Page 131
Section 4-6
Remote Adapters Input Devices
Use a printed circuit board to wire I/O devices to a flat cable MIL plug which can be connected to the Remote Adapter. Brown (red) NPN output 3-wire sensor (photoelectric or proximity sensor) Black (white) Blue (black)
2-wire sensor (limit switch)
I/O power supply
Top View
Brown (white) Blue (black)
– ▲ Triangle mark
+
Connector pin No.
Note In accordance with the changes in the standards for photoelectric sensors and proximity sensors, wire colors have been changed. Colors in parentheses are the old wire colors. Dimensions
The following diagram shows the dimensions for the DRT1-ID16X and DRT1ID16X-1 Remote Input Adapters. All dimensions are in mm. Approx. 73
50 max.
(With connector attached)
12
Flat cable length: Approx. 60 85 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
75 ± 0.3
116
40 max.
Page 132
Section 4-6
Remote Adapters
4-6-3
Remote Output Adapters with 16 Points: DRT1-OD16X (NPN) and DRT1-OD16X-1 (PNP)
Output Specifications Item
Specification DRT1-OD16X-1
Model
DRT1-OD16X
Internal I/O common Output points
NPN 16 points
Rated output current Residual voltage
30 mA/point 1.2 V max. (30 mA DC, 1.2 V max. (30 mA DC, between each output termi- between each output terminal and G) nal and V)
Leakage current ON delay time
0.1 mA max. 0.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with one common
PNP
Components of the DRT1-OD16X and DRT1-OD16X-1 DeviceNet Indicators (Refer to page 312.)
MIL socket flat cable connector Connect the output power supply and output devices such as relays and indicators through an MIL-type flat cable connector.
Power supply terminals
DIN track mounting hooks
Communications connector
DIP switch (Refer to page 40.) Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting Pin 9: Reserved (Always OFF.) Pin 10: Hold/clear outputs for communications error
117
Page 133
Section 4-6
Remote Adapters Internal Circuits
The following diagram shows the internal circuits for the DRT1-OD16X Remote Output Adapter. Voltage step-down Photocoupler
Photocoupler V0 24 V DC
V+
0
CAN H DRAIN CAN L
1
Physical Photolayer coupler
SOURCE 24 V DC + SOURCE 24 V DC –
Internal circuitry
V–
Photocoupler
DC-DC converter (Isolated) G0 Voltage step-down Photocoupler V1 24 V DC 8 9
Photocoupler
G1
118
Page 134
Section 4-6
Remote Adapters
The following diagram shows the internal circuits for the DRT1-OD16X-1 Remote Output Adapter. Photocoupler Photocoupler
V+ CAN H DRAIN
Physical layer
CAN L
Photocoupler
SOURCE 24 V DC + SOURCE 24 V DC –
Voltage step-down
Internal circuitry
V–
Photocoupler
DC-DC converter (Isolated)
Photocoupler
Photocoupler
Voltage step-down
Wiring of the DRT1-OD16X (NPN) Connector Pin Allocation TOP VIEW
▲ Triangle mark Connector pin No.
Internal Circuits Power Supply SOURCE 24 V DC –
+
+
–
Internal circuits power supply
119
Page 135
Section 4-6
Remote Adapters Output Devices
Use a printed circuit board to wire I/O devices to a flat cable MIL plug which can be connected to the Remote Adapter. TOP VIEW Relay
LED indicator
I/O power supply
– ▲ Triangle mark
+ Connector pin No.
Note The G70D, NPN-output G7TC, and G70A can also be connected to the Remote Adapter, but the PNP-output G7TC and Input G7TC can’t be connected because the power supply’s polarity is reversed. (Reversing the power supply polarity can damage the Remote Adapter.)
Wiring of the DRT1-OD16X-1 (PNP) Connector Pin Allocation TOP VIEW
▲ Triangle mark Connector pin No.
Internal Circuits Power Supply SOURCE 24 V DC +
–
+
–
Internal circuits power supply
120
Page 136
Section 4-6
Remote Adapters Output Devices
Use a printed circuit board to wire I/O devices to a flat cable MIL plug which can be connected to the Remote Adapter. TOP VIEW Relay
LED indicator
I/O power supply
– +
▲ Triangle mark Connector pin No.
Note The G70D, NPN-output G7TC, and G70A can also be connected to the Remote Adapter, but the PNP-output G7TC and Input G7TC can’t be connected because the power supply’s polarity is reversed. (Reversing the power supply polarity can damage the Remote Adapter.) Dimensions
The following diagram shows the dimensions for the DRT1-OD16X and DRT1-OD16X-1 Remote Output Adapters. All dimensions are in mm. Approx. 73
50 max.
(With connector attached)
12
Flat cable length: Approx. 60
85 max.
40 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
75 ± 0.3
121
Page 137
Section 4-6
Remote Adapters
4-6-4
Mounting in Control Panels Either of the following methods can be used to mount an Remote Adapter in a control panel.
Using Screws
Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Remote Adapter with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.
Using DIN Track
Mount the back of the Remote Adapter to a 35-mm DIN Track. To mount the Adapter, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates. Connecting End Plates Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2
1
End Plate
Note Always attach End Plate to both ends of Slaves connected to DIN Track. Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical No.
IN No.
No.
IN
DRT1-ID16X
DRT1-ID16X
NS
IN
NS
MS
NS
REMOTE ADAPTER 24VDC
MS
MS
DRT1-ID16X REMOTE ADAPTER 24VDC
REMOTE ADAPTER 24VDC
Mounting Direction
No.
DRT1-ID16X
NS MS
Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines
Wiring the I/O Power Supply
The internal circuit power supplies, I/O power supplies, and I/O lines are all wired to M3 screw terminals. Connect M3 crimp terminals and then connect them to the terminal block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.
122
REMOTE ADAPTER 24VDC
IN
4-6-5
6.0 mm max.
Page 138
Section 4-6
Remote Adapters
Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the internal power supply for a DRT1-ID16X Remote Input Adapter. DRT1-ID16X
No.
REMOTE ADAPTER 24VDC
MS
NS
+
Wiring the I/O Power Supply
−
The I/O power supply and I/O are wired through the MIL socket on the I/O flat cable connector. An MIL connector for an I/O Relay Block or PCB can be connected. Connecting to I/O Relay Blocks The MIL socket on the flat cable connector on the Remote Adapter can be connected directly to the connector on an OMRON I/O Relay Block.The Remote Adapter-I/O Relay Block combinations that can be connected are listed in the following table. Remote Adapter DRT1-ID16X DRT1-OD16X
Note
I/O Relay Block G7TC-ID16-5 G7TC-IA16-5 G7TC-OC08 G7TC-OC16 G70D-SOC16 G70D-FOM16 G70A-ZOC16-3
1. Connection is also possible to manifold solenoid valves from Koganei or CKD. 2. The DRT1-ID16X-1 cannot be connected to an I/O Relay Block. Connecting to PCB MIL Connectors The MIL socket on the flat cable connector on the Remote Adapter can be connected to I/O devices connected to a PCB by connecting a MIL connector to the PCB. The PCB MIL connectors that can be used are listed in the following table. MIL Connector XG4A-2031
Remarks DIP straight terminals
XG4A-2034
DIP right-angle terminals
123
Page 139
Section 4-7
Sensor Terminals
4-7
Sensor Terminals
4-7-1
Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Baud rate setting:
Pins 1 through 6 Pins 7 and 8
ON
Output hold/clear setting: Pin 10 on DIP switch on bottom panel (affects only outputs)
1 2 3 4 5 6 7 8 9 10 Output hold/clear setting for communications errors (for outputs)
Node address setting
Reserved (Always OFF.) Baud rate setting
Node Address Settings
Each Slave’s node address is set with pins 1 through 6 of the Slave’s DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. DIP switch setting
Node address
Pin 6 Pin 5 Pin 4 Pin 3 Pin 2 Pin 1 0 0 0 0 0 0 0 (default) 0 0
0 0
0 0
0 0
0 1
1 0
1 2
: :
: :
1 1
1 1
1 1
1 1
0 1
1 0
61 62
1
1
1
1
1
1
63
0: OFF, 1: ON Note
1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).
Baud Rate Setting
Pins 7 and 8 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 7
Note
Pin 8
Baud rate
OFF ON
OFF OFF
125 kbps (default) 250 kbps
OFF ON
ON ON
500 kbps Not allowed.
1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incor-
124
Page 140
Section 4-7
Sensor Terminals rect baud rate may cause communications errors between nodes with correct baud rate settings. Setting Pins 9 and 10
The functions of pins 9 and 10 differ for inputs and outputs, as shown in the following diagram.
Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF
Pin 9:
Reserved (Always OFF)
Pin 10: As follows: Inputs: No function (Always OFF) Outputs: Hold/Clear outputs for communications error OFF (Clear): All output data from the Master will be cleared to 0 when a communications error occurs. ON (Hold): All output data from the Master will be retained when a communications error occurs. Pins 9 and 10 are factory-set to OFF.
4-7-2
Transistor Input Sensor Terminals with 16 Points: DRT1-HD16S
Input Specifications Item Input points ON voltage OFF voltage
Specification 16 NPN points 12 V DC min. (between each input terminal and VCC, the external sensor power supply) 4 V DC max. (between each input terminal and VCC, the external sensor power supply)
OFF current Input current
1.0 mA max. 10 mA max./point
ON delay time OFF delay time
1.0 ms max. 1.5 ms max.
125