Page 91
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the wiring of the DRT1-OD16TA-1 Remote Output Terminal. 0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
+
Solenoid, valve, etc.
Note
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
−
Solenoid, valve, etc.
Solenoid, valve, etc.
Solenoid, valve, etc.
1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully. 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally.
Dimensions
The following diagram shows the dimensions for the DRT1-OD16T and DRT1OD16TA-1 Remote Output Terminals. All dimensions are in mm. 180 DRT1-OD16TA
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
OUT
MS NS
50
(54)
DR0 DR1 NC HOLD
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
58 (83) Mounting holes
Two, 4.2 dia. or M4
40±0.2
Values in parentheses are reference values.
170±0.2
Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-OD16TA and DRT1-OD16TA-1.)
76
Page 92
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.
4-4-6
Transistor Remote I/O Terminals with 8 Inputs and 8 Outputs and 3-tier I/O Terminal Blocks: DRT1-MD16T (NPN) and DRT1-MD16T-1 (PNP)
Input Specifications Item
Specification
Model Internal I/O common
DRT1-MD16T NPN
DRT1-MD16T-1 PNP
Input points ON voltage
8 points 15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V) 1 mA max.
15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)
OFF voltage OFF current Input current ON delay time
6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC 1.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with one common
Output Specifications Item
Specification DRT1-MD16T-1
Model
DRT1-MD16T
Internal I/O common Output points
NPN 8 points
Rated output current Residual voltage
Leakage current
0.5 A/point 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V) 0.1 mA max.
ON delay time OFF delay time
0.5 ms max. 1.5 ms max.
Number of circuits
8 points with one common
PNP
77
Page 93
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-MD16T and DRT1-MD16T-1 Rotary switches (Refer to page 62.) Set the node address.
DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error DeviceNet Indicators (Refer to page 312.)
DRT1-MD16T REMOTE TERMINAL DC24V
Input indicators Indicate the input status of each contact. (Lit when the input is ON.)
Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
0
5
1
2
3
4
5
6
7
0
1
2
3
4
6
7
ON DR0 DR1 NC HOLD
IN
MS NS
OUT
Circuit removal screws.
DIN track mounting hooks
Communications connector Internal power supply terminals
Output terminal block
Input terminal block
Internal Circuit
The following diagram shows the internal circuits for the DRT1-MD16T Remote I/O Terminal. Photocoupler
V1 24 V DC G1
V− CANL DRAIN
V1 Physical layer
Photocoupler
CANH
Internal circuitry
V+
Photocoupler Voltage step-down
Input (0 to 7) G1 V2 24 V DC G2
SOURCE 24 V DC + SOURCE 24 V DC −
78
I/O power supply
V2 DC-DC converter (Isolated)
Output (0 to 7) Photocoupler G2
I/O power supply
Page 94
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the internal circuits for the DRT1-MD16T-1 Remote I/O Terminal. Photocoupler
V1 24 V DC
I/O power supply
G1
V−
V1
CANL Physical layer
DRAIN
Input (0 to 7)
Photocoupler
CANH Internal circuitry
V+
SOURCE 24 V DC +
G1
Photocoupler
V2 24 V DC
Voltage stepdown
G2
I/O power supply
V2 DC-DC converter (Isolated)
SOURCE 24 V DC −
Output (0 to 7) G2 Photocoupler
Wiring
The following diagram shows the wiring of the DRT1-MD16T Remote I/O Terminal.
−
+
+
−
+
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
0
1
7
V2
V2
V2
V2
G2
G2
G2
G2
−
Brown (red)
Black (white)
Blue (black)
Blue (black)
Brown (white)
Internal circuits power supply
2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)
Solenoid, valve, etc.
Solenoid, valve, etc.
79
Page 95
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the wiring of the DRT1-MD16T-1 Remote I/O Terminal.
−
+
+
−
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
+
0
1
7
V2
V2
V2
V2
G2
G2
G2
G2
−
Black (white)
Brown (red)
Blue (black)
Brown (white)
Blue (black)
Internal circuits power supply
Solenoid, valve, etc.
2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)
Note
Solenoid, valve, etc.
1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally. 3. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses.
Dimensions
The following diagram shows the dimensions for the DRT1-MD16T and DRT1-MD16T-1 Remote I/O Terminals. All dimensions are in mm. 180 DRT1-MD16T
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
ON
IN
MS NS
50
(54)
DR0 DR1 NC HOLD
0
1
2
3
4
5
6
7
8
9
10
11
12
OUT
13
14
15
58 (83) Values in parentheses are reference values.
Two, 4.2 dia. or M4
40±0.2
Mounting holes
170±0.2
Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-MD16T and DRT1-MD16T-1.)
80
Page 96
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.
4-4-7
Transistor Remote I/O Terminals with 8 Inputs and 8 Outputs and 3-tier I/O Terminal Blocks: DRT1-MD16TA (NPN) and DRT1-MD16TA-1 (PNP)
Input Specifications Item
Specification DRT1-MD16TA-1
Model
DRT1-MD16TA
Internal I/O common Input points
NPN 8 points
PNP
ON voltage
15 V DC min. (between each input terminal and V)
15 V DC min. (between each input terminal and G)
OFF voltage
5 V DC max. (between each input terminal and V) 1.0 mA max.
5 V DC max. (between each input terminal and G)
OFF current Input current
6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC
ON delay time OFF delay time
1.5 ms max. 1.5 ms max.
Number of circuits
8 points with one common
Output Specifications Item
Specification DRT1-MD16TA-1
Model
DRT1-MD16TA
Internal I/O common Output points
NPN 8 points
Rated output current Residual voltage
0.5 A/point 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V)
Leakage current ON delay time
0.1 mA max. 0.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with one common
PNP
81
Page 97
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-MD16TA and DRT1-MD16TA-1 Rotary switches (Refer to page 62.) Set the node address. (Refer to page 62.)
DIP switch Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error DeviceNet Indicators (Refer to page 312.)
DRT1-MD16TA REMOTE TERMINAL DC24V
Input indicators Indicate the output status of each contact. (Lit when the input is ON.)
Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
0
5
1
2
3
4
5
6
7
0
1
2
3
4
6
7
ON DR0 DR1 NC HOLD
IN
MS NS
OUT
Circuit removal screws.
Communications connector
DIN track mounting hooks Input terminal block
Internal Circuits
Output terminal block
The following diagram shows the internal circuits for the DRT1-MD16TA Remote I/O Terminal. V1 24 V DC 5
V+
G1
Photocoupler
4
CAN_H
V1
3
DRAIN 2
CAN_L 1
Physical layer
0 to 7
Voltage step-down
Internal circuitry
V−
V2 24 V DC
Photocoupler DC-DC converter (Isolated)
G1
G2 V2 0 to 7
G2
82
Page 98
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the internal circuits for the DRT1-MD16TA-1 Remote I/O Terminal. V1 24 V DC 5
G1
V+ 4
CAN_H DRAIN 2
CAN_L 1
V1
Photocoupler
3
Physical layer
0 to 7 G1
Internal circuitry
V−
Voltage stepdown
V2 24 V DC G2 V2
DC-DC converter (Isolated)
Photocoupler 0 to 7 G2
The following diagram shows the wiring of the DRT1-MD16TA Remote I/O Terminal 1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
0
1
7
V2
V2
V2
V2
G2
G2
G2
G2
−
Black (white)
Brown (red)
Blue (black)
+
Blue (black)
+
0
Brown (white)
Wiring
2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)
Solenoid, valve, etc.
Solenoid, valve, etc.
83
Page 99
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the wiring of the DRT1-MD16TA-1 Remote I/O Terminal. 0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
1
7
V2
V2
V2
V2
G2
G2
G2
G2
−
Black (white)
Brown (red)
Blue (black)
Blue (black)
+
Brown (white)
+
0
Solenoid, valve, etc.
2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)
Note
Solenoid, valve, etc.
1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally. 3. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses.
Dimensions
The following diagram shows the dimensions for the DRT1-MD16TA and DRT1-MD16TA-1 Remote I/O Terminals. All dimensions are in mm. 180 DRT1-MD16TA
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
ON
IN
MS NS
50
(54)
DR0 DR1 NC HOLD
0
1
2
3
4
5
6
7
8
9
10
11
12
OUT
13
14
15
58 (83) Mounting holes
Two, 4.2 dia. or M4
40±0.2
Values in parentheses are reference values.
170±0.2
Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-MD16TA and DRT1-MD16TA-1.)
84
Page 100
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.
4-4-8
Mounting in Control Panels Either of the following methods can be used to mount an Remote I/O Terminal in a control panel.
Using Screws
Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Remote I/O Terminal with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.
Using DIN Track
Mount the back of the Remote I/O Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates. Connecting End Plates Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2
1
End Plate
Note Always attach End Plate to both ends of Slaves connected to DIN Track.