The text of a manual · part 5 of 39

C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 41 to 50

Pages 41 to 50 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual

The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron DRT1-ID16

Page 41

Section 2-5

Checking Operations refer to the C200HX, C200HG, C200HE Programmable Controllers Operation Manual (W322). 35315 NEG Rightmost bit of temperature data

353 DM1000

35315 MOV (21) 353 DM1000

25315 BCD (24) Normally ON

DM1000 110

• Use the MVN(022) instruction to reverse data for displays that require positive logic. • Use the 7SEG(214) instruction in the I/O Unit instructions for dynamic displays. Checking I/O Links for C200H I/O Link Units

Read/Write Areas in the C200H I/O Link Unit are allocated by default to the words in the PLC that it is mounted to as follows: Read Area: Write Area:

IR 50 (1 word) IR 350 (1 word)

The C200H I/O Link Unit’s Read/Write Areas are normally linked to the Input/ Output Areas of the Master (the Input/Output Areas occupied by the C200H I/ O Link Unit in the Master Unit) as shown in the following diagram. Input Area Output area Master Unit

IR 057 IR 357

Slave IR 050 C200H I/O Link Unit

IR 350 Read Area Write Area

Connect the Peripheral Device to the PLC, monitor the changes in current positions, and check that the links are operating normally.

26

Page 42

SECTION 3 Common Slave Specifications This section provides specifications that are common to all Slaves. 3-1

Common Slave Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

28

3-1-1

Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .

28

3-1-2

MS and NS Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

29

27

Page 43

Section 3-1

Common Slave Specifications

3-1

Common Slave Specifications

3-1-1

Communications Specifications Item Communications protocol Supported connections (communications) Connection forms Baud rate

Specification DeviceNet Master-Slave: Remote I/O and explicit messages Both conform to DeviceNet specifications Combination of multi-drop and T-branch connections (for trunk or drop lines) 500 kbps, 250 kbps, or 125 kbps (switchable)

Communications media

Special 5-wire cables (2 signal lines, 2 power lines, 1 shield line)

Communications distances

Network length: 100 m max. (100 m max.) Drop line length: 6 m max. Total drop line length: 39 m max.

500 kbps

250 kbps

Network length: 250 m max. (100 m max.) Drop line length: 6 m max. Total drop line length: 78 m max. 125 kbps Network length: 500 m max. (100 m max.) Drop line length: 6 m max. Total drop line length: 156 m max. Parentheses indicate the length when Thin Cables are used. Communications power supply Max. number of nodes

11 to 25 V DC 64 nodes (including Configurator when used)

Max. number of Masters

Without Configurator: 1 With Configurator:

Max. number of Slaves

63 Slaves

Communications cycle time

Without Configurator: Input Slaves (16-pt): 16 Output Slaves (16-pt):16 Cycle time at 500 kbps: 9.3 ms With Configurator: Set between 2 and 500 ms Calculated value takes priority if longer.

Max. communications cycle time with multiple Masters

Input Slaves (16-pt): 16 Output Slaves (16-pt):16 Max. cycle time at 500 kbps: 18 ms CRC error check

Error control checks

28

63

Page 44

Section 3-1

Common Slave Specifications

3-1-2

MS and NS Indicators This section describes the meaning of MS and NS indicators for the Slave Units. The MS (Module Status) indicator displays the status of a node on the network. The NS (Network Status) indicator displays the status of the entire network. The MS and NS indicators can be green or red and they can be OFF, flashing, or ON. The following table shows the meaning of these indicator conditions. The following diagram shows the indicator panel on a basic Slave Unit. The position and status of the indicators, may change depending on the specific Slave Unit.

Indicator

Color

Status

Definition

Meaning

MS

Green

ON

Normal operating status.

Flashing

Device Operational Device in Standby Unrecoverable Fault Minor Fault

---

OFF

No Power

Power isn’t being supplied, waiting for initial processing to start, or the Unit is being reset.

Green

ON

Link OK. On-line, Connected.

Network is operating normally (communications established)

Flashing

On-line, Not Connected

ON

Critical Link Failure

Network is operating normally, but communications have not yet been established. A fatal communications error has occurred. Network communications are not possible. Check for a node address duplication or Bus Off error.

Flashing

Connection Time-out

Communications timeout.

OFF

Not Powered/ Not On-Line

Checking for node address duplication on the Master, switch settings are incorrect, or the power supply is OFF.

Flashing Red

NS

Red

---

ON

Reading switch settings. Unit hardware error: Watchdog timer error. Switch settings incorrect, etc.

29

Page 45

This page is a scan with no text; see it in the PDF.

Page 46

SECTION 4 General-purpose Slaves This section provides specifications and describes the components, indicators, switch settings, and other aspects of General-purpose Slaves. 4-1 4-2

4-3

Common Specifications for General-purpose Slaves . . . . . . . . . . . . . . . . . . .

33

4-1-1

Current Consumption and Weight . . . . . . . . . . . . . . . . . . . . . . . . . .

33

Connecting Communications Cables to General-purpose Slaves . . . . . . . . . .

34

4-2-1

Connecting Communications Cables . . . . . . . . . . . . . . . . . . . . . . . .

34

4-2-2

Connecting Communications Cables to the Nodes . . . . . . . . . . . . .

37

4-2-3

Mounting Terminating Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . .

39

Transistor Remote I/O Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40

4-3-1

Node Address, Baud Rate, and Output Hold/Clear Settings . . . . . .

40

4-3-2

Transistor Remote Input Terminals with 8 Points: DRT1-ID08 (NPN) and DRT1-ID08-1 (PNP) . . . . . . . . . . . . . . . . .

41

4-3-3

Transistor Remote Input Terminals with 16 Points: DRT1-ID16 (NPN) and DRT1-ID16-1 (PNP) . . . . . . . . . . . . . . . . .

45

4-3-4

Transistor Remote Output Terminals with 8 Points: DRT1-OD08 (NPN) and DRT1-OD08-1 (PNP). . . . . . . . . . . . . . . .

49

Transistor Remote Output Terminals with 16 Points: DRT1-OD16 (NPN) and DRT1-OD16-1 (PNP). . . . . . . . . . . . . . . .

53

Transistor Remote I/O Terminal with 8 Inputs and 8 Outputs: DRT1-MD16 (NPN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

56

4-3-7

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59

4-3-8

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines

60

Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks . . . . . . . .

62

4-4-1

Node Address, Baud Rate, and Output Hold/Clear Settings . . . . . .

62

4-4-2

Transistor Remote Input Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-ID16T (NPN) and DRT1-ID16T-1 (PNP) . . . . . . . . . . . . . . .

63

Transistor Remote Input Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-ID16TA (NPN) and DRT1-ID16TA-1 (PNP) . . . . . . . . . . . .

67

4-4-4

Transistor Remote Output Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-OD16T (NPN) and DRT1-OD16T-1 (PNP) . . . . . . . . . . . . .

70

4-4-5

Transistor Remote Output Terminals with 16 Points and 3-tier I/O Terminal Blocks: DRT1-OD16TA (NPN) and DRT1-OD16TA-1 (PNP). . . . . . . . . . .

73

Transistor Remote I/O Terminals with 8 Inputs and 8 Outputs and 3-tier I/O Terminal Blocks: DRT1-MD16T (NPN) and DRT1-MD16T-1 (PNP) . . . . . . . . . . . . .

77

Transistor Remote I/O Terminals with 8 Inputs and 8 Outputs and 3-tier I/O Terminal Blocks: DRT1-MD16TA (NPN) and DRT1-MD16TA-1 (PNP) . . . . . . . . . .

81

4-4-8

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

85

4-4-9

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines

86

4-3-5 4-3-6

4-4

4-4-3

4-4-6

4-4-7

31

Page 47

4-5

Transistor Remote I/O Terminals with Connectors . . . . . . . . . . . . . . . . . . . . .

87

4-5-1

Node Address, Baud Rate, and Output Hold/Clear Settings. . . . . . .

87

4-5-2

Transistor Remote Input Terminals with 32 Points and Connectors: DRT1-ID32ML (NPN) and DRT1-ID32ML-1 (PNP) . . . . . . . . . . .

88

Transistor Remote Output Terminals with 32 Points and Connectors: DRT1-OD32ML (NPN) and DRT1-OD32ML-1 (PNP) . . . . . . . . . .

93

Transistor Remote I/O Terminals with 16 Inputs and 16 Outputs and Connectors: DRT1-MD32ML (NPN) and DRT1-MD32ML-1 (PNP) . . . . . . . . .

98

4-5-5

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

103

4-5-6

4-5-3 4-5-4

4-6

4-7

4-8

108 111

4-6-1

Node Address, Baud Rate, and Output Hold/Clear Settings. . . . . . .

111

4-6-2

Remote Input Adapters with 16 Points: DRT1-ID16X (NPN) and DRT1-ID16X-1 (PNP). . . . . . . . . . . . . . .

112

4-6-3

Remote Output Adapters with 16 Points: DRT1-OD16X (NPN) and DRT1-OD16X-1 (PNP) . . . . . . . . . . . . .

117

4-6-4

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

122

4-6-5

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines

122

Sensor Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

124

4-7-1

Node Address, Baud Rate, and Output Hold/Clear Settings. . . . . . .

124

4-7-2

Transistor Input Sensor Terminals with 16 Points: DRT1-HD16S . .

125

4-7-3

Transistor I/O Sensor Terminals with 8 Inputs and 8 Outputs: DRT1-ND16S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

129

4-7-4

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

132

4-7-5

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines

133

Analog I/O Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

136

4-8-1

Node Address and Baud Rate Setting . . . . . . . . . . . . . . . . . . . . . . . .

136

4-8-2

Analog Input Terminals: DRT1-AD04 and DRT1-AD04H . . . . . . .

137

4-8-3

Analog Output Terminal: DRT1-DA02. . . . . . . . . . . . . . . . . . . . . . .

149

4-8-4

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

156

4-8-5

Wiring Internal Power Supplies and I/O Lines . . . . . . . . . . . . . . . . .

156

Temperature Input Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

157

4-9-1

Node Address and Baud Rate Settings . . . . . . . . . . . . . . . . . . . . . . .

157

4-9-2

Temperature Input Terminals: DRT1-TS04T and DRT1-TS04P . . .

158

4-9-3

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

169

4-9-4

Wiring Internal Power Supplies and I/O Lines . . . . . . . . . . . . . . . . .

170

4-10 CQM1 I/O Link Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

171

4-10-1 Node Address, Baud Rate, and Output Hold/Clear Settings. . . . . . .

171

4-9

32

Wiring Internal Power Supplies, I/O Power Supplies and I/O . . . . .

Remote Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-10-2 CQM1 I/O Link Unit: CQM1-DRT21 . . . . . . . . . . . . . . . . . . . . . . .

173

4-10-3 Mounting to Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

174

Page 48

Section 4-1

Common Specifications for General-purpose Slaves

4-1

Common Specifications for General-purpose Slaves The following table lists specifications which are common to all General-purpose Slaves. For details of specifications for each Slave, refer to the following Slave specifications pages.

4-1-1

Item Communications power supply voltage Internal power supply voltage I/O power supply voltage

Specifications 11 to 25 V DC (Supplied from the communications connector.) 20.4 to 26.4 V DC (24 V DC, –15 to +10%) 20.4 to 26.4 V DC (24 V DC, –15 to +10%)

Noise immunity

±1.5 kVp-p

Vibration resistance Shock resistance

10 to 55 Hz, 1.0-mm double amplitude 200 m/s2

Dielectric strength Insulation resistance

500 V AC (between isolated circuits) 20 MΩ min. at 250 V DC (between isolated circuits)

Ambient temperature Ambient humidity

0 to 55°C 35% to 85%

Operating atmosphere Storage temperature

No corrosive gases –20 to 65°C

Mounting Mounting strength

M4 screw mounting or DIN 35-mm track mounting 50 N Track direction: 10 N

Screw tightening torque

M2 (Communications connector): M3 (Power supply, I/O terminals): M4 (Mounting Unit):

Pulse width: 0.1 to 1 µs Pulse rise time: 1 ns (via noise simulator)

0.25 to 0.3 N⋅m 0.3 to 0.5 N⋅m 0.6 to 0.98 N⋅m

Current Consumption and Weight The following table lists the current consumption, weight, and connector lock strength for basic Slaves. Model DRT1-ID08(-1)

Communications Internal power power supply supply 30 mA max. 50 mA max.

Weight 135 g max.

DRT1-ID16 (-1) DRT1-OD08(-1)

30 mA max. 30 mA max.

50 mA max. 50 mA max.

170 g max. 140 g max.

DRT1-OD16 (-1) DRT1-MD16

30 mA max. 25 mA max.

50 mA max. 45 mA max.

180 g max. 170 g max.

DRT1-ID16T(-1) DRT1-ID16TA(-1)

30 mA max. 50 mA max.

DRT1-OD16T(-1)

30 mA max.

90 mA max. 315 g max. (Same as communica- 315 g max. tions power supply) 90 mA max. 315 g max.

DRT1-OD16TA(-1)

50 mA max.

DRT1-MD16T(-1)

30 mA max.

DRT1-MD16TA(-1)

50 mA max.

(Same as communica- 315 g max. tions power supply)

DRT1-ID32ML(-1)

50 mA max.

(Same as communica- 110 g max. tions power supply)

DRT1-OD32ML(-1)

90 mA max.

(Same as communica- 100 g max. tions power supply)

(Same as communica- 315 g max. tions power supply) 90 mA max. 315 g max.

33

Page 49

Section 4-2

Connecting Communications Cables to General-purpose Slaves Model

DRT1-ID16X(-1)

Communications Internal power Weight power supply supply 70 mA max. (Same as communica- 110 g max. tions power supply) 30 mA max. 70 mA max. 110 g max.

DRT1-OD16X (-1) DRT1-HD16S

30 mA max. 40 mA max.

70 mA max. 60 mA max.

110 g max. 140 g max.

DRT1-ND16S DRT1-AD04

40 mA max. 30 mA max.

60 mA max. 80 mA max.

140 g max. 160 g max.

DRT1-AD04H DRT1-DA02

30 mA max. 30 mA max.

130 mA max. 140 mA max.

160 g max. 160 g max.

DRT1-TS04T DRT1-TS04P

30 mA max. 30 mA max.

130 mA max. 130 mA max.

230 g max. 160 g max.

CQM1-DRT21

40 mA max.

CPM1A-DRT21

30 mA max.

80 mA max. at 5 V DC 185 g max. (Power supplied from the PLC’s Power Supply Unit.) 50 mA max. at 5 V DC 125 g max. (Power supplied from the PLC’s CPU Unit.)

DRT1-MD32ML(-1)

4-2

Connecting Communications Cables to General-purpose Slaves Communications cables are connected to General-purpose Slaves using normal square connectors.

4-2-1

Connecting Communications Cables Use the following procedure to prepare and connect the communications cables to the connectors. Although some connectors are equipped with set screws and some are not, the methods used to connect the cables to the connectors are the same. 1,2,3...

1. Remove about 30 to 80 mm of the cable covering, being careful not to damage the shield weaving underneath. Do not remove more than necessary; removing too much of the covering can result in short circuits. About 30 to 80 mm (Remove as little as possible.)

2. Carefully peel back the weaving. You will find the signal lines, power lines, and the shielding wire. The shielding wire will be loose on the outside of the other lines, but it is harder than the weaving and should be easily identified. Shielding wire

34

Page 50

Section 4-2

Connecting Communications Cables to General-purpose Slaves

3. Remove the exposed weaving, remove the aluminum tape from the signal and power lines, and strip the covering from the signal and power lines to the proper length for the crimp terminal connectors. Twist together the wires of each of the signal and power lines.

Strip to match the crimp terminals

4. Attach the crimp terminals to the lines and then cover any exposed areas of the cable and lines with electricians tape or heat-shrinking tubes. 5. Orient the connector properly, loosen the line set screws, and then insert the lines in order: Black, blue, shield, white, and then red. The wiring method is the same regardless of whether or not the connector is equipped with set screws. Connector without Set Screws Black (–V)

Connector with Set Screws Black (–V)

Blue (CAN low)

Blue (CAN low)

Shield

Shield White (CAN high) Red (+V)

White (CAN high) Red (+V)

There are colored stickers provided on the Master Unit and Slaves that match the colors of the lines to be inserted. Be sure that the colors match when wiring the connectors. These colors are as follows: Black

Color

Signal Power line, negative voltage (–V)

Blue ---

Communications line, low (CAN low) Shield

White Red

Communications line, high (CAN high) Power line, positive voltage (+V)

Note Be sure the line set screws are sufficiently loosened before attempting to insert the lines. If these screws are not loose, the lines will enter the gaps in the back of the connector and will not lock properly.

35