For the Omron DRT1-ID16

Page 61

Section 4-3

Transistor Remote I/O Terminals Components of the DRT1-ID16 and DRT1-ID16-1

Input indicators Indicate the status of each contact. (Lit when the input is ON.) DeviceNet Indicators (Refer to page 312.) Terminal block

DIN track mounting hooks Communications connector DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pins 9 and 10: Reserved (Always OFF.)

Internal Circuits The following diagram shows the internal circuits for the DRT1-ID16 Remote Input Terminal. Photocoupler

Photocoupler

V+

DRAIN CAN L

Physical layer

0 Photocoupler

V–

SOURCE 24 V DC + SOURCE 24 V DC –

46

DC-DC converter (Isolated)

Internal circuitry

CAN H

V 24 V DC V 24 V DC

1 Photocoupler

G G

Page 62

Section 4-3

Transistor Remote I/O Terminals

The following diagram shows the internal circuits for the DRT1-ID16-1 Remote Input Terminal. V Photocoupler

V 24 V DC Photocoupler

0

V+ Physical layer

DRAIN CAN L

1 Photocoupler

V–

Internal circuitry

CAN H

Photocoupler

G SOURCE 24 V DC +

G

DC-DC converter (Isolated)

SOURCE 24 V DC –

Wiring

The following diagram shows the wiring of the DRT1-ID16 Remote Input Terminal. SOURCE 24 V DC

24 V DC

+

– –

+

Internal circuits power supply

NPN output 3-wire sensor (photoelectric or proximity sensor)

2-wire sensor (limit switch)

Blue (black)

Black (white)

Brown (red)

Blue (black)

Brown (white)

Blue (black)

I/O power supply

Black (white)

+ Brown (red)

–

NPN output 3-wire sensor (photoelectric or proximity sensor)

47

Page 63

Section 4-3

Transistor Remote I/O Terminals

The following diagram shows the wiring of the DRT1-ID16-1 Remote Input Terminal. SOURCE 24 V DC

24 V DC

+

– –

+

Internal circuits power supply

PNP output 3-wire sensor (photoelectric or proximity sensor)

Note

2-wire sensor (limit switch)

Brown (red)

Black (white)

Blue (black)

Brown (red)

Black (white)

Blue (black)

Brown (white)

Blue (black)

Brown (white)

Blue (black)

Brown (red)

Black (white)

Black (blue) Brown (red)

I/O power supply

Black (white)

+ Blue (black)

–

PNP output 3-wire sensor (photoelectric or proximity sensor)

1. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors. 2. The V terminals (terminal numbers 13 and 22) are connected internally, as are the G terminals (terminal numbers 2 and 11). When I/O power is supplied to terminals 13 and 2, power can be supplied to sensors from terminals 22 and 11. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead.

48

Page 64

Section 4-3

Transistor Remote I/O Terminals Dimensions

The following diagram shows the dimensions for the DRT1-ID16 and DRT1ID16-1 Remote Input Terminals. All dimensions are in mm. Approx. 73

12

50 max.

(With connector attached)

150 max.

40 max.

Mounting holes

40 ± 0.3

Two, 4.2 dia. or M4

140 ± 0.3

4-3-4

Transistor Remote Output Terminals with 8 Points: DRT1-OD08 (NPN) and DRT1-OD08-1 (PNP)

Output Specifications Item

Specification DRT1-OD08-1

Model

DRT1-OD08

Internal I/O common Output points

NPN PNP 8 points (Master Unit uses one word)

Rated output current Residual voltage

Leakage current

0.3 A/point, 2.4 A/common 1.2 V max. (at 0.3 A, 1.2 V max. (at 0.3 A, between each output termi- between each output terminal and G) nal and V) 0.1 mA max.

ON delay time OFF delay time

0.5 ms max. 1.5 ms max.

Number of circuits

8 points with one common

49

Page 65

Section 4-3

Transistor Remote I/O Terminals Components of the DRT1-OD08 and DRT1-OD08-1

Output indicators Indicate the output status of each contact. (Lit when the output is ON.)

DeviceNet Indicators (Refer to page 312.) Terminal block

DIN track mounting hooks

Mounting screw holes

Communications connector

DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error

Internal Circuits

The following diagram shows the internal circuits for the DRT1-OD08 Remote Output Terminal. Photocoupler

Voltage step-down

V+ CAN H DRAIN CAN L

Photocoupler Physical layer

Photocoupler

SOURCE 24 V DC –

V 24 V DC V 24 V DC 0 1

Internal circuitry

V–

SOURCE 24 V DC +

V 24 V DC

Photocoupler

DC-DC converter (Isolated)

G

50

Page 66

Section 4-3

Transistor Remote I/O Terminals

The following diagram shows the internal circuits for the DRT1-OD08-1 Remote Output Terminal. Photocoupler V 24 V DC

V+

DRAIN CAN L

Physical layer

1

V–

SOURCE 24 V DC + SOURCE 24 V DC –

0

Photocoupler Internal circuitry

CAN H

Photocoupler

Photocoupler

DC-DC converter (Isolated)

G G Voltage step-down

Wiring

The following diagram shows the wiring of the DRT1-OD08 Remote Output Terminal. SOURCE 24 V DC 24 V DC +

– –

+

Internal circuits power supply –

+

I/O power supply Solenoid

Valve

Solenoid

Note The V terminals (terminal numbers 7, 9, and 14) are connected internally. When I/O power is supplied to terminals 9, power can be supplied to output devices from terminals 7 and 14. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead.

51

Page 67

Section 4-3

Transistor Remote I/O Terminals

The following diagram shows the wiring of the DRT1-OD08-1 Remote Output Terminal. SOURCE 24 V DC 24 V DC +

G

– –

G

+

Internal circuits power supply –

+

I/O power supply Solenoid

Valve

Solenoid

Note The G terminals (terminal numbers 2, 7, and 14) are connected internally. When I/O power is supplied to terminal 2, power can be supplied to output devices from terminals 7 and 14. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead. Dimensions

The following diagram shows the dimensions for the DRT1-OD08 and DRT1OD08-1 Remote Output Terminals. All dimensions are in mm. Approx. 73

12

50 max.

(With connector attached)

125 max.

Mounting holes

40 ± 0.3

Two, 4.2 dia. or M4

115 ± 0.3

52

40 max.

Page 68

Section 4-3

Transistor Remote I/O Terminals

4-3-5

Transistor Remote Output Terminals with 16 Points: DRT1-OD16 (NPN) and DRT1-OD16-1 (PNP)

Output Specifications Item

Specification DRT1-OD16-1

Model

DRT1-OD16

Internal I/O common Output points

NPN 16 points

Rated output current Residual voltage

0.3 A/point, 2.4 A/common 1.2 V max. (at 0.3 A, 1.2 V max. (at 0.3 A, between each output termi- between each output terminal and G) nal and V)

Leakage current ON delay time

0.1 mA max. 0.5 ms max.

OFF delay time Number of circuits

1.5 ms max. 16 points with one common

PNP

Components of the DRT1-OD16 and DRT1-OD16-1 Output indicators Indicate the output status of each contact. (Lit when the output is ON.) DeviceNet Indicators (Refer to page 312.) Terminal block

DIN track mounting hooks Communications connector DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error

53

Page 69

Section 4-3

Transistor Remote I/O Terminals Internal Circuits

The following diagram shows the internal circuits for the DRT1-OD16 Remote Output Terminal. Photocoupler

Voltage step-down

V+ CAN H DRAIN CAN L

V 24 V DC Photocoupler Physical layer

SOURCE 24 V DC –

V 24 V DC

Photocoupler

0 1 Internal circuitry

V–

SOURCE 24 V DC +

V 24 V DC

Photocoupler

DC-DC converter (Isolated)

G

The following diagram shows the internal circuits for the DRT1-OD16-1 Remote Output Terminal. Photocoupler V+

V 24 V DC Photocoupler

CAN H DRAIN CAN L

Physical layer

Photocoupler

SOURCE 24 V DC –

1

Internal circuitry

V–

SOURCE 24 V DC +

0

Photocoupler

DC-DC converter (Isolated)

G G Voltage step-down

54

Page 70

Section 4-3

Transistor Remote I/O Terminals Wiring

The following diagram shows the wiring of the DRT1-OD16 Remote Output Terminal. SOURCE 24 V DC 24 V DC +

– –

+

Internal circuits power supply –

+

I/O power supply Solenoid

Valve

Solenoid

Note The V terminals (terminal numbers 11, 13, and 22) are connected internally. When I/O power is supplied to terminal 13, power can be supplied to output devices from terminals 22 and 11. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead. The following diagram shows the wiring of the DRT1-OD16-1 Remote Output Terminal. SOURCE 24 V DC 24 V DC +

G

– –

G

+

Internal circuits power supply –

+

I/O power supply Solenoid

Valve

Solenoid

Note The G terminals (terminal numbers 2, 11, and 22) are connected internally. When I/O power is supplied to terminal 2, power can be supplied to output devices from terminals 22 and 11. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead.

55