The text of a manual · part 47 of 48

SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Appendices, pages 413 to 418

Pages 413 to 418 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 413

Appendices

A-6-2

Load Short-circuit Protection for CJ1WOD204/OD212/OD232/MD232

Normal Operation OUT: OUTPUT instruction IOUT: Output current

ON

OUT

OFF

ERR: Alarm output, ERR indicator Ilim: Detection current

ON

IOUT

Tj: Junction temperature of transistor Tstd: Thermal shutdown temperature Tr: Reset temperature

OFF

ON

ERR

OFF

Operation for Overload or Short Circuit ON

OUT

OFF

ON

IOUT

Tj =Tstd Tj =Tr Ilim

OFF

ON

ERR

OFF

CJ2 CPU Unit Hardware User’s Manual

A-151

A-6-2 Load Short-circuit Protection for CJ1WOD204/OD212/OD232/MD232

These Units are provided with short-circuit protection, these are for protecting internal circuits against momentary short-circuiting in the load. As shown in Figure 2, the short-circuit protection is automatically released when the Tj equals to Tr. Therefore, unless the cause of short-circuit is removed, ON/OFF operations will be repeated in the output. Leaving short-circuits for any length of time will cause internal temperature rise, deterioration of elements, discoloration of the case or PCBs, etc. Therefore, observe the following restrictions.

App

Operating Restrictions for the CJ1W-OD204/OD212/OD232/MD232

A-6 Load Short-circuit Protection and Line Disconnection Detection for Basic I/O Units

As shown below, normally when the output bit turns ON (OUT), the transistor will turn ON and then output current (Iout) will flow. If the output (Iout) is overloaded or short-circuited exceeding the detection current (Ilim), the output current (Iout) will be limited as shown in second figure below. When the junction temperature (Tj) of the output transistor reaches the thermal shutdown temperature (Tstd), the output will turn OFF to protect the transistor from being damaged, and the alarm output bit will turn ON to light the ERR indicator. When the junction temperature (Tj) of the transistor drops down to the reset temperature (Tr), the ERR indicator will be automatically reset and the output current will start flowing.

Page 414

Appendices z Restrictions If a short-circuit occurs in an external load, immediately turn OFF the corresponding output and remove the cause. An alarm output bit that corresponds to the external load output number is turned ON. There is an alarm output bit for every common. When an alarm output bit turns ON, use a self-holding bit for the alarm in the user program and turn OFF the corresponding output. The alarm output bit is allocated in the Basic I/O Unit Information Area (A050 to A069) for every Unit mounting slot. The following table shows the correspondence between output bits and bits in the Basic I/O Unit Information Area. Output bit CJ1W-OD204 CJ1W-OD212 m 0 to 7

Mounted in even slot

0

Mounted in odd slot

8

8 to 15 m+1 m+2 m+3

0 to 15

0 to 15

0 to 15

Mounted in even slot

0

Mounted in odd slot

8

CJ1W-MD232 Mounted in even slot

0

Mounted in odd slot

8

Mounted in even slot

0

1

Mounted in odd slot

8

9

CJ1W-OD232

For example, when the CJ1W-OD212 is mounted in slot 0 on Rack 0, A50.00 will turn ON if the output 8 is short-circuited. When the CJ1W-OD232 is mounted in slot 1 of Rack 0, A50.09 will turn ON if the output m+1 is short-circuited.

z Programming Example In this example, CJ1W-OD212 is mounted in slot 0 of the Rack 0. This example shows how to turn OFF output bits CIO 0.00 to CIO 0.07 immediately if the alarm output bit A50.00 turns ON and how to keep the output bits OFF until the cause is removed and the bit is reset using work bit W0.01. A50.00

W0.01 W0.00

W0.00

A

W0.00 0.00

B

W0.00 0.01

H

W0.00 0.07

A-152

CJ2 CPU Unit Hardware User’s Manual

Page 415

Appendices

A-7

Relay Output Noise Reduction Methods The CJ-series PLCs conforms to the Common Emission Standards (EN61000-6-4) of the EMC Directives. However, noise generated by relay output switching may not satisfy these Standards. In such a case, a noise filter must be connected to the load side or other appropriate countermeasures must be provided external to the PLC. Countermeasures taken to satisfy the standards vary depending on the devices on the load side, wiring, configuration of machines, etc. Following are examples of countermeasures for reducing the generated noise.

Countermeasures (Refer to EN61000-6-4 for more details.) Countermeasures are not required if the frequency of load switching for the whole system with the PLC included is less than 5 times per minute.

Countermeasure Examples When switching an inductive load, connect an surge protector, diodes, etc., in parallel with the load or contact as shown below. Current

Circuit

AC Yes

C Power supply

R

Inductive load

CR method

DC Yes

If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset.

The capacitance of the capacitor must be 1 to 0.5 µF per contact current of 1 A and resistance of the resistor must be 0.5 to 1 Ω per contact voltage of 1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again.

If the supply voltage is 24 or 48 V, insert the surge protector in parallel with the load. If the supply voltage is 100 to 200 V, insert the surge protector between the contacts.

The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity.

CJ2 CPU Unit Hardware User’s Manual

A-153

A-6-2 Load Short-circuit Protection for CJ1WOD204/OD212/OD232/MD232

Required element

App

Characteristic

A-7 Relay Output Noise Reduction Methods

Countermeasures are required if the frequency of load switching for the whole system with the PLC included is more than 5 times per minute.

Page 416

Appendices

Current

Circuit

AC No

Power supply

Yes

Inductive load

Diode method

Characteristic

Required element

The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load.

The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value. The forward current of the diode must be the same as or larger than the load current.

DC

This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method. Yes

Yes

Inductive load

Varistor method

Power supply

The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset.

The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the surge protector is applied to electronic circuits with low circuit voltages. ---

If the supply voltage is 24 or 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to 200 V, insert the varistor between the contacts.

When switching a load with a high inrush current such as an incandescent lamp, suppress the inrush current as shown below. Countermeasure 1

Countermeasure 2 R

OUT

OUT R

COM Providing a dark current of approx. one-third of the rated value through an incandescent lamp

A-154

COM Providing a limiting resistor

CJ2 CPU Unit Hardware User’s Manual

Page 417

Appendices

A-8

Functions Supported for Unit Versions

A-8-1

CJ2H CPU Units

Functions Supported for Unit Version 1.3 or Later CX-Programmer version 9.1 or higher must be used to enable using the functions added for unit version 1.3. Units

CJ2H CPU Units

Models

CJ2H-CPU6@-EIP and CJ2H-CPU6@ Unit version

Unit version 1.2

Unit version 1.1

Unit version 1.0

Special instructions for certain Special I/O Units

CJ1W-NC281/NC481/NC881 Position Control Units: PCU HIGH-SPEED POSITIONING (NCDMV(218))

Supported.

Not supported.

Not supported.

Not supported.

CJ1W-NC281/NC481/NC881 Position Control Units: PCU POSITIONING TRIGGER (NCDTR(219))

Supported.

Not supported.

Not supported.

Not supported.

New special instructions

SIGNED AREA RANGE COMPARE: ZCPS(088)

Supported.

Not supported.

Not supported.

Not supported.

DOUBLE SIGNED AREA RANGE COMPARE: ZCPSL(116)

Supported.

Not supported.

Not supported.

Not supported.

Unit Version 1.2 or Later CX-Programmer version 8.3 or higher must be used to enable using the functions added for unit version 1.2. CJ2H CPU Units

Model

CJ2H-CPU6@-EIP CJ2H-CPU6@

Unit version

Supported.

Unit versions earlier than 1.2 Not supported.

Note User programs that use functions of CJ2H CPU Units with unit version 1.2 or later cannot be used with CJ2H CPU Units with unit version 1.1 or earlier. If an attempt is made to transfer a program that uses any of these functions from the CX-Programmer to a CPU Unit with unit version 1.1 or earlier, an error will be displayed and it will not be possible to download to the CPU Unit.

CJ2 CPU Unit Hardware User’s Manual

A-155

A-8-1 CJ2H CPU Units

EM Area Force-setting/resetting

Unit version 1.2 or later

App

Unit

A-8 Functions Supported for Unit Versions

Unit version 1.3 or later

Function

Page 418

Appendices

Functions Supported for Unit Version 1.1 or Later CX-Programmer version 8.1* or higher must be used to enable using the functions added for unit version 1.1. Units

CJ2H CPU Unit

Models

CJ2H-CPU6@-EIP and CJ2H-CPU6@ Unit version

Function

Unit version 1.1

Unit version 1.0

Supported.

Not supported.

Changing the minimum cycle time setting during operation

Supported.

Not supported.

Synchronous unit operation

Supported.

Not supported.

Addition of immediate refreshing instructions for certain Special I/O Units

Supported.

Not supported.

Supported.

Not supported.

High-speed interrupt function Reduced overhead time for interrupt tasks Minimum interval for scheduled interrupt task execution: 0.1 ms

CJ1W-AD042 High-speed Analog Input Unit: ANALOG INPUT DIRECT CONVERSION (AIDC(216)) CJ1W-DA042V High-speed Analog Output Unit: ANALOG OUTPUT DIRECT CONVERSION (AODC(217)) High-speed Serial Communications Units CJ1W-SCU22/SCU32/SCU42 High-speed Serial Communications Units: DIRECT RECEIVE VIA SERIAL COMMUNICATIONS UNIT (DRXDU(261)) and DIRECT TRANSMIT VIA SERIAL COMMUNICATIONS UNIT (DTXDU(262)

* CX-Programmer version 8.02 or higher is required to use the high-speed interrupt function and the function to change the minimum cycle time setting during operation. Note User programs that use functions of CJ2H CPU Units with unit version 1.1 or later cannot be used with CJ2H CPU Units with unit version 1.0 or earlier. If an attempt is made to transfer a program that uses any of these functions from the CX-Programmer to a CPU Unit with unit version 1.0, an error will be displayed and it will not be possible to download to the CPU Unit. If a program file (extension: .OBJ) that uses any of these functions is transferred to a CPU Unit with unit version 1.0, a program error will occur when operation starts or when the function starts and operation of the CPU Unit will stop.

A-8-2

CJ2M CPU Units

Functions Supported for Unit Version 2.0 or Later CX-Programmer version 9.12 or higher must be used to enable using the functions added for unit version 2.0. Unit

CJ2M CPU Unit CJ2M-CPU@@

Model Unit version Function Pulse I/O

A-156

Unit version 2.0 or later Supported.

Unit versions earlier than 2.0 Not supported.

CJ2 CPU Unit Hardware User’s Manual