SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual: SECTION 5 Instruction Set, pages 309 to 318

Pages 309 to 318 of 520, from SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron CQM1-CPU21

Page 309

Section 5-21

Binary Calculation Instructions

CY is turned ON if the result is negative. If normal data is being used, a negative result (signed binary) must be converted to normal data using NEG(––). Refer to 5-19-17 2’s COMPLEMENT – NEG(––) for details.

00001 CLC(41)

SBB(51)

Address

Instruction

00000 00001 00002 00003

LD OUT CLC(41) SBB(51)

Operands TR

00001 1

LR HR

002 00 01

002 LR00 HR 01

In the case below, the content of LR 00 (#7A03) and CY are subtracted from IR 002 (#F8C5). Since the result is positive, CY is 0. If the result had been negative, CY would have been set to 1. For normal (unsigned) data, the result would have to be converted to its 2’s complement.

F

Mi: IR 002 8 C 5

–

7

Su: LR 00 A 0 3

–

0

7

0

0

0

R: HR 01 E C

2

CY = 0 (from CLC(41))

Note For signed binary calculations, the status of the UF and OF flags indicate whether the result has exceeded the signed binary data range (–32,768 (8000) to +32,767 (7FFF)). only)

5-21-3 BINARY MULTIPLY – MLB(52) Operand Data Areas Md: Multiplicand word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # MLB(52)

@MLB(52)

Md

Md

Mr

Mr

R

R

Mr: Multiplier word (binary)

Limitations

IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

DM 6143 to DM 6655 cannot be used for R. MLB(52) cannot be used to multiply signed binary data. In CQM1 PCs, MBS(––) can be used. Refer to 5-21-7 SIGNED BINARY MULTIPLY – MBS(––).

291

Page 310

Section 5-21

Binary Calculation Instructions Description

When the execution condition is OFF, MLB(52) is not executed. When the execution condition is ON, MLB(52) multiplies the content of Md by the contents of Mr, places the rightmost four digits of the result in R, and places the leftmost four digits in R+1. Md

X

Mr

R +1

Flags

R

ER:

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ:

ON when the result is 0.

5-21-4 BINARY DIVIDE – DVB(53) Operand Data Areas Dd: Dividend word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # DVB(53)

@DVB(53)

Dd

Dd

Dr

Dr

R

R

Dr: Divisor word (binary)

Limitations

IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

DM 6143 to DM 6655 cannot be used for R. DVB(53) cannot be used to divide signed binary data. In CQM1 PCs, DBS(––) can be used. Refer to 5-21-9 SIGNED BINARY DIVIDE – DBS(––) for details.

Description

When the execution condition is OFF, DVB(53) is not executed. When the execution condition is ON, DVB(53) divides the content of Dd by the content of Dr and the result is placed in R and R+1: the quotient in R, the remainder in R+1. Quotient R

Dr

Flags

ER:

Remainder R+1

Dd

Dr contains 0. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ:

292

ON when the result is 0.

Page 311

Section 5-21

Binary Calculation Instructions

5-21-5 DOUBLE BINARY ADD – ADBL(––) Operand Data Areas Au: First augend word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # ADBL(––)

@ADBL(––)

Au

Au

Ad

Ad

R

R

Ad: First addend word (binary) IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR, LR

Limitations

This instruction is available in the only. Au and Au+1 must be in the same data area, as must Ad and Ad+1, and R and R+1. DM 6142 to DM 6655 cannot be used for R.

Description

When the execution condition is OFF, ADBL(––) is not executed. When the execution condition is ON, ADBL(––)) adds the eight-digit contents of Au+1 and Au, the eight-digit contents of Ad+1 and Ad, and CY, and places the result in R. CY will be set if the result is greater than FFFF FFFF. Au + 1

Au

Ad + 1

Ad

+ CY

CY

R+1

R

ADBL(––) can also be used to add signed binary data. The underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 32-bit signed binary data range. Flags

ER:

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

CY:

ON when the result is greater than FFFF FFFF.

EQ:

ON when the result is 0.

OF:

ON when the result exceeds +2,147,483,647 (7FFF FFFF).

UF:

ON when the result is below –2,147,483,648 (8000 0000).

293

Page 312

Section 5-21

Binary Calculation Instructions Example

The following example shows an eight-digit addition with CY (SR 25504) used to represent the status of the 9th digit. The status of the UF and OF flags indicate whether the result has exceeded the signed binary data range (–2,147,483,648 (8000 0000) to +2,147,483,647 (7FFF FFFF)).

00100 CLC(41)

ADBL(––)

Address

Instruction

00000 00001 00002

LD CLC(41) ADBL(––)

LR 00

DM 0020

Au : LR 00 0 0 0

Ad + 1 : DM 0011

Ad : DM 0010 F F F 0

F

F

F

F

CY 1

R + 1 : DM 0021 7 F F F

Note

20 0010 0020

0

0

+

00100

LR DM DM

DM 0010

Au + 1 : LR 01 8 0 0 0

Operands

CY (Cleared with CLC(41))

R : DM 0020 F F F 0 1

UF (SR 25405)

0

OF (SR 25404)

1. For unsigned binary addition, CY indicates that the sum of the two values exceeds FFFF FFFF. (UF and OF can be ignored.) 2. For signed binary addition, the UF flag indicates that the sum of the two values is below –2,147,483,648 (8000 0000). (CY can be ignored.)

5-21-6 DOUBLE BINARY SUBTRACT – SBBL(––) Operand Data Areas Mi: Minuend word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # SBBL(––)

@SBB(––)

Mi

Mi

Su

Su

R

R

Su: Subtrahend word (binary)

Limitations

IR, SR, AR, DM, HR, TC, LR, # R: Result word IR, SR, AR, DM, HR, LR

This instruction is available in the only. Mi and Mi+1 must be in the same data area, as must Su and Su+1, and R and R+1. DM 6142 to DM 6655 cannot be used for R.

294

Page 313

Section 5-21

Binary Calculation Instructions

When the execution condition is OFF, SBBL(––) is not executed. When the execution condition is ON, SBBL(––) subtracts CY and the eight-digit value in Su and Su+1 from the eight-digit value in Mi and Mi+1, and places the result in R and R+1. If the result is negative, CY is set and the 2’s complement of the actual result is placed in R+1 and R. Use NEGL(––) to convert the 2’s complement to the true result.

Description

Mi + 1

Mi

Su + 1

Su

– CY

CY

R+1

R

SBBL(––) can also be used to subtract signed binary data. The underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 32-bit signed binary data range. Flags

ER: CY: EQ: OF: UF:

Example

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is negative, i.e., when Mi is less than Su plus CY. ON when the result is 0. ON when the result exceeds +2,147,483,647 (7FFF FFFF). ON when the result is below –2,147,483,648 (8000 0000).

The following example shows an eight-digit subtraction with CY (SR 25504) used to indicate a negative result (with unsigned data). The status of the UF and OF flags indicate whether the result has exceeded the signed binary data range (–2,147,483,648 (8000 0000) to +2,147,483,647 (7FFF FFFF)).

00101 CLC(41)

SBBL(––)

Address

Instruction

00000 00001 00002

LD CLC(41) SBBL(––)

LR 02

DM 0022

–

Mi : LR 02 F F F

Su + 1 : DM 0023

Su : DM 0022 F F F 0

F

F

F

F

CY 1

R + 1 : LR 03 8 0 0 0

Note

R : LR 02 0 0 0

22 0012 0022

0

0

–

00101

LR DM DM

DM 0012

Mi + 1 : LR 03 7 F F F

Operands

CY (Cleared with CLC(41))

0 0

UF (SR 25405)

1

OF (SR 25404)

1. For unsigned binary data, CY indicates that the result is negative. Take the 2’s complement using NEGL(––) to obtain the absolute value of the true result. (UF and OF can be ignored.) 2. For signed binary data, the OF flag indicates that the result exceeds +2,147,483,647 (7FFF FFFF). (CY can be ignored.)

295

Page 314

Section 5-21

Binary Calculation Instructions

5-21-7 SIGNED BINARY MULTIPLY – MBS(––) Operand Data Areas Md: Multiplicand word

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # MBS(––)

@MBS(––)

Md

Md

Mr

Mr

R

R

Mr: Multiplier word

Limitations

IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

This instruction is available in the only. DM 6143 to DM 6655 cannot be used for R.

Description

MBS(––) multiplies the signed binary content of two words and outputs the 8-digit signed binary result to R+1 and R. The rightmost four digits of the result are placed in R, and the leftmost four digits are placed in R+1. Note Refer to 1-10 Calculating with Signed Binary Data for more details. Md

X

Mr

R +1

Flags

Example

R

ER:

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ:

ON when the result is 0000 0000, otherwise OFF.

In the following example, MBS(––) is used to multiply the signed binary contents of DM 0010 with the signed binary contents of DM 0012 and output the result to DM 0100 and DM 0101.

00100 MBS(––) DM 0010

Address

Instruction

00000 00001

LD MBS(––)

DM 0100

R+1: DM 0101 F F A A

296

00100 DM DM DM

DM 0012

X

Operands

1

Md: DM 0010 5 B 1

(5,553)

F

Mr: DM 0012 C 1 3

(–1,005)

D

R: DM 0100 8 2 3

(–5,580,765)

0010 0012 0100

Page 315

Section 5-21

Binary Calculation Instructions

5-21-8 DOUBLE SIGNED BINARY MULTIPLY – MBSL(––) Operand Data Areas Md: First multiplicand word

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # MBSL(––)

@MBSL(––)

Md

Md

Mr

Mr

R

R

Mr: First multiplier word IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

Limitations

This instruction is available in the only. Md and Md+1 must be in the same data area, as must Mr and Mr+1. R and R+3 must be in the same data area. DM 6143 to DM 6655 cannot be used for R.

Description

MBSL(––) multiplies the 32-bit (8-digit) signed binary data in Md+1 and Md with the 32-bit signed binary data in Mr+1 and Mr, and outputs the 16-digit signed binary result to R+3 through R. Note Refer to 1-10 Calculating with Signed Binary Data for more details.

x R+3

Flags

Example

Md + 1

Md

Mr + 1

Mr

R+1

R

R+2

ER:

Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ:

ON when the result is zero (content of R+3 through R all zeroes), otherwise OFF.

In the following example, MBSL(––) is used to multiply the signed binary contents of IR 101 and IR 100 with the signed binary contents of DM 0021 and DM 0020 and output the result to LR 24 through LR 01.

00000

Address

Instruction

00000 00001

LD MBSL(––)

MBSL(––) 100

Operands 00000

DM 0020

DM LR

LR 01

Md+1: IR 101 0 0 8

7

Md: IR 100 9 3 8

(555,320)

Mr+1: DM 0021 F F F 0

A

Mr: DM 0020 8 1 2

(–1,005,550)

R+1: LR 02 C A 5

4

R: LR 01 5 F

0

X F

R+3: LR 04 F F F

F

R+2: LR 03 F 7 D

F

0

100 0020 21

(–55,840,206,000)

297

Page 316

Section 5-21

Binary Calculation Instructions

5-21-9 SIGNED BINARY DIVIDE – DBS(––) Operand Data Areas Dd: Dividend word

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # DBS(––)

@DBS(––)

Dd

Dd

Dr

Dr

R

R

Dr: Divisor word

Limitations

IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

This instruction is available in the only. DM 6143 to DM 6655 cannot be used for R.

Description

DBS(––) divides the signed binary content of Dd by the signed binary content of Dr, and outputs the 8-digit signed binary result to R+1 and R. The quotient is placed in R, and the remainder is placed in R+1. Note Refer to 1-10 Calculating with Signed Binary Data for more details. Quotient R

Dr

Flags

ER:

Remainder R+1

Dd

Dr contains 0. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.)

EQ: Example

ON when the content of R (the quotient) is 0000, otherwise OFF.

In the following example, DBS(––) is used to divide the signed binary contents of DM 0010 with the signed binary contents of DM 0020 and output the result to LR 21 and LR 02.

00000 DBS(––) DM 0010

Address

Instruction

00000 00001

LD DBS(––)

LR 01

F

R+1: LR 02 F F A

Remainder (–6)

298

00000 DM DM LR

DM 0020

÷

Operands

Dd: DM 0010 D D D A

0

Dr: DM 0020 0 1 A

F

R: LR 01 E B

0

Quotient (–336)

(–8,742)

(26)

(–336 and –6/26)

0010 0020 21

Page 317

Section 5-21

Binary Calculation Instructions

5-21-10 DOUBLE SIGNED BINARY DIVIDE – DBSL(––) Operand Data Areas Dd: Dividend word (binary)

Ladder Symbols

IR, SR, AR, DM, HR, TC, LR, # DBS(––)

@DBS(––)

Dd

Dd

Dr

Dr

R

R

Dr: Divisor word (binary) IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR

Limitations

This instruction is available in the only. Dd and Dd+1 must be in the same data area, as must Dr and Dr+1. R and R+3 must be in the same data area. DM 6143 to DM 6655 cannot be used for R.

Description

DBS(––) divides the 32-bit (8-digit) signed binary data in Dd+1 and Dd by the 32-bit signed binary data in Dr+1 and Dr, and outputs the 16-digit signed binary result to R+3 through R. The quotient is placed in R+1 and R, and the remainder is placed in R+3 and R+2. Note Refer to 1-10 Calculating with Signed Binary Data for more details. Remainder R+3

Dr+1

Flags

ER:

R+2

Dr

R+1

R

Dd+1

Dd

Dr+1 and Dr contain 0. Indirectly addressed DM word is non-existent. (Content of DM word is not BCD, or the DM area boundary has been exceeded.) ON when the content of R+1 and R (the quotient) is 0, otherwise OFF.

EQ: Example

Quotient

In the following example, DBSL(––) is used to divide the signed binary contents of IR 101 and IR 100 with the signed binary contents of DM 0021 and DM 0020 and output the result to LR 24 through LR 01.

00000 DBSL(––) 100

Address

Instruction

00000 00001

LD DBSL(––)

Operands 00000

DM 0020

DM LR

LR 01

÷

F

R+3: LR 04 F F F

F

R+2: LR 03 F F C

Remainder (–4)

Dd+1: IR 101 F 7 A

B

Dd: IR 100 1 5 C

(–8,736,420)

Dr+1: DM 0021 0 0 0 0

0

Dr: DM 0020 0 1 A

(26)

R+1: LR 02 F F A

D

R: LR 01 F 7

F

F

0

100 0020 21

(–336,016 and –4/26)

Quotient (–336)

299

Page 318

Section 5-22

Special Math Instructions

5-22 Special Math Instructions 5-22-1 FIND MAXIMUM – MAX(––) Ladder Symbols

Operand Data Areas C: Control data

MAX(––)

@MAX(––)

C

C

R1

R1

D

D

IR, SR, AR, DM, HR, TC, LR, # R1: First word in range IR, SR, AR, DM, HR, TC, LR D: Destination word IR, SR, AR, DM, HR, LR

Limitations

This instruction is available in the CQM1 only. N must be BCD between 0001 to 9999. R1 and R1+N–1 must be in the same data area. DM 6144 to DM 6655 cannot be used for D.

Description

When the execution condition is OFF, MAX(––) is not executed. When the execution condition is ON, MAX(––) searches the range of memory from R1 to R1+N–1 for the address that contains the maximum value and outputs the maximum value to the destination word (D). If bit 15 of C is ON, MAX(––) identifies the address of the word containing the maximum value in D+1. The address is identified differently for the DM area: 1, 2, 3...

1. For an address in the DM area, the word address is written to C+1. For example, if the address containing the maximum value is DM 0114, then #0114 is written in D+1. 2. For an address in another data area, the number of addresses from the beginning of the search is written to D+1. For example, if the address containing the maximum value is IR 114 and the first word in the search range is IR 014, then #0100 is written in D+1. If bit 14 of C is ON and more than one address contains the same maximum value, the position of the lowest of the addresses will be output to D+1. The position will be output as the DM address for the DM area, but as an absolute position relative to the first word in the range for all other areas. The number of words within the range (N) is contained in the 3 rightmost digits of C, which must be BCD between 001 and 999. When bit 15 of C is OFF, data within the range is treated as unsigned binary and when it is ON the data is treated as signed binary. C:

15 14 13 12 11

00 Number of words in range (N) Not used – set to zero.

Data type 1 (ON): Signed binary 0 (OFF): Unsigned binary

! Caution

300

Output address to D+1? 1 (ON): Yes. 0 (OFF): No.

If bit 14 of C is ON, values above #8000 are treated as negative numbers, so the results will differ depending on the specified data type. Be sure that the correct data type is specified.