Page 393

Appendices z Connections to RS-232C Ports RS-232C can also be used to connect two CJ2M CPU Units with a Serial PLC Link. CJ2M CPU Unit RS-232C Option Board Pin No.

Pin No.

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

FG SD RD RS CS 5V DR ER SG

Signal name

FG SD RD RS CS 5V DR ER SG

RS-232C

RS-232C

Signal name

CJ2M CPU Unit RS-232C Option Board z Connection Example CJ2M CPU Unit (Polled Unit 0) RS-422A/485 Option Board CP1W-CIF11/CIF12 DIP SW SW1: ON (terminating resistance OFF) SW2: OFF (4-wire) SW3: OFF (4-wire) SW4: OFF SW5: OFF (no RS control for RD) SW6: ON (RS control for SD)

RS-422A/485 interface

RS-422A/485 interface

CJ1M CPU Unit (Polled Unit 1) CJ1W-CIF11 DIP SW SW1: ON (terminating resistance ON) SW2: OFF (4-wire) SW3: OFF (4-wire) SW4: OFF SW5: OFF (no RS control for RD) SW6: ON (RS control for SD)

A-4 Connecting to a Serial Port on the CPU Unit

CJ2M CPU Unit (Polling Unit) RS-232C Option Board CP1W-CIF01 CJ1W-CIF11 DIP SW SW1: ON (terminating resistance ON) SW2: OFF (4-wire) SW3: OFF (4-wire) SW4: OFF SW5: OFF (no RS control for RD) SW6: OFF (no RS control for SD)

Signal name

Signal name

Signal name

RS-422A/485 interface

Pin No.

Pin No.

Pin No.

Shield

CJ2M CPU Unit (Polled Unit 0) RS-422A/485 Option Board CP1W-CIF11/CIF12 DIP SW SW1: OFF (terminating resistance OFF) SW2: ON (2-wire) SW3: ON (2-wire) SW4: OFF SW5: OFF (no RS control for RD) SW6: ON (RS control for SD)

Pin No.

FG

5

SDB

4

SDA

3

RDB

2

Signal name

1

RDA

Pin No.

FG

5

SDB

4

SDA

FG

3

RDB

SDB

2

RS-422A/485 interface

RDA

SDA

1

Signal name

RDB

RS-422A/485 interface

RDA

Pin No.

CJ1W-CIF11 DIP SW SW1: ON (terminating resistance ON) SW2: ON (2-wire) SW3: ON (2-wire) SW4: OFF SW5: OFF (no RS control for RD) SW6: ON (RS control for SD)

1

2

3

4

5

A-4-2 Connection Examples

Signal name

RS-422A/485 interface

CJ1M CPU Unit (Polled Unit 1)

App

CJ2M CPU Unit (Polling Unit) RS-232C Option Board CP1W-CIF01 CP1W-CIF11 DIP SW SW1: ON (terminating resistance ON) SW2: ON (2-wire) SW3: ON (2-wire) SW4: OFF SW5: OFF (no RS control for RD) SW6: ON (RS control for SD)

Shield

CJ2 CPU Unit Hardware User’s Manual

A-131

Page 394

Appendices z Connections for Echoback Test Use the following connections. RS-232C port Pin No. Signal name 2 SD 3 RD 4 RS 5 CS 1 FG 8 ER 7 DR

A-4-3

RS-422A/485 port Pin No. Signal name 3 SDA4 SDB+ 1 RDA2 RDB+ 5 FG

Applicable Connectors and Recommended Cables

Examples of Recommended RS-232C Wiring We recommend the following wiring methods for RS-232C, especially in environment prone to noise. • Use shielded twisted-pair cable for communications cables. • Use a twisted-pair cable for each signal line and SG (signal ground) to connect the CPU Unit to a communications partner. Also, bundle all the SG lines at the Unit and at the other device and connect them together. • Connect the shield line of the communications cable to the hood (FG) of the RS-232C connector at the Unit. Also, ground the protective earth (GR) terminal of the Power Supply Units on the CPU Rack and the CJ-series Expansion Racks to a resistance of 100 Ω or less. The following example shows connecting SD-SG, RD-SG, RS-SG, and CS-SG for Serial Communications Mode using a twistedpair cable using the peripheral bus. SG signal line CPU Unit

External device

Pin Signal No. name 2 SD 3 RD 4 RS 5 CS 9 SG Hood FG 1 FG

Signal name RD SD CS RS SG FG

SG signal lines bundled together Aluminum foil

XM2S-0911-E

Shield

Note The hood (FG) is internally connected to the protective earth (GR) terminal on the Power Supply Unit through the CPU Rack. FG can thus be connected by connecting the protective earth (GR) terminal on the Power Supply Unit. The hood (FG) is also electrically connected to pin 1 (FG), but the connection resistance between the shield and the FG is smaller for the hood. To reduce contact resistance between the hood (FG) and the FG, connect the shield both to the hood (FG) and to pin 1 (FG). Example for CJ2H CPU Unit

Example for CJ2M CPU Unit

Power Supply Unit

Power Supply Unit

CPU Unit

Pulse I/O Module

PA205R POWER

L1

AC100-240V INPUT L2/N

GR

GR

COMM

RUN OUTPUT AC240V DC24V

Ground to 100 Ω or less

A-132

Hood and GR connected internally. The hood will be grounded if the GR terminal is grounded.

Ground to 100 Ω or less

CJ2 CPU Unit Hardware User’s Manual

Page 395

Appendices z Applicable Connector and Recommended Cables Use the following connectors and cables when making an RS-232C cable to connect to the RS-232C port. Computer (9-pin male connector)

IBM PC/AT or compatible

CPU Unit

Plug: XM2D-0901 (9-pin female)

RS-232C port

Hood: XM2S-0913 Recommended cable Hood: XM2S-0911-E

Plug: XM2A-0901

Provided with the CPU Unit

Applicable Connectors CPU Unit Connector Item

Model

Specifications

Plug

XM2A-0901

9-pin male

Hood

XM2S-0911-E

9-pin, millimeter screws, static-resistant

Used together (One of each provided with CPU Unit.) A-4 Connecting to a Serial Port on the CPU Unit

Personal Computer Connector for IBM PC/AT Computer (9-pin Male Connector) Item

Model

Specifications

Plug

XM2A-0901

9-pin female

Hood

XM2S-0913

9-pin, inch screws, staticresistant

Used together

Recommended Cables We recommend using the following shielded twisted-pair cables to provide noise resistance. Fujikura Ltd.:

UL2464 AWG28 × 5P IFS-RVV-SB (UL product) AWG 28 × 5P IFVV-SB (non-UL product)

Hitachi Cable, Ltd.: UL2464-SB(MA) 5P × 28AWG (7/0.127) (UL product) CO-MA-VV-SB 5P × 28AWG (7/0.127) (non-UL product)

CJ2 CPU Unit Hardware User’s Manual

A-133

A-4-3 Applicable Connectors and Recommended Cables

Use the special cables provided from OMRON for all connections whenever possible. If cables are produced in-house, be sure they are wired correctly. External devices and the CPU Unit may be damaged if general purpose (e.g., computer to modem) cables are used or if wiring is not correct.

App

Precautions for Correct Use

Page 396

Appendices z Wiring Connectors Use the following procedures to wire connectors. Preparing the Cable Lengths for steps in the procedure are provided in the diagrams. Connecting the Shield Line to the Hood (FG)

1 Cut the cable to the required length, leaving leeway for wiring and laying the cables. 2 Use a razor blade to cut away the sheath, being careful not to damage the braiding. 40 mm (RS-232C)

3 Use scissors to cut away all but 10 mm of the exposed braiding. 10 mm

4 Use wire strippers to remove the insulation from the end of each wire. 5 mm

5 Fold the braiding back over the end of the sheath. 6 Wrap aluminum foil tape over the top of the braiding for one and a half turns. Aluminum foil tape z Not Connecting the Shield to the Hood (FG)

1 Cut the cable to the required length, leaving leeway for wiring and laying the cables. 2 Use a razor blade to cut away the sheath, being careful not to damage the braiding. 40 mm (RS-232C)

3 Use scissors to cut away the exposed braiding. 10 mm

A-134

CJ2 CPU Unit Hardware User’s Manual

Page 397

Appendices

4 Use wire strippers to remove the insulation from the end of each wire. 5 mm

5 Wrap electrician's tape over the top and end of the cut sheath. Electrician's tape z Soldering

1 Place heat-shrinking tubes over all wires. 2 Pre-solder all wires and connector terminals. 3 Solder the wires. A-4 Connecting to a Serial Port on the CPU Unit

1 mm

Soldering iron

Heat-shrinking tube (inner dia. 1.5, l = 10)

4 Move the heat-shrinking tubes onto the soldered area and shrink them into place.

App

Heat-shrinking tube A-4-3 Applicable Connectors and Recommended Cables z Assembling the Hood Assemble the connector hood as shown.

FG Connection

No FG Connection Aluminum foil tape

Ground plate

CJ2 CPU Unit Hardware User’s Manual

A-135

Page 398

Appendices z Connections to the CPU Unit • Always turn OFF the power supply to the PLC before connecting or disconnecting communications cables. • Tighten the communications connector attachment screws to 0.4 N·m.

Example of Recommended RS-422A/485 Wiring We recommend using the following wiring for RS-422A/485 to ensure transmission quality.

1 Use shielded twisted-pair cable for communications cables. • Recommended RS-422A/485 Cable Model CO-HC-ESV-3P × 7/0.2

Manufacturer Hirakawa Hewtech Corp.

2 Connect the shield on the communications cable to the FG terminal on the RS-422A/485 Option Board. Also, ground the protective earth (GR) terminal on the CPU Unit to a resistance of 100 Ω or less. Precautions for Correct Use Using the CP1W-CIF11 RS-422A/485 Option Board (Not Isolated) Use the CP1W-CIF11 only when there is no difference in electrical potential between devices. Connect the shield on the communications cable at both ends to the FG terminals on the RS422A/485 terminal blocks to ground it. Do not allow the communications distance to exceed 50 m. Using the CP1W-CIF12 RS-422A/485 Option Board (Isolated) Use the CP1W-CIF12 if there is a difference in electrical potential between devices or for longdistance communications (500 m max.). Connect the shield on the communications cable only at the Option Board to ground it. If the shield is connected at both ends of the cable when there is a difference in electrical potential, the devices may be damaged.

A-136

CJ2 CPU Unit Hardware User’s Manual

Page 399

Appendices z Connection Examples Examples for 2-wire and 4-wire Transmission Paths The transmission path for 2-wire and 4-wire connections are different, as shown below. Example for 4-wire Connections

Example for 2-wire Connections

2-wire/4-wire switch (DPDT)

2-wire/4-wire switch (DPDT)

Other Unit

Other Unit

Option Board

Option Board

Other Unit Other Unit NC (Non Connection)

Precautions for Correct Use • All nodes must use either 2-wire connections or 4-wire connections. • Do not use 4-wire connections with the switch on the Board set for 2-wire connections. A-4 Connecting to a Serial Port on the CPU Unit

Wiring Example for 1:1 Connections • Example for 2-wire Connections CJ2M CPU Unit RS-422A/485 Option Board

External device

Signal name

Signal name

SDA− SDB+ RDA− RDB+ FG

A(−) B(+)

Pin No. 3 4 1 2 5

FG

Shield

• Example for 4-wire Connections CJ2M CPU Unit RS-422A/485 Option Board

External device

Signal name RDA RDB SDA SDB FG

Signal name SDA− SDB+ RDA− RDB+ FG

App

Pin No. 3 4 1 2 5

Shield

CJ2M CPU Unit Option Board

Pin No.

Signal name

3 4 1 2 5

SDA− SDB+ RDA− RDB+ FG

B500-AL001 RS-422

Pin Signal No. name

6 1 9 5 7

External device

Signal Pin name No.

RDA RDA RS-422 RDB RDB Interface SDA SDA SDB SDB FG FG

A-4-3 Applicable Connectors and Recommended Cables

• Using a B500-AL001 Link Adapter RS-422

6 1 9 5 7

Signal name

RDA RDB SDA SDB FG

Signal name RDA RDB SDA SDB FG 1 9 5 7 Pin No. 6 External device

RS-422

Signal name

RDA RDB SDA SDB FG

CJ2 CPU Unit Hardware User’s Manual

A-137

Page 400

Appendices

Noise Countermeasures for External Wiring Take the following points into account when externally wiring communications cables. • When multi-conductor signal cable is being used, do not combine I/O wires and other control wires in the same cable. • If wiring racks are parallel, allow at least 300 mm between them. Low-power cables Communications cables 300 mm min. Control cables SYSMAC power supply lines and general control circuit lines Power cables

300 mm min.

Power lines

Ground to less than 100 Ω

• If the I/O wiring and power cables must be placed in the same duct, they must be shielded from each other using grounded steel sheet metal plates. Communications cables

SYSMAC power supply lines and general control circuit lines Power lines Steel sheet metal plates

200 mm min.

Ground to less than 100 Ω

A-138

CJ2 CPU Unit Hardware User’s Manual

Page 401

Appendices

A-5

Installing the USB Driver The USB driver must be installed in the computer to connect the PLC to the computer using the USB port.

Procedure for Installing the USB Driver This section describes the procedure for connecting a computer to the peripheral (USB) port on the CJ2 CPU Unit for the first time. This example assumes that the Support Software is already installed. The installation procedure given here is for CX-One version 4.0 (CX-Programmer version 9.1).

z Windows 2000, Vista, or Windows 7

1 Turn ON the power supply to the PLC and connect the peripheral USB port on the PLC to the personal computer using a USB cable. The USB driver will be automatically installed when the cable is connected.

Note If the software is not automatically installed, refer to Installing a Specified USB Driver later in this section.

1 Turn ON the power supply to the CJ2 PLC, and connect a USB cable between the USB port on the computer and the peripheral (USB) port on the CJ2 CPU Unit. After the cable has been connected, the computer will automatically recognize the device and the following message will be displayed.

App

2 The following dialog box will be displayed. Select one of the options and click the Next Button.

A-5 Installing the USB Driver z Windows XP

A-4-3 Applicable Connectors and Recommended Cables

CJ2 CPU Unit Hardware User’s Manual

A-139

Page 402

Appendices

3 The following dialog box will be displayed. Select the Install the software automatically (Recommended) Option and click the Next Button.

Note 1 If the software cannot be installed automatically, refer to Installing a Specified USB Driver later in this section. 2 If the installation media is not inserted or the USB device driver is installed for another port, a Driver List Dialog Box will be displayed. Make sure that the newest driver is selected and click the Next Button.

4 Ignore the following dialog box if it is displayed and click the Continue Anyway Button.

A-140

CJ2 CPU Unit Hardware User’s Manual