The text of a manual · part 8 of 39
C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 71 to 80
Pages 71 to 80 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual
The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron DRT1-ID16
Page 71
Section 4-3
Transistor Remote I/O Terminals Dimensions
The following diagram shows the dimensions for the DRT1-OD16 and DRT1OD16-1 Remote Output Terminals. All dimensions are in mm. Approx. 73
12
50 max.
(With connector attached)
40 max.
150 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
140 ± 0.3
4-3-6
Transistor Remote I/O Terminal with 8 Inputs and 8 Outputs: DRT1-MD16 (NPN)
Input Specifications Item
56
Specification
Model
DRT1-MD16
Internal I/O common Input points
NPN 8 points
ON voltage OFF voltage
15 V DC min. (between each input terminal and IN V) 5 V DC max. (between each input terminal and IN V)
OFF current Input current
1 mA max. 10 mA max./point
ON delay time OFF delay time
1.5 ms max. 1.5 ms max.
Number of circuits
8 points with one common
Page 72
Section 4-3
Transistor Remote I/O Terminals Output Specifications Item
Specification
Model
DRT1-MD16
Internal I/O common Output points
NPN 8 points
Rated output current Residual voltage
0.3 A/point, 2.4 A/common 1.2 V max. (at 0.3 A, between each output terminal and OUT G)
Leakage current ON delay time
0.1 mA max. 0.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with one common
Components
1
3
5
7
9
11
13
15
0
2
4
6
8
10
12
14
I/O Indicators Indicate the status of each input and output. The left half are for inputs; the right half are for outputs. (Lit when the input or output is ON.)
DeviceNet Indicators (Refer to page 312.)
Terminal block
DIN track mounting hooks Communications connector DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error
57
Page 73
Section 4-3
Transistor Remote I/O Terminals Internal Circuits
The following diagram shows the internal circuits for the DRT1-MD16 Remote I/O Terminal. Physical layer Photo-
Transceiver coupler
1
V+ 2 3
V 24 V DC
Photocoupler
NC
DRAIN
IN
Photocoupler
TXD
CAN_H 4
0
CAN_L
RXD
5
V−
Non-isolated power supply
5V
Photocoupler
5V @V
Internal circuitry
To physical layer SOURCE 24 V DC +
5V
DC-DC converter (Isolated)
SOURCE 24 V DC −
.1 . . .
G
1MS 1NS
@V
Voltage step-down
Photocoupler
OUT V 24 V DC 0
. . . .
Photocoupler
. . .
1
G
0V
Wiring
The following diagram shows the wiring of the DRT1-MD16 Remote I/O Terminal. SOURCE 24 V DC
24 V DC
12
13
IN V
+ 1
2
−
OUT
15
1 3
IN G
−
IN 14
3 4
0
16
17
5 5
2
18
7 6
4
1 7
6
19
3 8
0
21
5 9
2
24 V DC 20
22
10
4
OUT V
7 11
6
OUT G
+
Internal circuits power supply
− Blue (black)
Brown (white)
Power supply for inputs
Blue (black)
Brown (red)
+ Black (white)
−
3-wire sensor with 2-wire sensor NPN output (e.g., limit switch) (photoelectric or proximity sensor)
Note
58
+
Power supply for outputs Solenoid, valve, etc.
1. IN V is not connected internally to OUT V (terminals 13 and 22), and IN G is not connected internally to OUT G (terminals 2 and 11). Connect them carefully.
Page 74
Section 4-3
Transistor Remote I/O Terminals
2. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses. Dimensions
The following diagram shows the dimensions for the DRT1-MD16 Remote I/O Terminals. All dimensions are in mm. Approx.73 (With connector attached) DRT1-MD16
No.
50 max.
REMOTE TERMINAL 24VDC
MS
1
3
5
7
1
3
5
7
0
2
4
6
0
2
4
6
IN OUT
NS
2
3
4
5
6
7
0
1
2
3
4
5
6
7
12
0
1
150 max.
40 max.
Mounting holes
40±0.3
Two, 4.2 dia. or M4
140±0.3
4-3-7
Mounting in Control Panels Either of the following methods can be used to mount an Remote I/O Terminal in a control panel.
Using Screws
Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Remote I/O Terminal with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.
Using DIN Track
Mount the back of the Remote I/O Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates.
59
Page 75
Section 4-3
Transistor Remote I/O Terminals Connecting End Plates
Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2
1
End Plate
Note Always attach End Plate to both ends of Slaves connected to DIN Track. Mounting Direction
Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical
4-3-8
Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines The internal circuit power supplies, I/O power supplies, and I/O lines are all wired to M3 screw terminals. Connect M3 crimp terminals and then connect them to the terminal block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.
60
6.0 mm max.
Page 76
Section 4-3
Transistor Remote I/O Terminals Wiring the Internal Power Supply
Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the internal power supply for a DRT1-ID16 Remote Input Terminal. DRT1-ID16
No.
REMOTE TERMINAL 24VDC
−
Wiring the I/O Power Supply
1
3
5
7
9
11
13
15
0
2
4
6
8
10
12
14
+
Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the I/O power supply for a DRT1-ID16 Remote Input Terminal. DRT1-ID16
No.
REMOTE TERMINAL 24VDC
1
3
5
7
9
11
13
15
0
2
4
6
8
10
12
14
−
Wiring I/O
+
Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block and external I/O wiring. The following example shows the wiring to input 0 on a DRT1-ID16 Remote Input Terminal. DRT1-ID16 REMOTE TERMINAL 24VDC
No.
1
3
5
7
9
11
13
15
0
2
4
6
8
10
12
14
61
Page 77
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
4-4-1
Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Rotary switches Baud rate setting: Pins 1 and 2 Output hold/clear setting:Pin 4 (affects only outputs) Baud rate setting
ON
Reserved (Always OFF.) Output hold/clear setting for communications errors (for outputs)
1 2 3 4 5 6 7 8
2 3
4
0 1
7 8
2 3
5 6
9
4
9
0 1
Node address setting (×1) Node address setting (×10)
Node Address Settings
The node address of the Remote I/O Terminal is set with two rotary switches. The 10s digit is set on the left and the 1s digit is set on the right. Any node address within the setting range can be used as long as it isn’t already set on another node. Note The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).
Baud Rate Setting
Pins 1 and 2 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 1
Note
Pin 2
Baud rate
OFF ON
OFF OFF
125 kbps (default) 250 kbps
OFF ON
ON ON
500 kbps Not allowed.
1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.
62
Page 78
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The functions of pins 3 and 4 differ for inputs and outputs, as shown in the following diagram. ON
Setting Pins 3 and 4
3 4 Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF
Pin 3:
Reserved (Always OFF)
Pin 4:
As follows:
Inputs: Outputs: OFF (Clear): ON (Hold):
No function (Always OFF) Hold/Clear outputs for communications error All output data from the Master will be cleared to 0 when a communications error occurs. All output data from the Master will be retained when a communications error occurs.
Pins 3 and 4 are factory-set to OFF.
4-4-2
Transistor Remote Input Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-ID16T (NPN) and DRT1-ID16T-1 (PNP)
Input Specifications Item
Specification DRT1-ID16T-1
Model
DRT1-ID16T
Internal I/O common Input points
NPN 16 points
PNP
ON voltage
15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V) 1.0 mA max.
15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)
OFF voltage OFF current Input current
6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC
ON delay time OFF delay time
1.5 ms max. 1.5 ms max.
Number of circuits
8 points with two commons
63
Page 79
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-ID16T and DRT1-ID16T-1 Rotary switches (Refer to page 62.) Set the node address.
DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pins 3 and 4: Reserved (Always OFF.) Input Indicators Indicate the input status of each contact. (Lit when the input is ON.)
DeviceNet Indicators (Refer to page 312.)
DRT1-ID16T
0
REMOTE TERMINAL DC24V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON DR0 DR1 NC NC
IN
MS NS
Circuit removal screws.
Terminal block
Communications connector Internal power supply terminals
Internal Circuits
DIN track mounting hooks
The following diagram shows the internal circuits for the DRT1-ID16T Remote Input Terminal. Photocoupler
V1 24 V DC G1
V−
V1
CANL Physical layer
Photocoupler
CANH V+
Internal circuitry
DRAIN
Photocoupler
Input (0 to 7) G1 V2 24 V DC G2
SOURCE 24V DC + SOURCE 24V DC −
64
I/O power supply
V2 DC-DC converter (Isolated)
Input (8 to 15) Photocoupler G2
I/O power supply
Page 80
Section 4-4
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks
The following diagram shows the internal circuits for the DRT1-ID16T-1 Remote Input Terminal. Photocoupler
I/O power supply
V1 24 V DC G1
V−
V1
CANL Physical layer
DRAIN
Input (0 to 7)
Photocoupler
CANH
Internal circuitry
V+
G1
Photocoupler
V2 24 V DC
I/O power supply
G2 SOURCE 24 V DC +
V2 DC-DC converter (Isolated)
SOURCE 24 V DC −
Input (8 to 15)
G2 Photocoupler
Wiring
The following diagram shows the wiring of the DRT1-ID16T Remote Input Terminal.
−
+
+
−
+
0
1
7
V1
V1
V1
V1
G1
G1
G1
G1
−
+
8
9
15
V2
V2
V2
V2
G2
G2
G2
G2
−
2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)
Brown (red)
Black (white)
Blue (black)
Blue (black)
Brown (white)
Black (white)
Brown (red)
Blue (black)
Blue (black)
Brown (white)
Internal circuits power supply
2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)
65