For the Omron DRT1-ID16

Page 51

Section 4-2

Connecting Communications Cables to General-purpose Slaves

6. Tighten the line set screws for each line in the connector. Tighten the screws to a torque of 0.25 to 0.3 N⋅m. You will not be able to tighten these screws with a normal screwdriver, which narrows to a point at the end. You will need a screwdriver that is consistently thin for the entire length. Connector without Set Screws

Use a flat-blade screwdriver that is consistently thin at the end.

Crimp Terminals We recommend the following crimp terminals. • Phoenix Contact, AI-series Crimp Terminals

Crimp terminal

Wire

Insert the line into the terminal and then crimp. The following crimp tool is also available. Phoenix Contact, ZA3 Crimp Tool The OMRON XW4Z-00C Screwdriver is available for tightening the line set screws. The end of the screwdriver has the following dimensions. Side View

Front View

0.6 mm

3.5 mm

• Supplying Communications Power Using T-branch Taps Connect the V+ and V– of the power lines to the connectors in the same way as for the communications cables. If the communications power sup-

36

Page 52

Section 4-2

Connecting Communications Cables to General-purpose Slaves ply is in one location only, connect a shield to the connectors when fixing them, and ground to 100 Ω max. T-branch Tap or Power Supply Tap V+ CAN H Shield CAN L V–

Communications power supply

Communications cable

Ground (100 Ω max.)

FG

V– V+

Communications power supply Ground (100 Ω max.) Power supply with cable grounded (one location only)

4-2-2

Connecting Communications Cables to the Nodes Align the node connector with the cable connector and fully insert the projecting part of the cable connector into the node connector. Depending on the type of Slave used, the connectors are secured with screws or a connector band, or there is no component for securing the connectors. Always fix securely those connectors that can be secured. Master

Temperature Input Terminal Output Terminal Input Terminal

C200H I/O Link Unit RS-232C Unit

Securing Slave Connectors with Screws Tighten the screws fixing the connectors to a torque of 0.25 to 0.3 N⋅m. Securing Slave Connectors with Connector Bands Use the following procedure to secure connectors with connector bands.

37

Page 53

Section 4-2

Connecting Communications Cables to General-purpose Slaves 1,2,3...

1. Pull out the connector band from the Slave Unit. Slave

Connector band Slave

2. Lift up the connector band. 3. Insert the connector into the Slave Unit.

4. Wrap the connector band around the connector and secure firmly.

Note Multidrop connectors cannot be secured. Multi-drop Connections • Multi-drop Connections with Accessory Connector (Thin Cables Only) The connectors provided with the Units can be used for a multi-drop connection as long as thin cables are being used, just insert both lines into the same hole in the connector. Be sure to use crimp connectors on both lines. The following illustration shows a multi-drop connection for a connector without set screws.

When connecting two lines to the same hole, first place them together in one pressure-welded terminal as shown below.

Pressure-welded terminal for 2 lines

Cables

Pressure-welded terminal: Pheonix Contacts model AI-TWIN2X0.5-8WH (product number 3200933) Pressure-welding tool: Pheonix Contacts model UD6 (product number 1204436)

38

Page 54

Section 4-2

Connecting Communications Cables to General-purpose Slaves

• Multi-drop Connections with Special Connector (Thin or Thick Cables) A multi-drop wiring connector (sold separately) can be used to wire a multi-drop connector for either thin or thick cables. This multi-drop wiring connector is required to wire a multi-drop connection with thick cables, which are too thick for two lines to fit into the connector provided with the Units. The multi-drop wiring connector cannot always be used with Master Units or the CQM1 I/O Link Units because it may come into contact with the Units mounted next to the Master Unit or the CQM1 I/O Link Unit. If this happens, use a T-branch Tap to wire the connection.

4-2-3

Mounting Terminating Resistors Terminating Resistors must be used at both ends of the trunk line. Terminating Resistors • T-branch Tap Terminating Resistors A terminating resistor is included with the T-branch Tap. Clip the leads on the resistor to about 3 mm and insert it into the T-branch Tap as shown in the following diagram. The resistor can face in either direction.

• Terminal-block Terminating Resistors A terminating resistor is built into the Terminal-block Terminating Resistor. To connect the cable to the Terminating Resistor, attach standard M3 crimp terminals to the signal wires and securely screw the terminals to the Terminal-block Terminating Resistor. Tighten to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.

6.0 mm max.

39

Page 55

Section 4-3

Transistor Remote I/O Terminals

4-3

Transistor Remote I/O Terminals

4-3-1

Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Baud rate setting:

Pins 1 through 6 Pins 7 and 8

ON

Output hold/clear setting:Pin 10 (affects only outputs)

1 2 3 4 5 6 7 8 9 10 Output hold/clear setting for communications errors (for outputs)

Node address setting

Reserved (Always OFF.) Baud rate setting

Node Address Settings

The node address of the Remote I/O Terminal is set with pins 1 through 6 of the DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. DIP switch setting

Node address

Pin 6 Pin 5 Pin 4 Pin 3 Pin 2 Pin 1 0 0 0 0 0 0 0 (default) 0 0

0 0

0 0

0 0

0 1

1 0

1 2

: :

: :

1 1

1 1

1 1

1 1

0 1

1 0

61 62

1

1

1

1

1

1

63

0: OFF, 1: ON Note

1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

Pins 7 and 8 are used to set the baud rate as shown in the following table.

Note

Pin 7

Pin 8

OFF ON

OFF OFF

125 kbps (default) 250 kbps

Baud rate

OFF ON

ON ON

500 kbps Not allowed.

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (master and slaves) in the Network. Any slaves with baud rates different from the master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.

40

Page 56

Section 4-3

Transistor Remote I/O Terminals Setting Pins 9 and 10

The functions of pins 9 and 10 differ for inputs and outputs, as shown in the following diagram.

Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF

Pin 9:

Reserved (Always OFF)

Pin 10: As follows: Inputs: Outputs: OFF (Clear):

No function (Always OFF) Hold/Clear outputs for communications error All output data from the Master will be cleared to 0 when a communications error occurs.

ON (Hold):

All output data from the Master will be retained when a communications error occurs.

Pins 9 and 10 are factory-set to OFF.

4-3-2

Transistor Remote Input Terminals with 8 Points: DRT1-ID08 (NPN) and DRT1-ID08-1 (PNP)

Input Specifications Item

Specification

Model Internal I/O common

DRT1-ID08 NPN

Input points ON voltage

OFF current

8 points (allocated one word in Master) 15 V DC min. (between 15 V DC min. (between each input terminal and V) each input terminal and G) 5 V DC max. (between 5 V DC max. (between each input terminal and V) each input terminal and G) 1 mA max.

Input current ON delay time

10 mA max./point 1.5 ms max.

OFF delay time Number of circuits

1.5 ms max. 8 points with one common

OFF voltage

DRT1-ID08-1 PNP

41

Page 57

Section 4-3

Transistor Remote I/O Terminals Components of the DRT1-ID08 and DRT1-ID08-1

Input indicators Indicate the status of each contact. (Lit when the input is ON.)

DeviceNet Indicators (Refer to page 312.) Terminal block

DIN track mounting hooks

Communications connector

DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pins 9 and 10: Reserved (Always OFF.)

Internal Circuits The following diagram shows the internal circuits for the DRT1-ID08 Input Terminal. Photocoupler

Photocoupler

V+

DRAIN CAN L

Physical layer

0 Photocoupler

V–

SOURCE 24 V DC + SOURCE 24 V DC –

1 Internal circuitry

CAN H

V 24 V DC V 24 V DC

Photocoupler

DC-DC converter (Isolated) G G

42

Page 58

Section 4-3

Transistor Remote I/O Terminals

The following diagram shows the internal circuits for the DRT1-ID08-1 Remote Input Terminal. V

Photocoupler

V 24 V DC

Photocoupler

0

V+

DRAIN CAN L

Physical layer

1 Photocoupler

V–

Internal circuitry

CAN H

Photocoupler

G

The following diagram shows the wiring of the DRT1-ID08 Remote Input Terminal. SOURCE 24 V DC

24 V DC

+

– –

+

NPN output 3-wire sensor (photoelectric or proximity sensor)

2-wire sensor (limit switch)

Blue (black)

Black (white)

I/O power supply

Brown (red)

+

Blue (black)

–

Brown (white)

Internal circuits power supply Blue (black)

Wiring

Black (white)

SOURCE 24 V DC –

G

DC-DC converter (Isolated)

Brown (red)

SOURCE 24 V DC +

NPN output 3-wire sensor (photoelectric or proximity sensor)

43

Page 59

Section 4-3

Transistor Remote I/O Terminals

The following diagram shows the wiring of the DRT1-ID08-1 Remote Input Terminal. SOURCE 24 V DC

24 V DC

+

–

–

+

PNP output 3-wire sensor (photoelectric or proximity sensor)

Note

2-wire sensor (limit switch)

Brown (red)

Black (white)

Blue (black)

Blue (black)

Brown (red)

I/O power supply

Black (white)

+ Black (blue)

–

Brown (white)

Internal circuits power supply

PNP output 3-wire sensor (photoelectric or proximity sensor)

1. The V terminals (terminal numbers 9 and 14) are connected internally, as are the G terminals (terminal numbers 2 and 7). When I/O power is supplied to terminals 9 and 2, power can be supplied to sensors from terminals 14 and 7. When the power supply exceeds 1.2 A, the power supply should not be input through the terminals; an external power supply must be used instead. 2. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors.

44

Page 60

Section 4-3

Transistor Remote I/O Terminals Dimensions

The following diagram shows the dimensions for the DRT1-ID08 and DRT1ID08-1 Remote Input Terminals. All dimensions are in mm. Approx. 73

50 max.

(With connector attached)

125 max.

40 max.

Mounting holes

40 ± 0.3

Two, 4.2 dia. or M4

115 ± 0.3

4-3-3

Transistor Remote Input Terminals with 16 Points: DRT1-ID16 (NPN) and DRT1-ID16-1 (PNP)

Input Specifications Item

Specification DRT1-ID16-1

Model

DRT1-ID16

Internal I/O common Input points

NPN 16 points

PNP

ON voltage

15 V DC min. (between each input terminal and V)

15 V DC min. (between each input terminal and G)

OFF voltage

5 V DC max. (between each input terminal and V)

5 V DC max. (between each input terminal and G)

OFF current Input current

1 mA max. 10 mA max./point

ON delay time OFF delay time

1.5 ms max. 1.5 ms max.

Number of circuits

16 points with one common

45