Page 121

Section 4-5

Transistor Remote I/O Terminals with Connectors Mounting Parallel to a Panel Using a Mounting Bracket

A Remote I/O Terminal with a Connector can be mounted parallel to a panel by using the SRT2-ATT02 Mounting Bracket B (sold separately). Note A multi-drop DeviceNet connector cannot be used if the Remote I/O Terminal is mounted parallel to the panel. Panel surface

Mounted parallel to a panel

Mounting Bracket B

Mounting Method Use the following procedure to mounted the Remote I/O Terminal. 1,2,3...

1. Mount the SRT2-ATT02 Mounting Bracket B to the wall using two Phillip’s screws as shown below. Refer to page 107 for mounting dimensions.

2. Mount the Remote I/O Terminal to the Mounting Bracket B. The Mounting Bracket B is shaped like a DIN Track. Use the same mounting procedure as for DIN Track. Mounting Holes and Slave Center Line

Center of mounting holes

5

16±0.2

Two, 3.2 dia. or M3

Center of Slave Unit: mm

106

Page 122

Section 4-5

Transistor Remote I/O Terminals with Connectors Mounting Direction

Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical

45 mm

35 mm

Mounted to DIN Track

DIN track

4 mm

35 mm

Mounted to Perpendicular to a Panel

45 mm

Mounting Dimensions

Mounting Bracket B

3.3 mm

107

Page 123

Section 4-5

Transistor Remote I/O Terminals with Connectors

45 mm

35 mm

Mounted to Parallel to a Panel

Mounting Bracket B

0.1 mm

Mounting Bracket Dimensions

The dimensions of the SRT2-ATT02 Mounting Bracket B are shown below. 7.3

32.5

Mounting holes

35

16±0.2

Two, 3.2 dia. or M3

4-5-6

Wiring Internal Power Supplies, I/O Power Supplies and I/O Internal power is supplied together with the communications power supply and does not need to be wired separately. I/O power supplies and I/O are wired through the I/O MIL connector.

Connecting to I/O Terminals Using OMRON MIL Cables

Slave DRT1-ID32ML DRT1-OD32ML

108

The MIL Cables listed in the following table are available to connect OMRON I/O Terminals (e.g., I/O Relay Blocks). Select the MIL Cable that matches the Remote I/O Terminal and the I/O Terminal.

MIL Cable G79-I50-25-D1 (50 cm) G79-I75-50-D1 (75 cm) G79-O50-25-D1 (50 cm) G79-O75-50-D1 (75 cm)

I/O Relay Block or other I/O Terminal G7TC-ID16 G7TC-IA16 G7TC-OC08/OC16 G70D-SOC16/VSOC16 G70A-ZOC16-3 G70D-FOM16/VFOM16

Remarks

Page 124

Section 4-5

Transistor Remote I/O Terminals with Connectors Slave

MIL Cable

I/O Relay Block or other I/O Terminal Inputs: G7TC-ID16/IA16 Outputs: G7TC-OC08/OC16 G70D-SOC16/VSOC16 G70A-ZOC16-3

Remarks

DRT1-MD32ML

G79-M50-25-D1 (50 cm) G79-M75-50-D1 (75 cm)

DRT1-ID32ML-1

G79-I50-25-D2 (50 cm) G79-I75-50-D2 (75 cm)

G70A-ZIM16-5

---

DRT1-OD32ML-1

G79-O50-25-D1 (50 cm) G79-O75-50-D1 (75 cm)

G70A-ZOC16-4 G70D-SOC16-1

---

G79-I50-25-D1 (50 cm) G79-I75-50-D1 (75 cm) G79-M50-25-D2 (50 cm) G79-M75-50-D2 (75 cm)

G7TC-OC16-4 M7F Inputs: G70A-ZIM16-5 Outputs: G70A-ZOC16-4 G70D-SOC16-1

---

DRT1-MD32ML-1

I/O are distinguished by color. Input tube color: Red Output tube color: Yellow

I/O are distinguished by color. Input tube color: Red Output tube color: Yellow

The following cables are also available with a MIL connector on the Remote I/ O Terminal end and loose wires on the other end. MIL Cable

Remarks

G79-A200C-D1 (2 m) G79-A500C-D1 (5 m)

Loose wire size: AWG28 Loose wires are cut.

G79-Y100C-D1 (1 m) G79-Y200C-D1 (2 m) G79-Y500C-D1 (5 m)

Forked terminals are attached to the loose wires. Forked terminals: 161071-M2 (Nippon Terminal)

The MIL pin numbers, loose wire colors, dot markings, and dot colors are listed in the following table. Pin No.

Core color

Dot marking

Dot color

Pin No.

Core color

■

Black Red

21 22

Light brown

Dot marking

Dot color

■■■

Black Red

1 2

Light brown

3 4

Yellow

Black Red

23 24

Yellow

Black Red

5 6

Light green

Black Red

25 26

Light green

Black Red

7 8

Gray

Black Red

27 28

Gray

Black Red

9 10

White

Black Red

29 30

White

Black Red

11 12

Light brown

Black Red

31 32

Light brown

13 14

Yellow

Black Red

33 34

Yellow

Black Red

15 16

Light green

Black Red

35 36

Light green

Black Red

17 18

Gray

Black Red

37 38

Gray

Black Red

19 20

White

Black Red

39 40

White

Black Red

■■

■■■■

Black Red

109

Page 125

Section 4-5

Transistor Remote I/O Terminals with Connectors Using Pressure-welded Flat Cable Connectors 1,2,3...

Use the following procedure to prepare flat cables with XG4M-4030-T MIL Connectors. 1. Use precision screwdrivers to open the hooks on both ends and separate the contacts from the cover of the MIL socket. There are two tabs on each end of the contact side of the socket. Release both of these at the same time, not one at a time.

2. Place the flat cable between the contacts and cover of the socket, align the contacts, and press on the cover to lock it in place on the contacts. Use a vise or similar device to firmly press the cover on until the tabs are properly joined. Applicable Wires: 1.27-mm pitch flat cable, AWG28 (7-strand wire) UL2651: Standard Cable, UL20012: Stranded Cable, UL20028: Color Coded Cable

3. If required, fold the back over the connector, and insert and lock a strain relief in place.

4. Connect the MIL Connector to a Remote I/O Terminal with a Connector. Using Loose Wires with Pressure-welded Connectors

Note

110

Use the following parts to prepare cables. The Socket used depends on the wire size. Part Socket

Cable wire size: AWG24 XG5M-4032-N

Semi-cover (See note 1.)

XG5S-2001

Hood Cover (See note 2.)

XG5S-5022

Cable wire size: AWG26 to 26 XG5M-4035-N

1. Two Semi-covers are required for each connector.

Page 126

Section 4-6

Remote Adapters

2. A multi-drop DeviceNet Connector cannot be used if the Hood Cover is used. Refer to the PCB Relays Catalog (X33) for details on the XG5 Loose Wire Pressure-welded Connectors.

4-6

Remote Adapters

4-6-1

Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Baud rate setting:

Pins 1 through 6 Pins 7 and 8

ON

Output hold/clear setting:Pin 10 (affects only outputs)

1 2 3 4 5 6 7 8 9 10 Output hold/clear setting for communications errors (for outputs)

Node address setting

Reserved (Always OFF.) Baud rate setting

Node Address Settings

Each Slave’s node address is set with pins 1 through 6 of the Slave’s DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. Pin 6

DIP switch setting Pin 5 Pin 4 Pin 3 Pin 2

Node address Pin 1

0 0

0 0

0 0

0

0

0

0 0

0 0

0 1

0 (default) 1

0

1

0

2

: :

: :

1

1

1

1

0

1

61

1 1

1 1

1 1

1 1

1 1

0 1

62 63

0: OFF, 1: ON Note

1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

Pins 7 and 8 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 7

Pin 8

Baud rate

OFF

OFF

125 kbps (default)

ON OFF

OFF ON

250 kbps 500 kbps

ON

ON

Not allowed.

111

Page 127

Section 4-6

Remote Adapters Note

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings. The functions of pins 9 and 10 differ for inputs and outputs, as shown in the following diagram. ON

Setting Pins 9 and 10

9 10 Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF

Pin 9:

Reserved (Always OFF)

Pin 10: As follows: Inputs: Outputs: OFF (Clear): ON (Hold):

No function (Always OFF) Hold/Clear outputs for communications error All output data from the Master will be cleared to 0 when a communications error occurs. All output data from the Master will be retained when a communications error occurs.

Pins 9 and 10 are factory-set to OFF.

4-6-2

Remote Input Adapters with 16 Points: DRT1-ID16X (NPN) and DRT1-ID16X-1 (PNP)

Input Specifications Item

112

Specification DRT1-ID16X-1

Model

DRT1-ID16X

Internal I/O common Input points

NPN PNP 16 points (Try to use fewer than 8 points over an average 5 minute time span.)

ON voltage

15 V DC min. (between each input terminal and V)

15 V DC min. (between each input terminal and G)

OFF voltage

5 V DC max. (between each input terminal and V)

5 V DC max. (between each input terminal and G)

OFF current Input current

0.8 mA max. 10 mA max./point

ON delay time OFF delay time

9 ms max. 14.5 ms max.

Number of circuits

8 points with one common

Page 128

Section 4-6

Remote Adapters Components of the DRT1-ID16X and DRT1-ID16X-1 DeviceNet Indicators (Refer to page 312.)

MIL socket flat cable connector Connect the input power supply and input devices such as switches and sensors through an MIL-type flat cable connector.

Power supply terminals

DIN track mounting hooks

Communications connector

DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pins 9 and 10: Reserved (Always OFF.)

Internal Circuits

The following diagram shows the internal circuits for the DRT1-ID16X Remote Input Adapter. Photocoupler

Photocoupler

V0 24 V DC

V+

0

CAN H

1

DRAIN CAN L

Physical Photolayer coupler

Photocoupler

SOURCE 24 V DC + SOURCE 24 V DC –

Internal circuitry

V–

DC-DC converter (Isolated)

G0 Photocoupler

V1 24 V DC 8 9

Photocoupler

G1

113

Page 129

Section 4-6

Remote Adapters

The following diagram shows the internal circuits for the DRT1-ID16X-1 Remote Input Adapter. Photocoupler

V0

Photocoupler

0

V+ CAN H DRAIN

Physical layer

1 Photocoupler

Photocoupler

CAN L

SOURCE 24 V DC + SOURCE 24 V DC –

Internal circuitry

V–

DC-DC converter (Isolated)

G0 V1 Photocoupler

8 9

Photocoupler

G1

Wiring of the DRT1-ID16X (NPN) Connector Pin Allocation TOP VIEW

▲ Triangle mark Connector pin No.

Internal Circuits Power Supply SOURCE 24 V DC +

–

+

–

Internal circuits power supply

114

Page 130

Section 4-6

Remote Adapters Input Devices

Use a printed circuit board to wire I/O devices to a flat cable MIL plug which can be connected to the Remote Adapter. Brown (red) NPN output 3-wire sensor (photoelectric or proximity sensor) Black (white) Blue (black)

Top View

Brown (white) Blue (black)

2-wire sensor (limit switch)

I/O power supply

– +

▲ Triangle mark Connector pin No.

Note In accordance with the changes in the standards for photoelectric sensors and proximity sensors, wire colors have been changed. Colors in parentheses are the old wire colors.

Wiring of the DRT1-ID16X-1 (PNP) Connector Pin Allocation TOP VIEW

▲ Triangle mark Connector pin No.

Internal Circuits Power Supply SOURCE 24 V DC –

+

+

–

Internal circuits power supply

115