C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 81 to 90
Pages 81 to 90 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual
The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron DRT1-ID16
Page 81
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the wiring of the DRT1-ID16T-1 Remote Input Terminal.
−
+
+
−
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
+
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
−
Black (white)
Brown (red)
Blue (black)
2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)
2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)
Note
Blue (black)
Brown (white)
Black (white)
Brown (red)
Blue (black)
Brown (white)
Blue (black)
Internal circuits power supply
1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully. 2. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses.
Dimensions
The following diagram shows the dimensions for the DRT1-ID16T and DRT1ID16T-1 Remote Input Terminals. All dimensions are in mm. 180 DRT1-ID16T
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
IN
MS NS
50
(54)
DR0 DR1 NC NC
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
58 (83) Mounting holes
Two, 4.2 dia. or M4
40±0.2
Values in parentheses are reference values.
170±0.2
Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-ID16T and DRT1-ID16T-1.)
66
Page 82
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.
4-4-3
Transistor Remote Input Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-ID16TA (NPN) and DRT1-ID16TA-1 (PNP)
Input Specifications Item
Specification
Model Internal I/O common
DRT1-ID16TA NPN
DRT1-ID16TA-1 PNP
Input points ON voltage
16 points 15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V)
15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)
OFF voltage OFF current Input current ON delay time
1.0 mA max. 6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC 1.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with two commons
Components of the DRT1-ID16TA and DRT1-ID16TA-1 Rotary switches (Refer to page 62.) Set the node address.
DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pins 3 and 4: Reserved (Always OFF.) Input indicators Indicate the input status of each contact. (Lit when the input is ON.)
DeviceNet Indicators (Refer to page 312.)
DRT1-ID16TA
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON DR0 DR1 NC NC
IN
MS NS
Circuit removal screws.
Communications connector
Terminal block DIN track mounting hooks
67
Page 83
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Internal Circuits
The following diagram shows the internal circuits for the DRT1-ID16TA Remote Input Terminal. V1 24 V DC 5
G1
V+
Photocoupler
4
V1
CAN_H 3
DRAIN 2
CAN_L 1
Physical layer
0 to 7 G1
Internal circuitry
V−
V2 24 V DC G2
Photocoupler V2
DC-DC converter (Isolated)
8 to 15 G2
The following diagram shows the internal circuits for the DRT1-ID16TA-1 Remote Input Terminal. V1 24 V DC 5
G1
V+ 4
V1
CAN_H
Photocoupler
3
DRAIN 2
CAN_L 1
0 to 7
Physical layer
G1
Internal circuitry
V−
V2 24 V DC G2 V2
Photocoupler
DC-DC converter (Isolated)
8 to 15 G2
The following diagram shows the wiring of the DRT1-ID16TA Remote Input Terminal.
V1
G1
G1
G1
G1
−
Black (white)
Brown (red)
Blue (black)
+
2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)
68
V2
V2
V2
V2
G2
G2
G2
G2
−
Brown (red)
V1
15
Black (white)
V1
9
Blue (black)
V1
8
Blue (black)
7
Brown (white)
1
Brown (white)
+
0
Blue (black)
Wiring
2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)
Page 84
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the wiring of the DRT1-ID16TA-1 Remote Input Terminal.
V1
V1
V1
G1
G1
G1
G1
−
2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)
Note
15
V2
V2
V2
V2
G2
G2
G2
G2
−
Brown (white)
Black (white)
Brown (red)
Blue (black)
Blue (black)
+
Brown (white)
+
9
Black (white)
V1
8
Brown (red)
7
Blue (black)
1
Blue (black)
0
2-wire sensor 3-wire sensor with (e.g., limit switch) PNP output (photoelectric or proximity sensor)
1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully. 2. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses.
Dimensions
The following diagram shows the dimensions for the DRT1-ID16TA and DRT1-ID16TA-1 Remote Input Terminals. All dimensions are in mm. 180 DRT1-ID16TA
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
IN
MS NS
50
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
58 (83) Mounting holes
Values in parentheses are reference values.
Two, 4.2 dia. or M4
40±0.2
(54)
DR0 DR1 NC NC
170±0.2
Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-ID16TA and DRT1-ID16TA-1.)
69
Page 85
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.
4-4-4
Transistor Remote Output Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-OD16T (NPN) and DRT1-OD16T-1 (PNP)
Output Specifications Item
Specification DRT1-OD16T-1
Model
DRT1-OD16T
Internal I/O common Output points
NPN 16 points
Rated output current Residual voltage
Leakage current
0.5 A/point 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V) 0.1 mA max.
ON delay time OFF delay time
0.5 ms max. 1.5 ms max.
Number of circuits
8 points with two commons
PNP
Components of the DRT1-OD16T and DRT1-OD16T-1 Rotary switches (Refer to page 62.) Set the node address.
DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
DeviceNet Indicators (Refer to page 312.)
DRT1-OD16T
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON DR0 DR1 NC HOLD
MS NS
OUT
Circuit removal screws.
Communications connector Internal power supply terminals
70
Terminal block DIN track mounting hooks
Page 86
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Internal Circuits
The following diagram shows the internal circuits for the DRT1-OD16T Remote Output Terminal. Voltage step-down
V1 24 V DC
Photocoupler
I/O power supply
G1
V− V1 CANL DRAIN
Physical layer
Output (0 to 7)
Photocoupler
CANH
Photocoupler G1
Internal circuitry
V+
V2 24 V DC
I/O power supply
G2 SOURCE 24 V DC + SOURCE 24 V DC −
Voltage step-down
DC-DC converter (Isolated)
V2 Output (8 to 15)
Photocoupler G2
The following diagram shows the internal circuits for the DRT1-OD16T-1 Remote Output Terminal. Voltage step-down V1 24 V DC
Photocoupler
G1
V−
I/O power supply
V1
CANL DRAIN
Physical layer
Output (0 to 7)
Photocoupler
G1
CANH Internal circuitry
V+
Voltage Photocoupler step-down V2 24 V DC G2
SOURCE 24 V DC + SOURCE 24 V DC −
I/O power supply
V2 DC-DC converter (Isolated)
Output (8 to 15) G2 Photocoupler
71
Page 87
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Wiring
The following diagram shows the wiring of the DRT1-OD16T Remote Output Terminal.
−
+
+
−
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
−
+
Internal circuits power supply
Solenoid, valve, etc.
Solenoid, valve, etc.
Solenoid, valve, etc.
Solenoid, valve, etc.
The following diagram shows the wiring of the DRT1-OD16T-1 Remote Output Terminal.
−
+
+
−
+
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
−
Internal circuits power supply
Solenoid, valve, etc.
Note
Solenoid, valve, etc.
Solenoid, valve, etc.
Solenoid, valve, etc.
1. V1 is not connected internally to V2, and G1 is not connected internally to G2. Connect them carefully 2. When using inductive loads (such as solenoids or valves), use a load with a built-in diode to absorb reverse power or attach a diode externally.
72
Page 88
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Dimensions
The following diagram shows the dimensions for the DRT1-OD16T and DRT1OD16T-1 Remote Output Terminals. All dimensions are in mm. 180 DRT1-OD16T
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
OUT
MS NS
50
(54)
DR0 DR1 NC HOLD
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
58 (83) Mounting holes 40±0.2
Values in parentheses are reference values.
Two, 4.2 dia. or M4
170±0.2
Note The circuit section can be removed by loosening the circuit removal screws. (Refer to Components of the DRT1-OD16T and DRT1-OD16T-1.) Always turn OFF the communications, internal, and I/O power supplies before removing or attaching the circuit section.
4-4-5
Transistor Remote Output Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-OD16TA (NPN) and DRT1-OD16TA-1 (PNP)
Output Specifications Item
Specification DRT1-OD16TA-1
Model
DRT1-OD16TA
Internal I/O common Output points
NPN 16 points
Rated output current Residual voltage
Leakage current
0.5 A/point 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V) 0.1 mA max.
ON delay time OFF delay time
0.5 ms max. 1.5 ms max.
Number of circuits
8 points
PNP
73
Page 89
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-OD16TA and DRT1-OD16TA-1 Rotary switches (Refer to page 62.) Set the node address.
DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
DeviceNet Indicators (Refer to page 312.)
DRT1-OD16TA
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON DR0 DR1 NC HOLD
OUT
MS NS
Circuit removal screws.
Terminal block
Communications connector DIN track mounting hooks
Internal Circuits
The following diagram shows the internal circuits for the DRT1-OD16TA Remote Output Terminal. Voltage step-down
V1 24 V DC
Photocoupler
G1
I/O power supply
V− V1 CANL DRAIN
Physical layer
Output (0 to 7)
Photocoupler
CANH
Photocoupler G1
Internal circuitry
V+
V2 24 V DC G2 Voltage step-down
DC-DC converter (Isolated)
V2 Output (8 to 15)
Photocoupler G2
74
I/O power supply
Page 90
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the internal circuits for the DRT1-OD16TA-1 Remote Output Terminal. Voltage step-down V1 24 V DC
Photocoupler
G1
V− CANL DRAIN
I/O power supply
V1 Physical layer
Output (0 to 7)
Photocoupler
G1
CANH Internal circuitry
V+
Voltage Photocoupler step-down V2 24 V DC
I/O power supply
G2 V2 DC-DC converter (Isolated)
Output (8 to 15) G2 Photocoupler
Wiring
The following diagram shows the wiring of the DRT1-OD16TA Remote Output Terminal.
+
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
Solenoid, valve, etc.
+
Solenoid, valve, etc.
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
−
Solenoid, valve, etc.
Solenoid, valve, etc.
75