Page 61
Section 4-3
Transistor Remote I/O Terminals Components of the DRT1-ID16 and DRT1-ID16-1
Input indicators Indicate the status of each contact. (Lit when the input is ON.) DeviceNet Indicators (Refer to page 312.) Terminal block
DIN track mounting hooks Communications connector DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pins 9 and 10: Reserved (Always OFF.)
Internal Circuits The following diagram shows the internal circuits for the DRT1-ID16 Remote Input Terminal. Photocoupler
Photocoupler
V+
DRAIN CAN L
Physical layer
0 Photocoupler
V–
SOURCE 24 V DC + SOURCE 24 V DC –
46
DC-DC converter (Isolated)
Internal circuitry
CAN H
V 24 V DC V 24 V DC
1 Photocoupler
G G
Page 62
Section 4-3
Transistor Remote I/O Terminals
The following diagram shows the internal circuits for the DRT1-ID16-1 Remote Input Terminal. V Photocoupler
V 24 V DC Photocoupler
0
V+ Physical layer
DRAIN CAN L
1 Photocoupler
V–
Internal circuitry
CAN H
Photocoupler
G SOURCE 24 V DC +
G
DC-DC converter (Isolated)
SOURCE 24 V DC –
Wiring
The following diagram shows the wiring of the DRT1-ID16 Remote Input Terminal. SOURCE 24 V DC
24 V DC
+
– –
+
Internal circuits power supply
NPN output 3-wire sensor (photoelectric or proximity sensor)
2-wire sensor (limit switch)
Blue (black)
Black (white)
Brown (red)
Blue (black)
Brown (white)
Blue (black)
I/O power supply
Black (white)
+ Brown (red)
–
NPN output 3-wire sensor (photoelectric or proximity sensor)
47
Page 63
Section 4-3
Transistor Remote I/O Terminals
The following diagram shows the wiring of the DRT1-ID16-1 Remote Input Terminal. SOURCE 24 V DC
24 V DC
+
– –
+
Internal circuits power supply
PNP output 3-wire sensor (photoelectric or proximity sensor)
Note
2-wire sensor (limit switch)
Brown (red)
Black (white)
Blue (black)
Brown (red)
Black (white)
Blue (black)
Brown (white)
Blue (black)
Brown (white)
Blue (black)
Brown (red)
Black (white)
Black (blue) Brown (red)
I/O power supply
Black (white)
+ Blue (black)
–
PNP output 3-wire sensor (photoelectric or proximity sensor)
1. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors. 2. The V terminals (terminal numbers 13 and 22) are connected internally, as are the G terminals (terminal numbers 2 and 11). When I/O power is supplied to terminals 13 and 2, power can be supplied to sensors from terminals 22 and 11. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead.
48
Page 64
Section 4-3
Transistor Remote I/O Terminals Dimensions
The following diagram shows the dimensions for the DRT1-ID16 and DRT1ID16-1 Remote Input Terminals. All dimensions are in mm. Approx. 73
12
50 max.
(With connector attached)
150 max.
40 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
140 ± 0.3
4-3-4
Transistor Remote Output Terminals with 8 Points: DRT1-OD08 (NPN) and DRT1-OD08-1 (PNP)
Output Specifications Item
Specification DRT1-OD08-1
Model
DRT1-OD08
Internal I/O common Output points
NPN PNP 8 points (Master Unit uses one word)
Rated output current Residual voltage
Leakage current
0.3 A/point, 2.4 A/common 1.2 V max. (at 0.3 A, 1.2 V max. (at 0.3 A, between each output termi- between each output terminal and G) nal and V) 0.1 mA max.
ON delay time OFF delay time
0.5 ms max. 1.5 ms max.
Number of circuits
8 points with one common
49
Page 65
Section 4-3
Transistor Remote I/O Terminals Components of the DRT1-OD08 and DRT1-OD08-1
Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
DeviceNet Indicators (Refer to page 312.) Terminal block
DIN track mounting hooks
Mounting screw holes
Communications connector
DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error
Internal Circuits
The following diagram shows the internal circuits for the DRT1-OD08 Remote Output Terminal. Photocoupler
Voltage step-down
V+ CAN H DRAIN CAN L
Photocoupler Physical layer
Photocoupler
SOURCE 24 V DC –
V 24 V DC V 24 V DC 0 1
Internal circuitry
V–
SOURCE 24 V DC +
V 24 V DC
Photocoupler
DC-DC converter (Isolated)
G
50
Page 66
Section 4-3
Transistor Remote I/O Terminals
The following diagram shows the internal circuits for the DRT1-OD08-1 Remote Output Terminal. Photocoupler V 24 V DC
V+
DRAIN CAN L
Physical layer
1
V–
SOURCE 24 V DC + SOURCE 24 V DC –
0
Photocoupler Internal circuitry
CAN H
Photocoupler
Photocoupler
DC-DC converter (Isolated)
G G Voltage step-down
Wiring
The following diagram shows the wiring of the DRT1-OD08 Remote Output Terminal. SOURCE 24 V DC 24 V DC +
– –
+
Internal circuits power supply –
+
I/O power supply Solenoid
Valve
Solenoid
Note The V terminals (terminal numbers 7, 9, and 14) are connected internally. When I/O power is supplied to terminals 9, power can be supplied to output devices from terminals 7 and 14. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead.
51
Page 67
Section 4-3
Transistor Remote I/O Terminals
The following diagram shows the wiring of the DRT1-OD08-1 Remote Output Terminal. SOURCE 24 V DC 24 V DC +
G
– –
G
+
Internal circuits power supply –
+
I/O power supply Solenoid
Valve
Solenoid
Note The G terminals (terminal numbers 2, 7, and 14) are connected internally. When I/O power is supplied to terminal 2, power can be supplied to output devices from terminals 7 and 14. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead. Dimensions
The following diagram shows the dimensions for the DRT1-OD08 and DRT1OD08-1 Remote Output Terminals. All dimensions are in mm. Approx. 73
12
50 max.
(With connector attached)
125 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
115 ± 0.3
52
40 max.
Page 68
Section 4-3
Transistor Remote I/O Terminals
4-3-5
Transistor Remote Output Terminals with 16 Points: DRT1-OD16 (NPN) and DRT1-OD16-1 (PNP)
Output Specifications Item
Specification DRT1-OD16-1
Model
DRT1-OD16
Internal I/O common Output points
NPN 16 points
Rated output current Residual voltage
0.3 A/point, 2.4 A/common 1.2 V max. (at 0.3 A, 1.2 V max. (at 0.3 A, between each output termi- between each output terminal and G) nal and V)
Leakage current ON delay time
0.1 mA max. 0.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 16 points with one common
PNP
Components of the DRT1-OD16 and DRT1-OD16-1 Output indicators Indicate the output status of each contact. (Lit when the output is ON.) DeviceNet Indicators (Refer to page 312.) Terminal block
DIN track mounting hooks Communications connector DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error
53
Page 69
Section 4-3
Transistor Remote I/O Terminals Internal Circuits
The following diagram shows the internal circuits for the DRT1-OD16 Remote Output Terminal. Photocoupler
Voltage step-down
V+ CAN H DRAIN CAN L
V 24 V DC Photocoupler Physical layer
SOURCE 24 V DC –
V 24 V DC
Photocoupler
0 1 Internal circuitry
V–
SOURCE 24 V DC +
V 24 V DC
Photocoupler
DC-DC converter (Isolated)
G
The following diagram shows the internal circuits for the DRT1-OD16-1 Remote Output Terminal. Photocoupler V+
V 24 V DC Photocoupler
CAN H DRAIN CAN L
Physical layer
Photocoupler
SOURCE 24 V DC –
1
Internal circuitry
V–
SOURCE 24 V DC +
0
Photocoupler
DC-DC converter (Isolated)
G G Voltage step-down
54
Page 70
Section 4-3
Transistor Remote I/O Terminals Wiring
The following diagram shows the wiring of the DRT1-OD16 Remote Output Terminal. SOURCE 24 V DC 24 V DC +
– –
+
Internal circuits power supply –
+
I/O power supply Solenoid
Valve
Solenoid
Note The V terminals (terminal numbers 11, 13, and 22) are connected internally. When I/O power is supplied to terminal 13, power can be supplied to output devices from terminals 22 and 11. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead. The following diagram shows the wiring of the DRT1-OD16-1 Remote Output Terminal. SOURCE 24 V DC 24 V DC +
G
– –
G
+
Internal circuits power supply –
+
I/O power supply Solenoid
Valve
Solenoid
Note The G terminals (terminal numbers 2, 11, and 22) are connected internally. When I/O power is supplied to terminal 2, power can be supplied to output devices from terminals 22 and 11. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead.
55