Page 71

Section 4-3

Transistor Remote I/O Terminals Dimensions

The following diagram shows the dimensions for the DRT1-OD16 and DRT1OD16-1 Remote Output Terminals. All dimensions are in mm. Approx. 73

12

50 max.

(With connector attached)

40 max.

150 max.

Mounting holes

40 ± 0.3

Two, 4.2 dia. or M4

140 ± 0.3

4-3-6

Transistor Remote I/O Terminal with 8 Inputs and 8 Outputs: DRT1-MD16 (NPN)

Input Specifications Item

56

Specification

Model

DRT1-MD16

Internal I/O common Input points

NPN 8 points

ON voltage OFF voltage

15 V DC min. (between each input terminal and IN V) 5 V DC max. (between each input terminal and IN V)

OFF current Input current

1 mA max. 10 mA max./point

ON delay time OFF delay time

1.5 ms max. 1.5 ms max.

Number of circuits

8 points with one common

Page 72

Section 4-3

Transistor Remote I/O Terminals Output Specifications Item

Specification

Model

DRT1-MD16

Internal I/O common Output points

NPN 8 points

Rated output current Residual voltage

0.3 A/point, 2.4 A/common 1.2 V max. (at 0.3 A, between each output terminal and OUT G)

Leakage current ON delay time

0.1 mA max. 0.5 ms max.

OFF delay time Number of circuits

1.5 ms max. 8 points with one common

Components

1

3

5

7

9

11

13

15

0

2

4

6

8

10

12

14

I/O Indicators Indicate the status of each input and output. The left half are for inputs; the right half are for outputs. (Lit when the input or output is ON.)

DeviceNet Indicators (Refer to page 312.)

Terminal block

DIN track mounting hooks Communications connector DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error

57

Page 73

Section 4-3

Transistor Remote I/O Terminals Internal Circuits

The following diagram shows the internal circuits for the DRT1-MD16 Remote I/O Terminal. Physical layer Photo-

Transceiver coupler

1

V+ 2 3

V 24 V DC

Photocoupler

NC

DRAIN

IN

Photocoupler

TXD

CAN_H 4

0

CAN_L

RXD

5

V−

Non-isolated power supply

5V

Photocoupler

5V @V

Internal circuitry

To physical layer SOURCE 24 V DC +

5V

DC-DC converter (Isolated)

SOURCE 24 V DC −

.1 . . .

G

1MS 1NS

@V

Voltage step-down

Photocoupler

OUT V 24 V DC 0

. . . .

Photocoupler

. . .

1

G

0V

Wiring

The following diagram shows the wiring of the DRT1-MD16 Remote I/O Terminal. SOURCE 24 V DC

24 V DC

12

13

IN V

+ 1

2

−

OUT

15

1 3

IN G

−

IN 14

3 4

0

16

17

5 5

2

18

7 6

4

1 7

6

19

3 8

0

21

5 9

2

24 V DC 20

22

10

4

OUT V

7 11

6

OUT G

+

Internal circuits power supply

− Blue (black)

Brown (white)

Power supply for inputs

Blue (black)

Brown (red)

+ Black (white)

−

3-wire sensor with 2-wire sensor NPN output (e.g., limit switch) (photoelectric or proximity sensor)

Note

58

+

Power supply for outputs Solenoid, valve, etc.

1. IN V is not connected internally to OUT V (terminals 13 and 22), and IN G is not connected internally to OUT G (terminals 2 and 11). Connect them carefully.

Page 74

Section 4-3

Transistor Remote I/O Terminals

2. Line colors have been changed accompanying changes in JIS standards for photoelectric and proximity sensors. Previous colors are given in parentheses. Dimensions

The following diagram shows the dimensions for the DRT1-MD16 Remote I/O Terminals. All dimensions are in mm. Approx.73 (With connector attached) DRT1-MD16

No.

50 max.

REMOTE TERMINAL 24VDC

MS

1

3

5

7

1

3

5

7

0

2

4

6

0

2

4

6

IN OUT

NS

2

3

4

5

6

7

0

1

2

3

4

5

6

7

12

0

1

150 max.

40 max.

Mounting holes

40±0.3

Two, 4.2 dia. or M4

140±0.3

4-3-7

Mounting in Control Panels Either of the following methods can be used to mount an Remote I/O Terminal in a control panel.

Using Screws

Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Remote I/O Terminal with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.

Using DIN Track

Mount the back of the Remote I/O Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates.

59

Page 75

Section 4-3

Transistor Remote I/O Terminals Connecting End Plates

Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2

1

End Plate

Note Always attach End Plate to both ends of Slaves connected to DIN Track. Mounting Direction

Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical

4-3-8

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines The internal circuit power supplies, I/O power supplies, and I/O lines are all wired to M3 screw terminals. Connect M3 crimp terminals and then connect them to the terminal block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.

60

6.0 mm max.

Page 76

Section 4-3

Transistor Remote I/O Terminals Wiring the Internal Power Supply

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the internal power supply for a DRT1-ID16 Remote Input Terminal. DRT1-ID16

No.

REMOTE TERMINAL 24VDC

−

Wiring the I/O Power Supply

1

3

5

7

9

11

13

15

0

2

4

6

8

10

12

14

+

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the I/O power supply for a DRT1-ID16 Remote Input Terminal. DRT1-ID16

No.

REMOTE TERMINAL 24VDC

1

3

5

7

9

11

13

15

0

2

4

6

8

10

12

14

−

Wiring I/O

+

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block and external I/O wiring. The following example shows the wiring to input 0 on a DRT1-ID16 Remote Input Terminal. DRT1-ID16 REMOTE TERMINAL 24VDC

No.

1

3

5

7

9

11

13

15

0

2

4

6

8

10

12

14

61

Page 77

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

4-4-1

Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Rotary switches Baud rate setting: Pins 1 and 2 Output hold/clear setting:Pin 4 (affects only outputs) Baud rate setting

ON

Reserved (Always OFF.) Output hold/clear setting for communications errors (for outputs)

1 2 3 4 5 6 7 8

2 3

4

0 1

7 8

2 3

5 6

9

4

9

0 1

Node address setting (×1) Node address setting (×10)

Node Address Settings

The node address of the Remote I/O Terminal is set with two rotary switches. The 10s digit is set on the left and the 1s digit is set on the right. Any node address within the setting range can be used as long as it isn’t already set on another node. Note The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

Pins 1 and 2 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 1

Note

Pin 2

Baud rate

OFF ON

OFF OFF

125 kbps (default) 250 kbps

OFF ON

ON ON

500 kbps Not allowed.

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.

62

Page 78

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The functions of pins 3 and 4 differ for inputs and outputs, as shown in the following diagram. ON

Setting Pins 3 and 4

3 4 Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF

Pin 3:

Reserved (Always OFF)

Pin 4:

As follows:

Inputs: Outputs: OFF (Clear): ON (Hold):

No function (Always OFF) Hold/Clear outputs for communications error All output data from the Master will be cleared to 0 when a communications error occurs. All output data from the Master will be retained when a communications error occurs.

Pins 3 and 4 are factory-set to OFF.

4-4-2

Transistor Remote Input Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-ID16T (NPN) and DRT1-ID16T-1 (PNP)

Input Specifications Item

Specification DRT1-ID16T-1

Model

DRT1-ID16T

Internal I/O common Input points

NPN 16 points

PNP

ON voltage

15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V) 1.0 mA max.

15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)

OFF voltage OFF current Input current

6.0 mA max./point at 24 V DC 3.0 mA min./point at 17 V DC

ON delay time OFF delay time

1.5 ms max. 1.5 ms max.

Number of circuits

8 points with two commons

63

Page 79

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Components of the DRT1-ID16T and DRT1-ID16T-1 Rotary switches (Refer to page 62.) Set the node address.

DIP switch (Refer to page 62.) Pins 1 and 2: Baud rate setting Pins 3 and 4: Reserved (Always OFF.) Input Indicators Indicate the input status of each contact. (Lit when the input is ON.)

DeviceNet Indicators (Refer to page 312.)

DRT1-ID16T

0

REMOTE TERMINAL DC24V

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

ON DR0 DR1 NC NC

IN

MS NS

Circuit removal screws.

Terminal block

Communications connector Internal power supply terminals

Internal Circuits

DIN track mounting hooks

The following diagram shows the internal circuits for the DRT1-ID16T Remote Input Terminal. Photocoupler

V1 24 V DC G1

V−

V1

CANL Physical layer

Photocoupler

CANH V+

Internal circuitry

DRAIN

Photocoupler

Input (0 to 7) G1 V2 24 V DC G2

SOURCE 24V DC + SOURCE 24V DC −

64

I/O power supply

V2 DC-DC converter (Isolated)

Input (8 to 15) Photocoupler G2

I/O power supply

Page 80

Section 4-4

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

The following diagram shows the internal circuits for the DRT1-ID16T-1 Remote Input Terminal. Photocoupler

I/O power supply

V1 24 V DC G1

V−

V1

CANL Physical layer

DRAIN

Input (0 to 7)

Photocoupler

CANH

Internal circuitry

V+

G1

Photocoupler

V2 24 V DC

I/O power supply

G2 SOURCE 24 V DC +

V2 DC-DC converter (Isolated)

SOURCE 24 V DC −

Input (8 to 15)

G2 Photocoupler

Wiring

The following diagram shows the wiring of the DRT1-ID16T Remote Input Terminal.

−

+

+

−

+

0

1

7

V1

V1

V1

V1

G1

G1

G1

G1

−

+

8

9

15

V2

V2

V2

V2

G2

G2

G2

G2

−

2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)

Brown (red)

Black (white)

Blue (black)

Blue (black)

Brown (white)

Black (white)

Brown (red)

Blue (black)

Blue (black)

Brown (white)

Internal circuits power supply

2-wire sensor 3-wire sensor with (e.g., limit switch) NPN output (photoelectric or proximity sensor)

65