

A5 B5

OUT6

A6 B6

NC 12 to 24 VDC COM1

A7 B7 A8 B8

OUT3

L L

A-1-2 Basic I/O Units

NC 12 to 24 VDC

OUT1

NC +V NC OUT5 OUT7

L L

NC

+V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

CJ2 CPU Unit Hardware User’s Manual

A-23

Page 286

Appendices z CJ1W-OD203 Transistor Output Unit (8 Points) Name

8-point Transistor Output Unit with Terminal Block (Sinking Outputs)

Model

CJ1W-OD203

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

0.5 A/point, 4.0 A/Unit

Maximum Inrush Current

4.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.8 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

8 (8 points/common, 1 circuit)

Internal Current Consumption

100 mA max.

Fuse

None

External Power Supply

10.2 to 26.4 VDC, 20 mA min.

Weight

110 g max. Signal name

Circuit Configuration

Internal circuits

Output indicator +V OUT0 to OUT7

COM

*1

Signal Connec- Signal name tor pin name

Terminal Connections

L OUT0 A0 OUT1 L B0 L OUT2 A1 OUT3 L B1 OUT4 L A2 OUT5 L B2 L OUT6 A3 OUT7 L B3 NC A4 NC B4 NC A5 NC B5 NC A6 NC B6 NC A7 NC 12 to 24 VDC B7 COM A8 +V B8

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

A-24

CJ2 CPU Unit Hardware User’s Manual

Page 287

Appendices z CJ1W-OD211 Transistor Output Unit (16 Points) Name

16-point Transistor Output Unit with Terminal Block (Sinking Outputs)

Model

CJ1W-OD211

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

0.5 A/point, 5.0 A/Unit

Maximum Inrush Current

4.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.8 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

16 (16 points/common, 1 circuit)

Internal Current Consumption

5 VDC 100 mA max.

Fuse

None

External Power Supply

10.2 to 26.4 VDC, 20 mA min.

Weight

110 g max.

Internal circuits

Circuit Configuration

A-1 Specifications of Basic I/O Units

Signal name

Output indicator +V OUT0 to OUT15

COM

*1

Signal name

L L L

OUT2 OUT4 OUT6

L

OUT8

L

OUT10

L

OUT12

L

OUT14 COM

12 to 24 VDC

B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8

OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15

L L L L L L L L

+V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

CJ2 CPU Unit Hardware User’s Manual

A-25

A-1-2 Basic I/O Units

L

A0

Signal name

App

Terminal Connections

OUT0

Connector pin

Page 288

Appendices z CJ1W-OD213 Transistor Output Unit (16 Points) Name

16-point Transistor Output Unit with Terminal Block (Sinking Outputs)

Model

CJ1W-OD213

Rated Voltage

24 VDC

Operating Load Voltage Range

20.4 to 26.4 VDC

Maximum Load Current

0.5 A/point, 5.0 A/Unit

Maximum Inrush Current

4.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

15 µs max.

OFF Response Time

80 µs max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

16 (16 points/common, 1 circuit)

Internal Current Consumption

5 VDC 150 mA max.

Fuse

None

External Power Supply

20.4 to 26.4 VDC, 55 mA min.

Weight

110 g max. Signal name +V OUT0 to

Internal circuits

Circuit Configuration

OUT15

COM Output indicator

*1

Signal name

L L L

Terminal Connections

OUT0 OUT2 OUT4

L

OUT6

L

OUT8

L

OUT10

L

OUT12

L

OUT14 COM

24 VDC

Connector pin

A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8

Signal name

OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15

L L L L L L L L

+V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. *1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

A-26

CJ2 CPU Unit Hardware User’s Manual

Page 289

Appendices z CJ1W-OD231 Transistor Output Unit (32 Points) Name

32-point Transistor Output Unit with Fujitsu Connector (Sinking Outputs)

Model

CJ1W-OD231

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

0.5 A/point, 2.0 A/common, 4.0 A/Unit

Maximum Inrush Current

4.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.8 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

32 (16 points/common, 2 circuits)

Internal Current Consumption

5 VDC 140 mA max.

Fuse

None

External Power Supply

10.2 to 26.4 VDC, 30 mA min.

Weight

70 g max.

Accessories

None A-1 Specifications of Basic I/O Units

Signal name

Allocated CIO word

+V

Circuit Configuration

Internal circuits

OUT0 to OUT15

Output indicator

Wd m

Connect or row A

Wd m+1

Connect or row B

COM0 COM0

SW

+V OUT0 to OUT15 COM1 COM1

App A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-27

Page 290

Appendices

Signal Connec- Signal name tor pin name

Allocated CIO word

OUT0

A1

B1

OUT0

OUT1

A2

B2

OUT1

L OUT2 A3

B3

OUT2

L OUT3 A4

B4

OUT3

L OUT4 A5

B5

OUT4

L L

Wd m

12 to 24 VDC

L

OUT5

A6

B6

OUT5

L

OUT6

A7

B7

OUT6

L OUT7 A8

B8

COM0

A9

B9

OUT7

Allocated CIO word L L L L L

12 to 24 VDC

Wd m+1

L L L

COM1

+V A10 B10 +V

L L

OUT8 A11 B11 OUT8 OUT9

A12 B12

OUT9

L L

L OUT10 A13 B13 OUT10 L

Terminal Connections

Wd m

L OUT11 A14 B14 OUT11 L L

OUT12

L

OUT13

L

OUT14

A15 B15 A16 B16 A17 B17

OUT12 OUT13 OUT14

Wd m+1

L L L

L OUT15 A18 B18 OUT15 L COM0 +V

A19 B19 A20 B20

COM1 +V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals A9 and A19 (COM0). • Be sure to wire both terminals B9 and B19 (COM1). • Be sure to wire both terminals A10 and A20 (+V). • Be sure to wire both terminals B10 and B20 (+V).

A-28

CJ2 CPU Unit Hardware User’s Manual

Page 291

Appendices z CJ1W-OD233 Transistor Output Unit (32 Points) Name

32-point Transistor Output Unit with MIL Connector (Sinking Outputs)

Model

CJ1W-OD233

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

0.5 A/point, 2 A/common, 4 A/Unit

Maximum Inrush Current

4.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.8 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

32 (16 points/common, 2 circuits)

Internal Current Consumption

140 mA max.

Fuse

None

External Power Supply

12 to 24 VDC, 30 mA min.

Weight

70 g max. Signal name

Allocated CIO word

A-1 Specifications of Basic I/O Units

+V

Circuit Configuration

Internal circuits

OUT0 to OUT15

Output indicator

Wd m

COM0 COM0

SW

+V OUT0 to OUT15

Wd m+1

COM1 COM1

App A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-29

Page 292

Appendices

Allocated CIO word

Signal Connec- Signal name tor pin name +V COM1

L L L Wd m+1

L L L L L

L

Terminal Connections

L Wd m

L L L 12 to 24 VDC

L L

2

3

4

OUT15

5

6

OUT14

7

8

OUT13

9 10

OUT12

11 12

OUT11

13 14

OUT10

15 16

OUT9

17 18

OUT8

19 20

+V

21 22

COM0

L

1

23 24

OUT15

25 26

OUT14

27 28

OUT13

29 30

OUT12

31 32

OUT11

33 34

OUT10

35 36

OUT9

37 38

OUT8

39 40

+V COM1 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0

L L L L L L

Wd m+1

12 to 24 VDC

L L

+V COM0 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0

L L L L L

Wd m

Allocated CIO word

L L L

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals 23 and 24 (COM0). • Be sure to wire both terminals 3 and 4 (COM1). • Be sure to wire both terminals 21 and 22 (+V). • Be sure to wire both terminals 1 and 2 (+V).

A-30