Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 33 of 60

SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual: SECTION 5 Instruction Set, pages 299 to 308

Pages 299 to 308 of 520, from SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron CQM1-CPU21

Page 299

Section 5-20

BCD Calculation Instructions Address

Instruction

00000 00001 00002 00003

LD OUT CLC(41) @SUB(31)

Operands 00002 0

TR

DM HR 00004 00005 00006

00007 00008 00009 00010 00011

AND CLC(41) @SUB(31)

LD LD OR AND LD OUT

# HR HR TR

010 0100 10 25504

HR

0000 10 10 0 25504 1100

HR

1100

The first and second subtractions for this diagram are shown below using example data for 010 and DM 0100. Note The actual SUB(31) operation involves subtracting Su and CY from 10,000 plus Mi. For positive results the leftmost digit is truncated. For negative results the 10s complement is obtained. The procedure for establishing the correct answer is given below. First Subtraction IR 010 1029 DM 0100 – 3452 CY –0 HR 10 7577 (1029 + (10000 – 3452)) CY 1 (negative result) Second Subtraction 0000 HR 10 –7577 CY –0 HR 10 2423 (0000 + (10000 – 7577)) CY 1 (negative result) In the above case, the program would turn ON HR 1100 to indicate that the value held in HR 10 is negative.

5-20-5 BCD MULTIPLY – MUL(32) Operand Data Areas Md: Multiplicand (BCD)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # MUL(32)

@MUL(32)

Md

Md

Mr

Mr

R

R

Mr: Multiplier (BCD)

Limitations

IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

DM 6143 to DM 6655 cannot be used for R.

281

Page 300

Section 5-20

BCD Calculation Instructions Description

When the execution condition is OFF, MUL(32) is not executed. When the execution condition is ON, MUL(32) multiplies Md by the content of Mr, and places the result In R and R+1. Md

X R +1

Example

Mr

R

When IR 00000 is ON with the following program, the contents of IR 013 and DM 0005 are multiplied and the result is placed in HR 07 and HR 08. Example data and calculations are shown below the program.

00000 MUL(32) 013 DM 0005

Address

Instruction

00000 00001

LD MUL(32)

HR 07

0

Flags

00000

DM HR

3

Md: IR 013 3 5 6

X

0

Mr: DM 0005 0 2 5

R+1: HR 08 0 0 8

3

R: HR 07 9 0

ER:

Operands

013 0005 07

0

Md and/or Mr is not BCD. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

CY:

ON when there is a carry in the result.

EQ:

ON when the result is 0.

5-20-6 BCD DIVIDE – DIV(33) Operand Data Areas Ladder Symbol

Dd: Dividend word (BCD) IR, SR, AR, DM, HR, TC, LR, #

DIV(33) Dr: Divisor word (BCD) Dd Dr R

Limitations

282

IR, SR, AR, DM, HR, TC, LR, # R: First result word (BCD) IR, SR, AR, DM, HR, LR

R and R+1 must be in the same data area. DM 6143 to DM 6655 cannot be used for R.

Page 301

Section 5-20

BCD Calculation Instructions Description

When the execution condition is OFF, DIV(33) is not executed and the program moves to the next instruction. When the execution condition is ON, Dd is divided by Dr and the result is placed in R and R + 1: the quotient in R and the remainder in R + 1. Remainder

Quotient

R+1

R

Dr

Flags

ER:

Dd

Dd or Dr is not in BCD. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ: Example

ON when the result is 0.

When IR 00000 is ON with the following program, the content of IR 216 is divided by the content of HR 09 and the result is placed in DM 0017 and DM 0018. Example data and calculations are shown below the program.

00000 DIV(33) 216

Address

Instruction

00000 00001

LD DIV(33)

Operands 00000

HR 09 DM 0017

1

0

Quotient

Remainder

R: DM 0017 1 5 0

R + 1: DM 0018 0 0 0 2

Dd: HR 09 0 0 3

3

HR DM

216 09 0017

Dd: IR 216 4 5 2

5-20-7 DOUBLE BCD ADD – ADDL(54) Operand Data Areas Au: First augend word (BCD)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR ADDL(54)

@ADDL(54)

Au

Au

Ad

Ad

R

R

Ad: First addend word (BCD)

Limitations

IR, SR, AR, DM, HR, TC, LR R: First result word IR, SR, AR, DM, HR, LR

DM 6143 to DM 6655 cannot be used for R.

283

Page 302

Section 5-20

BCD Calculation Instructions Description

When the execution condition is OFF, ADDL(54) is not executed. When the execution condition is ON, ADDL(54) adds the contents of CY to the 8-digit value in Au and Au+1 to the 8-digit value in Ad and Ad+1, and places the result in R and R+1. CY will be set if the result is greater than 99999999.

Au + 1

Au

Ad + 1

Ad

+ CY

Flags

ER:

CY R+1

R

Au and/or Ad is not BCD. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

Example

CY:

ON when there is a carry in the result.

EQ:

ON when the result is 0.

When 00000 is ON, the following program section adds two 12-digit numbers, the first contained in LR 00 through LR 02 and the second in DM 0010 through DM 0012. The result is placed in HR 10 through HR 13. The rightmost 8 digits of the two numbers are added using ADDL(54), i.e., the contents of LR 00 and LR 01 are added to DM 0010 and DM 0011 and the results is placed in HR 10 and HR 11. The second addition adds the leftmost 4 digits of each number using ADD(30), and includes any carry from the first addition. The last instruction, ADB(50) (see 5-21-1 BINARY ADD – ADB(50)) adds two allzero constants to place any carry from the second addition into HR 13.

00000

Address

Instruction

00000 00001 00002

LD CLC(41) @ADDL(54)

Operands

CLC(41) @ADDL(54) LR 00 DM 0010 HR 10 @ADD(30)

00003

DM 0012 HR 12

#0000 #0000 HR 13

284

00004

LR DM HR

00 0010 10

LR DM HR

02 0012 12

# # HR

0000 0000 13

@ADD(30)

LR 02

@ADB(50)

00000

@ADB(50)

Page 303

Section 5-20

BCD Calculation Instructions

5-20-8 DOUBLE BCD SUBTRACT – SUBL(55) Operand Data Areas Mi: First minuend word (BCD)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # SUBL(55)

@SUBL(55)

Mi

Mi

Su

Su

R

R

Su: First subtrahend word (BCD) IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR, LR

Limitations

DM 6143 to DM 6655 cannot be used for R.

Description

When the execution condition is OFF, SUBL(55) is not executed. When the execution condition is ON, SUBL(55) subtracts CY and the 8-digit contents of Su and Su+1 from the 8-digit value in Mi and Mi+1, and places the result in R and R+1. If the result is negative, CY is set and the 10’s complement of the actual result is placed in R. To convert the 10’s complement to the true result, subtract the content of R from zero. Since an 8-digit constant cannot be directly entered, use the BSET(71) instruction (see 5-17-4 BLOCK SET – BSET(71)) to create an 8-digit constant. Mi + 1

Mi

Su + 1

Su

– CY

Flags

ER:

CY

R+1

R

Mi, M+1,Su, or Su+1 are not BCD. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

Example

CY:

ON when the result is negative, i.e., when Mi is less than Su.

EQ:

ON when the result is 0.

The following example works much like that for single-word subtraction. In this example, however, BSET(71) is required to clear the content of DM 0000 and

285

Page 304

Section 5-20

BCD Calculation Instructions

DM 0001 so that a negative result can be subtracted from 0 (inputting an 8-digit constant is not possible). TR 0 00003 CLC(41)

First subtraction

@SUBL(55) HR 00 120 DM 0100 25504 @BSET(71) #0000 DM 0000 DM 0001 CLC(41)

Second subtraction

@SUBL(55) DM 0000 DM 0100 DM 0100 25504 HR 0100

HR 0100

Turned ON to indicate negative result.

Address

Instruction

Operands

00000 00001 00002 00003

LD OUT CLC(41) @SUBL(55)

TR

HR DM 00004 00005

AND @BSET(71) # DM DM

Address

00003 0

Instruction

00006 00007

00 120 0100 25504

00008 00009 00010 00011 00012

0000 0000 0001

Operands

CLC(41) @SUBL(55)

LD LD OR AND LD OUT

DM DM DM TR HR

0000 0100 0100 0 25504 0100

HR

0100

5-20-9 DOUBLE BCD MULTIPLY – MULL(56) Operand Data Areas Md: First multiplicand word (BCD)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR MULL(56)

@MULL(56)

Md

Md

Mr

Mr

R

R

Mr: First multiplier word (BCD)

286

IR, SR, AR, DM, HR, TC, LR R: First result word IR, SR, AR, DM, HR LR

Page 305

Section 5-20

BCD Calculation Instructions Limitations

DM 6141 to DM 6655 cannot be used for R.

Description

When the execution condition is OFF, MULL(56) is not executed. When the execution condition is ON, MULL(56) multiplies the eight-digit content of Md and Md+1 by the content of Mr and Mr+1, and places the result in R to R+3.

x R+3

Flags

ER:

R+2

Md + 1

Md

Mr + 1

Mr

R+1

R

Md, Md+1,Mr, or Mr+1 is not BCD. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

CY:

ON when there is a carry in the result.

EQ:

ON when the result is 0.

5-20-10 DOUBLE BCD DIVIDE – DIVL(57) Operand Data Areas Dd: First dividend word (BCD)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR DIVL(57)

@DIVL(57)

Dd

Dd

Dr

Dr

R

R

Dr: First divisor word (BCD) IR, SR, AR, DM, HR, TC, LR R: First result word IR, SR, AR, DM, HR LR

Limitations

DM 6141 to DM 6655 cannot be used for R.

Description

When the execution condition is OFF, DIVL(57) is not executed. When the execution condition is ON, DIVL(57) the eight-digit content of Dd and D+1 is divided by the content of Dr and Dr+1 and the result is placed in R to R+3: the quotient in R and R+1, the remainder in R+2 and R+3. Remainder R+3

Dr+1

Flags

ER:

R+2

Dr

Quotient R+1

R

Dd+1

Dd

Dr and Dr+1 contain 0. Dd, Dd+1, Dr, or Dr+1 is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)

EQ:

ON when the result is 0.

287

Page 306

Section 5-20

BCD Calculation Instructions

5-20-11 SQUARE ROOT – ROOT(72) Ladder Symbols

Operand Data Areas Sq: First source word (BCD)

ROOT(72)

@ROOT(72)

Sq

Sq

R

R

IR, SR, AR, DM, HR, TC, LR R: Result word

Limitations

IR, SR, AR, DM, HR, LR,

This instruction is available in the CQM1 only. DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, ROOT(72) is not executed. When the execution condition is ON, ROOT(72) computes the square root of the eight-digit content of Sq and Sq+1 and places the result in R. The fractional portion is truncated.

Description

R

Sq+1

Flags

ER:

Sq

Sq is not BCD. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ: Example

ON when the result is 0.

The following example shows how to take the square root of an eight digit number. The result is a four-digit number, with the remainder rounded off. and then round the result. In this example, √63250561 = 7953.0221..., which is rounded off to 7953.

00000 @ROOT(72) DM 0000 001

DM 0001 6 3 2 5

0

DM 0000 5 6 1

63,250,561 = 7953.0221 (The remainder is rounded off.) 7 9

288

001 5

3

Address

Instruction

00000 00001

LD @ROOT(72)

Operands 00000 DM

0000 001

Page 307

Section 5-21

Binary Calculation Instructions

5-21 Binary Calculation Instructions 5-21-1 BINARY ADD – ADB(50) Operand Data Areas Au: Augend word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # ADB(50)

@ADB(50)

Au

Au

Ad

Ad

R

R

Ad: Addend word (binary) IR, SR, AR, DM, HR, TC, LR, # R: Result word IR, SR, AR, DM, HR, LR

Limitations

DM 6144 to DM 6655 cannot be used for R.

Description

When the execution condition is OFF, ADB(50) is not executed. When the execution condition is ON, ADB(50) adds the contents of Au, Ad, and CY, and places the result in R. CY will be set if the result is greater than FFFF.

Au + Ad + CY

CY

R

ADB(50) can also be used to add signed binary data. With the CPM1A, and SRM1, the underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Flags

ER: CY: EQ: OF: UF:

Example

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is greater than FFFF. ON when the result is 0. ON when the result exceeds +32,767 (7FFF). only) ON when the result is below –32,768 (8000). only)

The following example shows a four-digit addition with CY used to place either #0000 or #0001 into R+1 to ensure that any carry is preserved. TR 0

00000 CLC(41)

ADB(50)

Address

Instruction

00000 00001 00002 00003

LD OUT CLC(41) ADB(50)

Operands TR

010 DM 0100 HR 10

=R

25504

00004 00005

MOV(21) #0000 HR 11

DM HR AND NOT MOV(21)

= R+1

25504 MOV(21) #0001 HR 11

= R+1

00006 00007 00008

LD AND MOV(21)

00000 0

010 0100 10 25504

# HR TR

0000 11 0 25504

# HR

00001 11

289

Page 308

Section 5-21

Binary Calculation Instructions

In the case below, A6E2 + 80C5 = 127A7. The result is a 5-digit number, so CY (SR 25504) = 1, and the content of R + 1 becomes #0001.

0

A

Au: IR 010 6 E 2

+

8

Ad: DM 0100 0 C 5

R+1: HR 11 0 0 1

2

R: HR 10 7 A

7

Note For signed binary calculations, the status of the UF and OF flags indicate whether the result has exceeded the signed binary data range (–32,768 (8000) to +32,767 (7FFF)). only)

5-21-2 BINARY SUBTRACT – SBB(51) Operand Data Areas Mi: Minuend word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # SBB(51)

@SBB(51)

Mi

Mi

Su

Su

R

R

Su: Subtrahend word (binary) IR, SR, AR, DM, HR, TC, LR, # R: Result word IR, SR, AR, DM, HR, LR

Limitations

DM 6144 to DM 6655 cannot be used for R.

Description

When the execution condition is OFF, SBB(51) is not executed. When the execution condition is ON, SBB(51) subtracts the contents of Su and CY from Mi and places the result in R. If the result is negative, CY is set and the 2’s complement of the actual result is placed in R.

Mi – Su – CY

CY

R

SBB(51) can also be used to subtract signed binary data. With CPM1A, and SRM1, the underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Flags

Example

290

ER:

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

CY:

ON when the result is negative, i.e., when Mi is less than Su plus CY.

EQ:

ON when the result is 0.

OF:

ON when the result exceeds +32,767 (7FFF). only)

UF:

ON when the result is below –32,768 (8000). only)

The following example shows a four-digit subtraction. When IR 00001 is ON, the content of LR 00 and CY are subtracted from the content of IR 002 and the result is written to HR 01.