Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 10 of 39

C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 91 to 100

Pages 91 to 100 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual

The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron DRT1-ID16

Page 91

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The following diagram shows the wiring of the DRT1-OD16TA-1 Remote Output Terminal. 0

1

7

V1

V1

V1

V1

G1

G1

G1

G1

−

+

+

Solenoid, valve, etc.

Note

8

9

15

V2

V2

V2

V2

G2

G2

G2

G2

−

Solenoid, valve, etc.

Solenoid, valve, etc.

Solenoid, valve, etc.

1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully. 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally.

Dimensions

The following diagram shows the dimensions for the DRT1-OD16T and DRT1OD16TA-1 Remote Output Terminals. All dimensions are in mm. 180 DRT1-OD16TA

0

REMOTE TERMINAL DC24V

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

ON

OUT

MS NS

50

(54)

DR0 DR1 NC HOLD

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

58 (83) Mounting holes

Two, 4.2 dia. or M4

40±0.2

Values in parentheses are reference values.

170±0.2

Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-OD16TA and DRT1-OD16TA-1.)

76

Page 92

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.

4-4-6

Transistor Remote I/O Terminals with 8 Inputs and 8 Outputs and 3-tier I/O Terminal Blocks: DRT1-MD16T (NPN) and DRT1-MD16T-1 (PNP)

Input Specifications Item

Specification

Model Internal I/O common

DRT1-MD16T NPN

DRT1-MD16T-1 PNP

Input points ON voltage

8 points 15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V) 1 mA max.

15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)

OFF voltage OFF current Input current ON delay time

6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC 1.5 ms max.

OFF delay time Number of circuits

1.5 ms max. 8 points with one common

Output Specifications Item

Specification DRT1-MD16T-1

Model

DRT1-MD16T

Internal I/O common Output points

NPN 8 points

Rated output current Residual voltage

Leakage current

0.5 A/point 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V) 0.1 mA max.

ON delay time OFF delay time

0.5 ms max. 1.5 ms max.

Number of circuits

8 points with one common

PNP

77

Page 93

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-MD16T and DRT1-MD16T-1 Rotary switches (Refer to page 62.) Set the node address.

DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error DeviceNet Indicators (Refer to page 312.)

DRT1-MD16T REMOTE TERMINAL DC24V

Input indicators Indicate the input status of each contact. (Lit when the input is ON.)

Output indicators Indicate the output status of each contact. (Lit when the output is ON.)

0

5

1

2

3

4

5

6

7

0

1

2

3

4

6

7

ON DR0 DR1 NC HOLD

IN

MS NS

OUT

Circuit removal screws.

DIN track mounting hooks

Communications connector Internal power supply terminals

Output terminal block

Input terminal block

Internal Circuit

The following diagram shows the internal circuits for the DRT1-MD16T Remote I/O Terminal. Photocoupler

V1 24 V DC G1

V− CANL DRAIN

V1 Physical layer

Photocoupler

CANH

Internal circuitry

V+

Photocoupler Voltage step-down

Input (0 to 7) G1 V2 24 V DC G2

SOURCE 24 V DC + SOURCE 24 V DC −

78

I/O power supply

V2 DC-DC converter (Isolated)

Output (0 to 7) Photocoupler G2

I/O power supply

Page 94

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The following diagram shows the internal circuits for the DRT1-MD16T-1 Remote I/O Terminal. Photocoupler

V1 24 V DC

I/O power supply

G1

V−

V1

CANL Physical layer

DRAIN

Input (0 to 7)

Photocoupler

CANH Internal circuitry

V+

SOURCE 24 V DC +

G1

Photocoupler

V2 24 V DC

Voltage stepdown

G2

I/O power supply

V2 DC-DC converter (Isolated)

SOURCE 24 V DC −

Output (0 to 7) G2 Photocoupler

Wiring

The following diagram shows the wiring of the DRT1-MD16T Remote I/O Terminal.

−

+

+

−

+

0

1

7

V1

V1

V1

V1

G1

G1

G1

G1

−

+

0

1

7

V2

V2

V2

V2

G2

G2

G2

G2

−

Brown (red)

Black (white)

Blue (black)

Blue (black)

Brown (white)

Internal circuits power supply

2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)

Solenoid, valve, etc.

Solenoid, valve, etc.

79

Page 95

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The following diagram shows the wiring of the DRT1-MD16T-1 Remote I/O Terminal.

−

+

+

−

0

1

7

V1

V1

V1

V1

G1

G1

G1

G1

−

+

+

0

1

7

V2

V2

V2

V2

G2

G2

G2

G2

−

Black (white)

Brown (red)

Blue (black)

Brown (white)

Blue (black)

Internal circuits power supply

Solenoid, valve, etc.

2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)

Note

Solenoid, valve, etc.

1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally. 3. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses.

Dimensions

The following diagram shows the dimensions for the DRT1-MD16T and DRT1-MD16T-1 Remote I/O Terminals. All dimensions are in mm. 180 DRT1-MD16T

0

REMOTE TERMINAL DC24V

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

ON

IN

MS NS

50

(54)

DR0 DR1 NC HOLD

0

1

2

3

4

5

6

7

8

9

10

11

12

OUT

13

14

15

58 (83) Values in parentheses are reference values.

Two, 4.2 dia. or M4

40±0.2

Mounting holes

170±0.2

Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-MD16T and DRT1-MD16T-1.)

80

Page 96

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.

4-4-7

Transistor Remote I/O Terminals with 8 Inputs and 8 Outputs and 3-tier I/O Terminal Blocks: DRT1-MD16TA (NPN) and DRT1-MD16TA-1 (PNP)

Input Specifications Item

Specification DRT1-MD16TA-1

Model

DRT1-MD16TA

Internal I/O common Input points

NPN 8 points

PNP

ON voltage

15 V DC min. (between each input terminal and V)

15 V DC min. (between each input terminal and G)

OFF voltage

5 V DC max. (between each input terminal and V) 1.0 mA max.

5 V DC max. (between each input terminal and G)

OFF current Input current

6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC

ON delay time OFF delay time

1.5 ms max. 1.5 ms max.

Number of circuits

8 points with one common

Output Specifications Item

Specification DRT1-MD16TA-1

Model

DRT1-MD16TA

Internal I/O common Output points

NPN 8 points

Rated output current Residual voltage

0.5 A/point 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V)

Leakage current ON delay time

0.1 mA max. 0.5 ms max.

OFF delay time Number of circuits

1.5 ms max. 8 points with one common

PNP

81

Page 97

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-MD16TA and DRT1-MD16TA-1 Rotary switches (Refer to page 62.) Set the node address. (Refer to page 62.)

DIP switch Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error DeviceNet Indicators (Refer to page 312.)

DRT1-MD16TA REMOTE TERMINAL DC24V

Input indicators Indicate the output status of each contact. (Lit when the input is ON.)

Output indicators Indicate the output status of each contact. (Lit when the output is ON.)

0

5

1

2

3

4

5

6

7

0

1

2

3

4

6

7

ON DR0 DR1 NC HOLD

IN

MS NS

OUT

Circuit removal screws.

Communications connector

DIN track mounting hooks Input terminal block

Internal Circuits

Output terminal block

The following diagram shows the internal circuits for the DRT1-MD16TA Remote I/O Terminal. V1 24 V DC 5

V+

G1

Photocoupler

4

CAN_H

V1

3

DRAIN 2

CAN_L 1

Physical layer

0 to 7

Voltage step-down

Internal circuitry

V−

V2 24 V DC

Photocoupler DC-DC converter (Isolated)

G1

G2 V2 0 to 7

G2

82

Page 98

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The following diagram shows the internal circuits for the DRT1-MD16TA-1 Remote I/O Terminal. V1 24 V DC 5

G1

V+ 4

CAN_H DRAIN 2

CAN_L 1

V1

Photocoupler

3

Physical layer

0 to 7 G1

Internal circuitry

V−

Voltage stepdown

V2 24 V DC G2 V2

DC-DC converter (Isolated)

Photocoupler 0 to 7 G2

The following diagram shows the wiring of the DRT1-MD16TA Remote I/O Terminal 1

7

V1

V1

V1

V1

G1

G1

G1

G1

−

0

1

7

V2

V2

V2

V2

G2

G2

G2

G2

−

Black (white)

Brown (red)

Blue (black)

+

Blue (black)

+

0

Brown (white)

Wiring

2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)

Solenoid, valve, etc.

Solenoid, valve, etc.

83

Page 99

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The following diagram shows the wiring of the DRT1-MD16TA-1 Remote I/O Terminal. 0

1

7

V1

V1

V1

V1

G1

G1

G1

G1

−

1

7

V2

V2

V2

V2

G2

G2

G2

G2

−

Black (white)

Brown (red)

Blue (black)

Blue (black)

+

Brown (white)

+

0

Solenoid, valve, etc.

2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)

Note

Solenoid, valve, etc.

1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally. 3. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses.

Dimensions

The following diagram shows the dimensions for the DRT1-MD16TA and DRT1-MD16TA-1 Remote I/O Terminals. All dimensions are in mm. 180 DRT1-MD16TA

0

REMOTE TERMINAL DC24V

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

ON

IN

MS NS

50

(54)

DR0 DR1 NC HOLD

0

1

2

3

4

5

6

7

8

9

10

11

12

OUT

13

14

15

58 (83) Mounting holes

Two, 4.2 dia. or M4

40±0.2

Values in parentheses are reference values.

170±0.2

Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-MD16TA and DRT1-MD16TA-1.)

84

Page 100

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.

4-4-8

Mounting in Control Panels Either of the following methods can be used to mount an Remote I/O Terminal in a control panel.

Using Screws

Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Remote I/O Terminal with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.

Using DIN Track

Mount the back of the Remote I/O Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates. Connecting End Plates Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2

1

End Plate

Note Always attach End Plate to both ends of Slaves connected to DIN Track.

85