Page 333
Appendices
Programmable Controller I/O Unit
CJ1W-ID233
Programmable Controller I/O Unit
CJ1W-ID233
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N
XW2D-40G6-RM
Wd m (Wd (m+1))
(Short bar)
− − A10 B10 A9 B9
+ 24 VDC
08 09 10 11 12 13 14 15
00
B19
01
B18
02
B17
03
A20 A19 A18 A17 B16 A16 B15 A15 B14 A14 B13 A13 B12
NC 08 09 10 11 12 13 14 15
Wd m
−
04
13 05
+ 12
06 07
Black (White)
−
Brown (Red)
+
3-wire sensor with PNP output (photoelectric sensor or proximity sensor)
11
COM0
10
A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2
Connection diagram
00
9 8
−
03
PNP
Blue (Black)
+
01 02
Blue (Black)
−
NC
Brown (White) 2-wire sensor (e.g., limit switch)
7
+
04
6 05
−
Wd (m+1)
06 07
5
Black (White)
+ 4 3
NC
+
A1
24 VDC
Brown (Red) Blue (Black)
−
COM1
A2 B1
NC
+ 14
3-wire sensor with NPN output (photoelectric sensor or proximity sensor)
NPN
2 Blue (Black)
+
2-wire sensor (e.g., limit switch)
Brown (White)
0
− +
Note 1 The polarity for input power supply connections indicated with dotted lines ( ) can be connected in either direction provided that the same polarity is used for the commons. 2 Both COM0 and COM1 have two pins each. They are internally connected inside the PLC, but they must all be wired.
CJ2 CPU Unit Hardware User’s Manual
24 VDC
Note 1 Connect the A9/B9 terminal and the NPN. Connect the A9/B9 terminal and the PNP. (Use the enclosed short bar.)
terminal for terminal for
2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
A-71
A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
− 1
App
COM1
− 15
A12 B11
Connection diagram
+
A-1 Specifications of Basic I/O Units
COM0
B20
Page 334
Appendices
Programmable Controller I/O Unit
CJ1W-ID261
Programmable Controller I/O Unit
CJ1W-ID261
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@B
Connecting Cables
XW2Z-@@@D
XW2D-40G6-RF
CN1 ( CN2 )
(Short bar)
CN1
Wd m (Wd (m+2)) NC NC COM0 (COM2) 15 14 13 12 11 10 09
Connection diagram
B19 A19 B18 A18 B17 A17 B16 A16 B15 A15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10
COM0 (COM2) 07
A9
05 24 VDC
B20 A20
08
06
04 03 02 01 00
( CN2 )
B9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2 A2 B1
NC
Wd m and m+1 (Wd m+2 and m+3)
− − A10 B10
Wd (m+1) (Wd (m+3))
A9 B9
+ +
NC COM1 (COM3)
− 15
15
+ 14
14
−
13
13 12
+ Black (White)
12
11
−
10
11
+
09
10
08
Connection diagram
COM1 (COM3) 07
Blue (Black) 3-wire sensor with PNP output (photoelectric sensor or proximity sensor)
PNP
− 9
Blue (Black)
+ 8
06
−
Brown (White) 2-wire sensor (e.g., limit switch)
7
05
+
04 03
Brown (Red)
24 VDC
02 01
6
− 5 4
−
00
A1
Black (White)
+
3
+
Brown (Red) Blue (Black) 3-wire sensor with NPN output (photoelectric sensor or proximity sensor)
NPN
2
−
Blue (Black)
+
2-wire sensor (e.g., limit switch)
Brown (White)
1 0
− +
Note 1 The polarity for input power supply connections indicated with dotted lines ( ) can be connected in either direction provided that the same polarity is used for the commons for rows A and B. 2 COM0, COM1, COM2, and COM3 have two pins each. They are internally connected inside the PLC, but they must all be wired.
A-72
24 VDC
Note 1 Connect the A9/B9 terminal and the NPN. Connect the A9/B9 terminal and the PNP. (Use the enclosed short bar.)
terminal for terminal for
2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
CJ2 CPU Unit Hardware User’s Manual
Page 335
Appendices
Programmable Controller I/O Unit
CJ1W-ID262
Programmable Controller I/O Unit
CJ1W-ID262
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N
XW2D-40G6-RM
CN1 ( CN2
(Short bar)
CN1 ( CN2
Wd m and m+1 (Wd m+2 and m+3)
)
− −
)
A10 B10 A9 B9
+ + 24 VDC 08 09 10 11 12 13 14
Connection diagram
12 13 14
03
B16 B15 A15 B14 A14 B13 A13 B12 B11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2
COM1 (COM3)
A2
NC
A1
B1
04
− 15
+ 14
−
Wd m (Wd (m+2))
13
+
05
Black (White)
12
−
06
11 07
+ 10
COM0 (COM2)
Connection diagram
NC
9 8
− + 6
04
06
Brown (White) 2-wire sensor (e.g., limit switch)
7
03
05
PNP
Blue (Black)
+
02
Blue (Black) 3-wire sensor with PNP output (photoelectric sensor or proximity sensor)
−
00 01
Brown (Red)
− Wd (m+1) (Wd (m+3))
07
5
Black (White)
+ 4
Blue (Black)
−
COM1 (COM3)
3
NC
2
+
24 VDC
Brown (Red)
3-wire sensor with NPN output (photoelectric sensor or proximity sensor)
Blue (Black)
+
2-wire sensor (e.g., limit switch)
Brown (White)
1 0
− +
Note 1 The polarity for input power supply connections indicated with dotted lines ( ) can be connected in either direction provided that the same polarity is used for the commons. 2 COM0, COM1, COM2, and COM3 have two pins each. They are internally connected inside the PLC, but they must all be wired.
CJ2 CPU Unit Hardware User’s Manual
24 VDC
Note 1 Connect the A9/B9 terminal and the NPN. Connect the A9/B9 terminal and the PNP. (Use the enclosed short bar.)
terminal for terminal for
2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
A-73
A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
−
NPN
App
15
B17
A16
A11
11
02
A17
NC
10
B18 A18
A12
09
B19
01
A19
COM0 (COM2)
08
00
A-1 Specifications of Basic I/O Units
15
B20 A20
Page 336
Appendices z Outputs Programmable Controller I/O Unit
CJ1W-OD231
Programmable Controller I/O Unit
CJ1W-OD231
ConnectorTerminal Block Conversion Unit
XW2D-40G6
XW2C-20G6-IO16 (2 Units)
XW2D-40C6
ConnectorTerminal Block Conversion Unit
Connecting Cables
XW2Z-@@@B
Connecting Cables
XW2Z-@@@L
XW2Z-@@@BU
Wd m (Wd (m+1))
− (Short bar)
Wd (m+1)
Wd m +V COM0
L L
15 14
L
13
L
12
L
11
L
10
L
09
L
Connection diagram
08 +V
COM0
L
12 to 24 VDC
COM0 (COM1)
07
L
06
L
05
L
04
L
03
L
02
L
01
L
00
B20 A20 B19 A19 B18 A18 B17 A17 B16 A16 B15
+V
− A10 B10 A9 B9
+
B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2 A2 B1
(Short bar)
+
COM1
−
15
15
15
L
14
L
13
L
12
L
+
14
14
Solenoid valve, etc.
−
13
13
+
12
A15
+V
11
L
10
L
09
L
08
L
12
−
11
11
+
10
10
+V
−
09
Connection diagram
COM1 07
L
06
L
05
L
04
L
03
L
02
L
01
L
00
L
9
+
08
8
−
07
7
+
06 12 to 24 VDC
6
−
05
5
+
04
4
−
03
3
A1
+
02
2
−
01
Solenoid valve, etc.
1
+
00
0
− +
12 to 24 VDC
Note The +V terminals and COM terminals are internally connected inside the PLC, but they must all be wired. Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
A-74
CJ2 CPU Unit Hardware User’s Manual
Page 337
Appendices
Programmable Controller I/O Unit
CJ1W-OD232
Programmable Controller I/O Unit
CJ1W-OD232
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N Wd m (Wd (m+1))
−
(Short bar)
−
COM0 (COM1)
A9 B9
A10 B10
+
24 VDC
L L
09
A19
L
10
A18
L
11
L
12
L
13
L
14
L
15
COM0 (+V)
L
08
L
09
L
10
L
11
L
12
L
13
L
14
L
15 0V
A20 B19
02
B17
03
L
B16
04
L
05
L
A17 A16 B15 A15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2
15
L
L L
Wd m
13
+
12
−
11
11
+
10
10
COM0 (+V)
−
09
L
Connection diagram
L
02
L
03
L
04
L
05
L
06
L
9
+
08
8
−
07
7
+
06
6 Wd (m+1)
L
−
05
5
+
04
4
−
0V 03
A2 A1
−
13
0V
07
Solenoid valve, etc.
12
07
01
+
14
14
06
00
−
15
L
(Short bar)
3 COM1 (+V)
App
COM1 (+V)
L
B18
B1 24 VDC
01
+
A-1 Specifications of Basic I/O Units
0V
Connection diagram
B20
08
00
+V
+
02
2
−
01
Solenoid valve, etc.
+
00
0
− + 24 VDC
Note The COM (+V) terminals and 0 V terminals are internally connected inside the PLC, but they must all be wired.
Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
CJ2 CPU Unit Hardware User’s Manual
A-75
A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
1
Page 338
Appendices
Programmable Controller I/O Unit
CJ1W-OD233
Programmable Controller I/O Unit
CJ1W-OD233
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N Wd m (Wd (m+1))
−
(Short bar)
−
COM0 (COM1)
A9 B9
A10 B10 12 to 24 VDC
L
08
L
09
L
10
L
11
L
12
L
13
L
14
L
15
COM0 +V
Connection diagram
L L
08 09
L
10
L
11
L
12
L
13
L
14
L
15
B20 A20 B19 A19
COM1 +V
01
15 L
B17
03
L
B16
04
L
05
L
A16 B15 A15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4
14
B3
13
+
12 06
L
07
L
12
−
11
11
COM0
+
10
10
+V 00
L
02
L
03
L
04
L
05
L
06
L
−
09
L
01
07
Solenoid valve, etc.
−
13
Connection diagram
9
+
08
8
−
07
7
+
06
6
Wd (m+1)
L
−
05
5
+
04
A3
4
A2 B1 A1
+
14 Wd m
A17
(Short bar)
−
15
L
B18 A18
+ +
L
02
B2 12 to 24 VDC
00
+V
COM1
−
03
3
+V
+
02
2
−
01
Solenoid valve, etc.
1
+
00
0
− + 12 to 24 VDC
Note The +V terminals and COM terminals are internally connected inside the PLC, but they must all be wired.
Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
A-76
CJ2 CPU Unit Hardware User’s Manual
Page 339
Appendices
Programmable Controller I/O Unit
CJ1W-OD234
Programmable Controller I/O Unit
CJ1W-OD234
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N Wd m (Wd (m+1))
−
(Short bar)
−
COM0 (COM1)
A9 B9
A10 B10 12 to 24 VDC
L
08
L
09
L
10
L
11
L
12
L
13
L
14
L
15
+V
Connection diagram
L L
08 09
L
10
L
11
L
12
L
13
L
14
L
15
A20 B19 A19
COM1
15
B18
L
B17
03
L
B16
04
L
05
L
A18
−
15
L
+
14
14
A16 B15 A15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3
13
13
+
12 06
L
07
L
12
−
11
11
COM0
+
10
10
+V 00
L
02
L
03
L
04
L
05
L
06
L
−
09
L
01
07
Solenoid valve, etc.
−
Wd m
A17
(Short bar)
Connection diagram
9
+
08
8
−
07
7
+
06
6
Wd (m+1)
L
−
05
5
+
04
A3
4
A2 B1 A1
COM1
−
03
3
+V
App
+V
01
+ +
L
02
B2 12 to 24 VDC
00
A-1 Specifications of Basic I/O Units
COM0
B20
+V
+
02
2
−
01
Solenoid valve, etc.
+
00
0
− + 12 to 24 VDC
Note The +V terminals and COM terminals are internally connected inside the PLC, but they must all be wired.
Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
CJ2 CPU Unit Hardware User’s Manual
A-77
A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
1
Page 340
Appendices
Programmable Controller I/O Unit
CJ1W-OD261
Programmable Controller I/O Unit
CJ1W-OD261
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@L
Connecting Cables
XW2D-40C6
XW2Z-@@@B XW2Z-@@@BU
CN1
Wd m and (m+1) (Wd (m+2) and (m+3))
( CN2 )
(Short bar)
− − A10 B10
COM
+ CN1
Wd m (Wd (m+2)) +V COM0 (COM2)
Connection diagram
L
15
L
14
L
13
L
12
L
11
L
10
L
09
L
08 +V
COM0 (COM2) 07
L
12 to 24 VDC
L
06
L
05
L
04
L
03
L
02
L
01
L
00
( CN2 )
B20 A20 B19 A19 B18 A18 B17 A17 B16 A16 B15 A15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2 A2 B1
+V
−
15
15
+
14
14
L
14
L
13
L
12
L
11
L
10
L
09
L
08
L
Solenoid valve, etc.
−
13
13
+
12
12
−
11
11
+
10
10
−
09
Connection diagram
+V
9
+
08
8
COM1 (COM3) 07
−
07
L
06
(Short bar)
+
Wd (m+1) (Wd (m+3))
COM1 (COM3) 15
+V
A9 B9
7
L
+
06
6
05
L
04
L
03
L
−
05 12 to 24 VDC
5
+
04
4
02
L
01
L
00
L
−
03
3
+
02
2
A1
−
01
Solenoid valve, etc.
1
+
00
0
− +
Note The +V terminals and COM terminals are internally connected inside the PLC, but they must all be wired.
12 to 24 VDC
Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
A-78
CJ2 CPU Unit Hardware User’s Manual
Page 341
Appendices
Programmable Controller I/O Unit
CJ1W-OD262
Programmable Controller I/O Unit
CJ1W-OD262
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N
CN1
Wd m and (m+1) (Wd (m+2) and (m+3))
( CN2 )
− CN1
24 VDC
L
08
L
09
L
10
B19 A19
A17
L
12
A16
L
13
L
14
L
15
L L
09
L
10
L
11
L
12
L
13
L
14
L
15 0V
COM0 (COM1)
A9 B9
01
L
03
L
B16
04
B15 B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2
+
L
B17
A15
L
05
L
06
L
07
L
(Short bar)
15
+
14
Solenoid valve, etc.
14
Wd m (Wd (m+2))
−
13
13
+
12
12
−
11
11
0V
10
L
02
L
03
L
04
L
05
L
06
L
−
09
L
01
+
10
COM0 (+V) (COM2 (+V)) 00
Connection diagram
9
+
08
8
−
07
7
+
06
07
+V
−
15
Wd (m+1) (Wd (m+3))
L
6
−
05
5
+
04
4
0V
−
03
App
A2 A1
A10 B10
+ L
B18
B1 24 VDC COM1 (+V) (COM3 (+V))
−
A-1 Specifications of Basic I/O Units
COM0 (+V) (COM2 (+V)) 08
00
02
A18
L
0V
Connection diagram
B20 A20
11
(Short bar)
( CN2 )
3
COM1 (+V) (COM3 (+V))
+
02
2 1
Solenoid valve, etc.
+
00
0
− + 24 VDC
Note The COM (+V) terminals and 0 V terminals are internally connected inside the PLC, but they must all be wired.
Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
CJ2 CPU Unit Hardware User’s Manual
A-79
A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
−
01
Page 342
Appendices
Programmable Controller I/O Unit
CJ1W-OD263
Programmable Controller I/O Unit
CJ1W-OD263
ConnectorTerminal Block Conversion Unit
XW2D-40G6
ConnectorTerminal Block Conversion Unit
XW2C-20G6-IO16 (2 Units)
Connecting Cables
XW2Z-@@@K
Connecting Cables
XW2Z-@@@N
CN1
Wd m and (m+1) (Wd (m+2) and (m+3))
( CN2 )
− CN1
( CN2
12 to 24 VDC
L
08
L
09
A19
L
10
A18
L
11
L
12
L
13
L
14
L
15
COM0 (COM2) +V
Connection diagram
L
12 to 24 VDC
B20
08
L
09
L
10
L
11
L
12
L
13
L
14
L
15
COM1 (COM3) +V
A20 B19
01
L L
B16
04
L
05
L
B14 A14 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 B5 A5 B4 A4 B3 A3 B2 A2 B1
A9 B9
06
L
07
L
01
(Short bar)
− +
14
14 Wd m (Wd (m+2))
Solenoid valve, etc.
−
13
13
+
12
12
−
11
11
+
10
10
−
09
L
Connection diagram
L
9
+
08
8
02
L
03
L
04
L
−
07
05
L
06
L
07
+
+V
15
COM0 (COM2) +V 00
A10 B10
15
L
03
A15
COM0 (COM1)
+
L
B17
B15
A1
00
02
A16
−
)
B18
A17
(Short bar)
7
+
06 Wd (m+1) (Wd (m + 3))
L
COM1 (COM3)
6
−
05
5
+
04
4
−
03
3
+V
+
02
2
−
01
Solenoid valve, etc.
1
+
00
0
− + 12 to 24 VDC
Note The +V terminals and COM terminals are internally connected inside the PLC, but they must all be wired.
Note 1 Connect the A9/B9 terminal and the terminal. Connect the A10/B10 terminal and the terminal. (Use the enclosed short bar.) 2 The COM terminals are wired inside the Connector-Terminal Block Conversion Unit.
A-80
CJ2 CPU Unit Hardware User’s Manual