A single scanned manual page with the specification table for Omron CQM1 Power Supply Units: the CQM1-PA203, CQM1-PA206, CQM1-PA216 and CQM1-PD026. It lists supply voltages, output capacity, power consumption and environmental ratings, and ends where the CPU Unit table begins.
- Document
- Specification table for the CQM1-PA203, CQM1-PA206, CQM1-PA216 and CQM1-PD026 Power Supply Units p. 1
- Operating temperature
- 0° to 55°C; storage -20° to 75°C (except battery) p. 1
- Humidity
- 10% to 90%, with no condensation p. 1
- Noise immunity
- 1,500 Vp-p (via noise simulation) p. 1
- Vibration
- 10 to 57 Hz at 0.075-mm amplitude and 57 to 150 Hz, 80 minutes each in X, Y and Z p. 1
- Atmosphere
- Must be free from corrosive gasses p. 1
- Supply voltage
- CQM1-PA203: 100 to 240 VAC, 50/60 Hz, operating range 85 to 264 VAC p. 1
- DC supply voltage
- CQM1-PD026: 24 VDC, operating range 20 to 28 VDC p. 1
- Output capacity
- CQM1-PA203: 5 VDC, 3.6 A (18 W); CQM1-PD026: 5 VDC, 6 A (30 W) p. 1
- Power consumption
- CQM1-PA203: 60 VA max.; CQM1-PD026: 50 W max. p. 1
- Inrush current
- 30 A max. p. 1
What this manual walks you through
- Comparing the specifications of the CQM1 Power Supply Units p. 1
- Preparing for insulation and dielectric strength tests p. 1
Good to know
- Disconnect the LG terminal from the GR terminal before insulation and dielectric strength tests; repeated tests with them shorted may damage internal components. p. 1
Questions this manual answers
What input voltage does the CQM1-PA203 take?
100 to 240 VAC at 50/60 Hz, with an operating range of 85 to 264 VAC. p. 1
What voltage does the CQM1-PD026 power supply need?
24 VDC, with an operating range of 20 to 28 VDC. p. 1
How much 5 VDC current can the CQM1-PA203 supply?
3.6 A at 5 VDC (18 W). p. 1
What temperature can CQM1 power supply units operate in?
0° to 55°C when operating; storage is -20° to 75°C. p. 1
The file
Size and text
Every page · 1
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 1
Open in the PDF
The text of page 1, read from a scan by OCR; it may hold reading errors
Unit Specifications Section 2-6 2-6 Unit Specifications 2-6-1 Power Supply Units Item CQM1-PA203 | CQM1-PA206 CQM1-PA216 CQM1-PD026 Supply voltage 100 to 240 VAC, 50/60 Hz 100 or 230 VAC 24 VDC (selectable), 50/60 Hz Operating voltage range | 85 to 264 VAC 8510 132 VAC or 170 |20to 28 VDC fo 264 VAC Operating frequency 47 to 63 Hz range Power consumption 60 VA max. | 120 VA max. 50 W max. Inrush current 30 A max. Output capacity 5 VDC:3.6A(18W) |5 VDC:6A 5 VDC: 6 A (30 W) 24 VDC:05A (30 W total) Insulation resistance 20 M@ min. (at 500 VDC) between AC external terminals and GR 20 MQ min. (at terminals (see note 1) 500 VDC) between AC external terminals and GR terminals (see note 1)
Dielectric strength
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals, (see note 1) leakage current: 10 mA max.
1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals, (see note 1) leakage current: 20 mA max.
Noise immunity
1,500 Vp-p, pulse width: 100 ns to 1 us, rise time: 1 ns (via noise simulation)
Vibration resistance
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s? (see note 2) in X, Y, and Z directions for 80 minutes each (Time coefficient; 8 minutes x coefficient factor 10 = total time 80 minutes)
Shock resistance
147 m/s® (21.8 m/s® for Contact Output Units) 3 times each in X, Y, and Z directions
Ambient temperature
Operating: 0° to 55°C Storage: -20° to 75°C (except battery)
(without cables)
Humidity 10% to 90% {with no condensation} Atmosphere Must be free from corrosive gasses Grounding Less than 1002
Enclosure rating Mounted in a panel
Weight 5 kilograms max.
Dimensions 219 to 443 x 110 x 107 mm (WxHxD)
Note 1. Disconnect the LG terminal of the Power Supply Unit from the GR terminal when performing insulation and dielectric strength tests. If the tests are repeatedly performed with the LG and GR terminals short-circuited, the
internal components may be damaged.
Accaleration (m/s*) ‘ Amplitude (0.075)
f q 57
10 150 Frequency (Hz) 2-6-2 CPU Unit Specifications Item CQM1-CPU11-E/21-E CQM1-CPU41 CQM1-CPU42 CQM1-CPU43-EV1 -EV1 -EV1 (44-EV1
Control methodStored program methodVO control method
Cyclic scan with direct output; immediate interrupt processing
Programming languageLadder diagram40