Page 293

Appendices z CJ1W-OD234 Transistor Output Unit (32 Points) Name

32-point Transistor Output Unit with MIL Connector (Sinking Outputs)

Model

CJ1W-OD234

Rated Voltage

24 VDC

Operating Load Voltage Range

20.4 to 26.4 VDC

Maximum Load Current

0.5 A/point, 2 A/common, 4 A/Unit

Maximum Inrush Current

4.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

15 µs max.

OFF Response Time

80 µs max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

32 (16 points/common, 2 circuits)

Internal Current Consumption

220 mA max.

Fuse

None

External Power Supply

20.4 to 26.4 VDC, 110 mA min.

Weight

70 g max.

Internal circuits

Circuit Configuration

A-1 Specifications of Basic I/O Units

Signal Allocated name CIO word +V OUT0 to Wd m OUT15 COM0 COM0 Output indicator SW

+V OUT0 to OUT15

Wd m+1

COM1 COM1

App A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-31

Page 294

Appendices

Allocated CIO word

Signal Connec- Signal name tor pin name

COM1

L L L Wd m+1

L L L L L

L

Terminal Connections

L Wd m

L L L L 24 VDC

L

2

3

4

OUT15

5

6

OUT14

7

8

OUT13

9 10

OUT12

11 12

OUT11

13 14

OUT10

15 16

OUT9

17 18

OUT8

19 20

+V

21 22

COM0

L

1

23 24

OUT15

25 26

OUT14

27 28

OUT13

29 30

OUT12

31 32

OUT11

33 34

OUT10

35 36

OUT9

37 38

OUT8

39 40

+V COM1 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0

L L L L L L

Wd m+1

+V

24 VDC

L L

+V COM0 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0

L L L L L

Wd m

Allocated CIO word

L L L

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals 23 and 24 (COM0). • Be sure to wire both terminals 3 and 4 (COM1). • Be sure to wire both terminals 21 and 22 (+V). • Be sure to wire both terminals 1 and 2 (+V).

A-32

CJ2 CPU Unit Hardware User’s Manual

Page 295

Appendices z CJ1W-OD261 Transistor Output Unit (64 Points) 64-point Transistor Output Unit with Fujitsu Connectors (Sinking Outputs)

Model

CJ1W-OD261

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

0.3 A/point, 1.6 A/common, 6.4 A/Unit

Maximum Inrush Current

3.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

64 (16 points/common, 4 circuits)

Internal Current Consumption

5 VDC, 170 mA max.

Fuse

None

External Power Supply

10.2 to 26.4 VDC, 50 mA min.

Weight

110 g max.

Accessories

None Signal name

A-1 Specifications of Basic I/O Units

Name

Allocated CIO word

Circuit Configuration

Internal circuits

+V

SW

Output indicator

OUT0 to OUT15 COM0 COM0 +V OUT0 to OUT15 COM1 COM1 +V

Connect or row A

CN1 Wd m+1

Connect or row B

Wd m+2

Connect or row A

CN2 Wd m+3

App

OUT0 to OUT15 COM2 COM2 +V OUT0 to OUT15 COM3 COM3

Wd m

Connect or row B

A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-33

Page 296

Appendices

CN1

+V COM1 name

B20 A20 B19 A19

Allocated CIO word

Allocated CIO word

+V

L OUT13 B16 A16 OUT13 L OUT12

L Wd m

Wd m+1

B15 A15

L OUT11 B14 A14 OUT11 L L OUT10 B13 A13 OUT10 L

Wd m+2

L OUT14 B17 A17 OUT14 L

OUT12

12 to 24 VDC

L OUT5 A6 B6 OUT5 L L OUT6 A7 B7 OUT6 L L

COM0

L OUT7 B8 A8 OUT7 L

L

B6 A6 OUT5

L

B5 A5 OUT4 OUT4

L

B4 A4 OUT3

L

OUT5

OUT3

L OUT2 B3 A3 OUT2 L

12 to 24 VDC

A8 B8 OUT7 A9 B9

COM3

+V

A10 B10

+V

L

OUT9

L

OUT10

L

OUT11

L

A12 B12 A13 B13 A14 B14

OUT9

L

OUT10

L

OUT11

L

L OUT12 A15 B15 OUT12 L L

OUT13

A16 B16

OUT13

L

L OUT14 A17 B17 OUT14 L L

OUT15

L OUT1 B2 A2 OUT1 L

COM2

L OUT0 B1 A1 OUT0 L

+V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals A9 and A19 (COM0) of CN1. • Be sure to wire both terminals B9 and B19 (COM1) of CN1. • Be sure to wire both terminals A10 and A20 (+V) of CN1. • Be sure to wire both terminals B10 and B20 (+V) of CN1.

A-34

Wd m+2

Wd m+1

Terminal Connections

12 to 24 VDC

L

Wd m

L OUT6 B7 A7 OUT6 L L

OUT7 COM2

12 to 24 VDC

L OUT8 A11 B11 OUT8 L

B10 A10 +V B9 A9

OUT2

L OUT4 A5 B5 OUT4 L

L OUT8 B11 A11 OUT8 L

COM1

OUT2

A3 B3 L L OUT3 A4 B4 OUT3 L

L

L OUT9 B12 A12 OUT9 L

+V

Allocated CIO word

L OUT1 A2 B2 OUT1 L

COM0

L OUT15 B18 A18 OUT15 L

L

Signal Connec- Signal name tor pin name L OUT0 A1 B1 OUT0 L

Wd m+3

Signal name

Wd m+3

Allocated CIO word

CN2

Connec- Signal tor pin

A18 B18 A19 B19 A20 B20

OUT15

L

COM3 +V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals A9 and A19 (COM2) of CN2. • Be sure to wire both terminals B9 and B19 (COM3) of CN2. • Be sure to wire both terminals A10 and A20 (+V) of CN2. • Be sure to wire both terminals B10 and B20 (+V) of CN2.

CJ2 CPU Unit Hardware User’s Manual

Page 297

Appendices z CJ1W-OD263 Transistor Output Unit (64 Points) Name

64-point Transistor Output Unit with MIL Connectors (Sinking Outputs)

Model

CJ1W-OD263

Rated Voltage

12 to 24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Maximum Load Current

0.3 A/point, 1.6 A/common, 6.4 A/Unit

Maximum Inrush Current

3.0 A/point, 10 ms max.

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

64 (16 points/common, 4 circuits)

Internal Current Consumption 170 mA max. Fuse

None

External Power Supply

12 to 24 VDC, 50 mA min.

Weight

110 g max. Allocated CIO word

A-1 Specifications of Basic I/O Units

Signal name

Circuit Configuration

Internal circuits

+V

SW Output indicator

OUT0 to OUT15 COM0 COM0 +V OUT0 to OUT15 COM1 COM1 +V OUT0 to OUT15 COM2 COM2 +V OUT0 to OUT15 COM3 COM3

Wd m CN1 Wd m+1

Wd m+2 CN2 Wd m+3

App A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-35

Page 298

Appendices

L

OUT1

L

OUT2

36 35

L

OUT3

34 33

L

OUT4

32 31

L

OUT5

30 29

L

OUT6

28 27

L

OUT7 COM0

38 37

26 25 24 23 22 21

OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15

L

12 to 24 VDC

L L

L

L

L

L

L

L

L

L

L L

L

OUT13 OUT12 OUT11 OUT10 OUT9

2 +V

3

4

5

6 OUT7 L

7

8

9 10 11 12 13 14 15 16

COM3

OUT6 OUT5 OUT4 OUT3 OUT2 OUT1

L L L L L

+V

OUT0 L OUT8 19 20 L +V

L

OUT1

18 17 OUT9 L

L

OUT2

16 15 OUT10 L

L

L

OUT3

14 13 OUT11 L

L

L

OUT4

12 11 OUT12 L

L

OUT5

10 9 OUT13 L

L

OUT6

8

7 OUT14 L

L

OUT7

6

5 OUT15 L

4

3

2

1

+V

OUT14

1

L

L

20 19

OUT15

Allocated CIO word

COM0

OUT0

COM1

OUT8

L

COM2

COM1 +V

12 to 24 VDC

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals 23 and 24 (COM0) of CN1. • Be sure to wire both terminals 3 and 4 (COM1) of CN1. • Be sure to wire both terminals 21 and 22 (+V) of CN1. • Be sure to wire both terminals 1 and 2 (+V) of CN1.

A-36

+V COM3

L L

Wd m+2

Terminal Connections

Wd m+1

+V

40 39

12 to 24 VDC

Wd m+3

OUT0

Signal Connec- Signal name tor pin name

Wd m

L

Allocated CIO word

L L 12 to 24 VDC

L L

OUT15 OUT14 OUT13 OUT12 OUT11 OUT10 OUT9 OUT8

17 18

Wd m+3

Signal Connec- Signal name tor pin name

Wd m+1

Wd m

Allocated CIO word

CN2 Allocated CIO word

L

21 22 +V 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

COM2 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2

L L L L L L

Wd m+2

CN1

OUT1

L OUT0

L

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. • Be sure to wire both terminals 23 and 24 (COM2) of CN2. • Be sure to wire both terminals 3 and 4 (COM3) of CN2. • Be sure to wire both terminals 21 and 22 (+V) of CN2. • Be sure to wire both terminals 1 and 2 (+V) of CN2.

CJ2 CPU Unit Hardware User’s Manual

Page 299

Appendices z CJ1W-OD202 Transistor Output Unit (8 Points) Name

8-point Transistor Output Unit with Terminal Block (Sourcing Outputs)

Model

CJ1W-OD202

Rated Voltage

24 VDC

Operating Load Voltage Range

20.4 to 26.4 VDC

Maximum Load Current

2 A/point, 8 A/Unit

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Load Short-circuit Protection

Detection current: 6 A min. Automatic restart after error clearance. (Refer to page A-149.) Detection current: 200 mA (Refer to page A-149.)

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

8 (4 points/common, 2 circuits)

Internal Current Consumption

110 mA max.

Fuse

None

External Power Supply

24 VDC, 50 mA min.

Weight

120 g max.

A-1 Specifications of Basic I/O Units

Line Disconnection Detection

Signal name

OUT0 to

OUT3 0V

Output indicator

Short-circuit protection

Circuit Configuration

Internal circuits

Short-circuit protection

COM0 (+V)

COM1 (+V) OUT4 to

OUT7 0V

ERR indicator

App

• The ERR indicator will light and the corresponding bit in A050 to A069 (Basic I/O Unit Information, two points per bit) will turn ON if an overcurrent or line disconnection is detected.

A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-37

Page 300

Appendices

*1

Signal name

OUT0

L L

OUT2 NC 0V NC

Terminal Connections L L

OUT4 OUT6 NC 0V

Connector pin

A0 A1 A2 A3 A4 A5 A6 A7 A8

B0 B1 B2 B3 B4 B5 B6 B7 B8

Signal name

OUT1 OUT3

L L

NC 24 VDC

COM0 (+V) NC OUT5 OUT7

L L

NC 24 VDC

COM1 (+V)

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.

*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

A-38

CJ2 CPU Unit Hardware User’s Manual

Page 301

Appendices z CJ1W-OD204 Transistor Output Unit (8 Points) Name

8-point Transistor Output Unit with Terminal Block (Sourcing Outputs)

Model

CJ1W-OD204

Rated Voltage

24 VDC

Operating Load Voltage Range

20.4 to 26.4 VDC

Maximum Load Current

0.5 A/point, 4.0 A/Unit

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Load Short-circuit Protection

Detection current: 0.7 to 2.5 A Automatic restart after error clearance. (Refer to page A-149.)

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

8 (8 points/common, 1 circuit)

Internal Current Consumption

100 mA max.

Fuse

None

External Power Supply

20.4 to 26.4 VDC, 40 mA min.

Weight

120 g max.

Short-circuit protection

Internal circuits

Circuit Configuration

OUT0 to OUT7 0V

Output indicator ERR indicator

• When overcurrent is detected, the ERR indicator will light, and the corresponding flag in the Basic I/O Unit Information Area (A050 to A069) will turn ON.

A-1 Specifications of Basic I/O Units

Signal name COM (+V)

*1

L OUT0 A0 OUT1 L B0 L OUT2 A1 OUT3 L B1 L OUT4 A2 OUT5 L B2 L OUT6 A3 OUT7 L B3 NC A4 NC B4 NC A5 NC B5 NC A6 NC B6 NC A7 NC 0V B7 COM (+V) A8 B8 24 VDC

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.

*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit. Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O tables.

CJ2 CPU Unit Hardware User’s Manual

A-39

A-1-2 Basic I/O Units

Terminal Connections

App

Signal Connec- Signal name tor pin name

Page 302

Appendices z CJ1W-OD212 Transistor Output Unit (16 Points) Name

16-point Transistor Output Unit with Terminal Block (Sourcing Outputs)

Model

CJ1W-OD212

Rated Voltage

24 VDC

Operating Load Voltage Range

20.4 to 26.4 VDC

Maximum Load Current

0.5 A/point, 5.0 A/Unit

Maximum Inrush Current

0.1 mA max.

Leakage Current

1.5 V max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

Load Short-circuit Protection

Detection current: 0.7 to 2.5 A Automatic restart after error clearance. (Refer to page A-149.)

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Number of Circuits

16 (16 points/common, 1 circuit)

Internal Current Consumption

5 VDC, 100 mA max.

External Power Supply

20.4 to 26.4 VDC, 40 mA min.

Weight

120 g max. Signal name

Internal circuits

Circuit Configuration

Short-circuit protection

COM (+V)

OUT0 to

OUT15 0V

Output indicator ERR indicator

• When overcurrent is detected, the ERR indicator will light, and the corresponding flag in the Basic I/O Unit Information Area (A050 to A069) will turn ON. *1

Signal name

Terminal Connections

Connector pin

L

OUT0

A0

L

OUT2

A1

L

OUT4

L

OUT6

L

OUT8

L

OUT10

L

OUT12

L

OUT14 0V

A2 A3 A4 A5 A6 A7 A8

B0 B1 B2 B3 B4 B5 B6 B7 B8

Signal name

OUT1

L

OUT3

L

OUT5

L

OUT7

L

OUT9

L

OUT11

L

OUT13

L

OUT15

L

COM (+V) 24 VDC

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.

*1 Terminal numbers A0 to A8 and B0 to B8 are used in this manual, but they are not printed on the Unit.

A-40

CJ2 CPU Unit Hardware User’s Manual