Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 20 of 39

C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 191 to 200

Pages 191 to 200 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual

The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron DRT1-ID16

Page 191

Section 5-1

Environment-resistive Slave Specifications

5-1

Environment-resistive Slave Specifications This section shows the specifications that are the same for all Environmentresistive Slaves. Differences for particular Slaves are shown in the explanatory page for each Slave. Item Environment-resistive Slave Specifications 11 to 25 V DC (supplied from the communications connector) Communications power supply voltage Internal power supply voltage

20.4 to 26.4 V DC (24 V DC −15% to 10%)

I/O power supply voltage

20.4 to 26.4 V DC (24 V DC −15% to 10%)

Noise resistance

±1.5 Vp-p, pulse width 0.1 to 1 µs, rise time 1-ns pulse at startup (by noise simulator)

Vibration resistance

10 to 150 Hz, double amplitude 1.0 mm, or 70 m/s2

Shock resistance

200 m/s2 500 V AC (between insulated circuits)

Dielectric strength

Insulation resistance 20 MΩ min. (between insulated circuits) Ambient temperature Operating: −10 to 55°C Storage: −20 to 65°C Ambient humidity 25% to 85% Ambient environment

No corrosive gases.

Degree of protection DRT1-@D@@C(-1): IP66 DRT1-@D@@CL(-1): IP67 DRT1-B7AC: IP66

5-1-1

Mounting method

For Slaves with IP66 protection: M4 screws (front panel) M5 screws (rear panel) For Slaves with IP67 protection: M5 screws for both front and rear panel

Mounting strength Communications connector strength Screw tightening torque

100 N 100 N Round connector (communications connectors, power supply, I/O): 0.39 to 0.49 N⋅m - For Slaves with IP66 protection M4 (mounting unit from front panel): 0.6 to 1.18 N⋅m M5 (mounting unit from rear panel): 1.47 to 1.96 N⋅m - For Slaves with IP67 protection M5 (mounting unit from front panel): 1.47 to 1.96 N⋅m M5 (mounting unit from rear panel): 1.47 to 1.96 N⋅m

Current Consumption, Weight, Degree of Protection The power consumption, weight and degree of protection of Environmentresistive Slaves are shown below. Model

176

DRT1-ID04CL(-1)

Communications Internal Power Weight Power Supply Supply current current 25 mA max. (See note.) 180 g max.

Degree of Protection IP67

DRT1-ID08C DRT1-ID08CL(-1)

30 mA max. 30 mA max.

50 mA max. (See note.)

580 g max. 240 g max.

IP66 IP67

DRT1-HD16C(-1)

30 mA max.

50 mA max.

180 g max.

IP66

Page 192

Section 5-2

Connecting Communications Cables to Environment-resistive Slaves Model

Communications Internal Power Power Supply Supply current current

Weight

Degree of Protection

DRT1-OD04CL(-1) 35 mA max. DRT1-OD08C 30 mA max.

(See note.) 50 mA max.

180 g max. 585 g max.

IP67 IP66

DRT1-OD08CL(-1) 40 mA max. DRT1-WD16C(-1) 30 mA max.

(See note.) 60 mA max.

240 g max. 590 g max.

IP67 IP66

DRT1-MD16C(-1) DRT1-B7AC

50 mA max. 500 mA max.

590 g max. 500 g max.

IP66 IP66

30 mA max. 70 mA max.

Note In these Slaves, the internal power supply shares the communications power supply.

5-2

Connecting Communications Cables to Environmentresistive Slaves Communications cables are connected to Environment-resistive Slaves (Waterproof Terminals, Environment-resistive Transistor Terminals, and B7AC Interface Units) using round shielded connectors. Thin communications cable is used with the round shielded connectors, so the cable characteristics (such as the power supply wiring limitations due to voltage drop over distance) are the same as regular thin cable. Slaves that use the regular square connectors can also be connected to the Master Unit through a T-branch Tap.

System with Slaves using Round Shielded Connectors Only DeviceNet Master Unit

DCA1-5CN@@H1 Cable with shielded connector on one end DCN2-1 shielded T-branch connector

T-branch Tap

DCA1-5CN@@W1 Cable with shielded connectors on both ends DCN2-1 shielded T-branch connector

Communications power supply

I/O

XS2W-D42@-@81-A Cable with shielded socket on one end and plug on the other

Sensor with attached connector

Environmentresistive Terminal

DCN2-1 shielded T-branch connector XS2W-D42@-@81-A Cables with shielded socket on one end and plug on the other

I/O Environmentresistive Terminal

Sensor with attached connector

Power supply

DRS2-@ Connector with terminating resistance

T-joint

XS2F-D42@-@80-@ Cable with connector on one end.

XS2R-D427-5 T-joint

I/O Power Supply Cables (carry power for internal circuitry)

177

Page 193

Section 5-2

Connecting Communications Cables to Environment-resistive Slaves System with Slaves using Round Shielded Connectors and Regular Square Connectors DeviceNet Master Unit DCA1-5CN@@H1 Cable with shielded connector on one end DCN2-1 shielded T-branch connector

T-branch Tap

T-branch Tap

Environment-resistive Terminals or other Slaves using shielded connectors

Slaves using different kinds of connectors can be connected through a T-branch Slave with normal Tap connector

Power supply

I/O Power Supply Cable

Always use the communications cables listed in the following table to connect Waterproof Terminals, Environment-resistive Transistor Terminals, and B7AC Interface Units. Model DCA1-5CN@@W1

Description Cable with round shielded connectors on both ends

DCA1-5CN@@F1

Cable with round shielded connector (female socket) on one end

DCA1-5CN@@H1

Cable with round shielded connector (male plug) on one end

DCN2-1

Shielded T-branch Connector (for 1 branch line)

The blank spaces (@@) in the model numbers indicate the cable length in 0.1m units. For example, add “C5” for a cable 0.5 m long. Note Standard thin DeviceNet cable is used for these cables, so the cables cannot be used in an environment that is subject to spattering unless steps are taken to protect the cables.

178

Page 194

Section 5-3

Environment-resistive Terminals (IP66)

The following connectors with built-in terminating resistors are also available. A Terminating Resistor can be connected to a T-branch Connector.

Note

Model DRS2-1

Description Shielded Connector (male plug) with Terminating Resistor

DRS2-2

Shielded Connector (female socket) with Terminating Resistor

1. Standard thin DeviceNet cable is used for cables with shielded connectors, so maximum current is 3 A. 2. Multi-drop wiring cannot be used with shielded connectors. Use T-branch wiring with DCN2-1 T-branch Connectors and cables that have shielded connectors on both ends. 3. The T-branch Connector’s communications power supply pin has a rated current capacity of 3 A. 4. A cable with a shielded connector (socket) on one end can be used to connect to a regular DCN1-@C T-branch Tap. A cable with a shielded connector (socket) on one end can also be used to connect to the communications power supply from a T-branch Connector.

5-2-1

Example System Assembly DCA1-5CN@@H1 Cable with shielded connector on one end Power Supply Tap

Terminating resistor installed

Male

Male

Female

Female

DCA1-5CN@@W1 Cable with shielded connectors on both ends

Female

Male

Male Female

Male

Female

Female

Male

Male Female

Female Male

Male Female DCA1-5CN@@F1 Cable with shielded connector on one end T-branch Tap (with terminating resistor)

DCN2-1 shielded T-branch connector Communications power supply

Note Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environmental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors.

5-3

Environment-resistive Terminals (IP66)

5-3-1

Node Address and Baud Rate Settings This section describes the node address settings and baud rate settings that are common to all of the Environment-resistive Terminals. These settings are made on separate switches, as shown in the following diagrams.

179

Page 195

Section 5-3

Environment-resistive Terminals (IP66) Node address setting: Baud rate setting:

Rotary switches DIP switch pins 1 and 2 9 0 1 O N

8 7 1

9 0 1 2 3

6 5 4

2

Baud rate setting

8 7

2 3 6 5 4

Node address setting

Note The DRT1-@D@@C(-1) Terminals do not have an “output hold/clear setting” for communications errors. When a communications error occurs with a Terminal that has outputs, the corresponding output data from the Master is cleared to 0 (OFF). Node Address Settings

Each Environment-resistive Terminal’s node address is set in two-digit decimal with the rotary switches. The 10’s digit is set on the left rotary switch and the 1’s digit is set on right rotary switch. Any node address within the allowed setting range can be used as long as it isn’t already set on another node. Note The Environment-resistive Terminal won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

DIP switch pins 1 and 2 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin settings Pin 1 Pin 2

Note

Baud rate

OFF ON

OFF OFF

125 kbps (default) 250 kbps

OFF ON

ON ON

500 kbps Not allowed.

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate setting may cause communications errors between nodes with correct baud rate settings.

5-3-2

Environment-resistive Terminal (IP66) with 8 Transistor Inputs: DRT1-ID08C (NPN)

Input Specifications Item

180

Specification

Model Internal I/O common

DRT1-ID08C NPN

Input points ON voltage

8 points (Uses one word in Master.) 15 V DC min. (between each input terminal and V)

OFF voltage OFF current

5 V DC max. (between each input terminal and V) 1 mA max.

Input current

6 mA max./point at 24 V DC (between each input terminal and V)

Page 196

Section 5-3

Environment-resistive Terminals (IP66) Item ON delay time

1.5 ms max.

Specification

OFF delay time Number of circuits

2.5 ms max. 8 points with one common

Components of the DRT1-ID08C DeviceNet Indicators Input indicators (Refer to page 312.) DIP switch pins 1 and 2: Indicates the input status of each input. Baud rate (Lit when the input is ON.) Not used (Refer to page 179)

Rotary switches 1 and 2: Node address (Refer to page 179)

Internal Circuits

DeviceNet communications connector

Input connector

External power supply connector

The following diagram shows the internal circuits for the DRT1-ID08C Environment-resistive Terminal. DC-DC converter (Isolated)

0 V (for internal circuits) 24 V CN2 (for inputs) (External power supply connector)

0V (for inputs)

Photocoupler

Photocoupler

24 V (for internal circuits)

CAN H

CAN L

4

DRAIN

CN1 (Communications connector)

coupler

1

V– V+

Internal circuitry

Input 0

Physical Photolayer

CN3

Photocoupler Input 1

DC-DC converter (Not isolated)

CN4

181

Page 197

Section 5-3

Environment-resistive Terminals (IP66) Wiring Input 2

Input 4

2-wire sensor (limit switch)

Blue (black)

Brown (white)

Input 3

Brown (white)

Blue (black)

Input 1

Black (white)

Input 0

(end surface)

Input 6

Input 5

Input 7

Internal power I/O power supply supply

NPN output 3-wire sensor (photoelectric or proximity sensor)

Note

1. External power supply line 0V and input line G are connected internally, as are external power supply line 24V and input line V. When input power is supplied to external power supply connectors, power can be supplied to sensors from input lines G and V provided that the total current does not exceed 1.0 A. If the total current exceeds 1.0 A, the power must not be supplied from the connector; it must be supplied externally instead. 2. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors.

182

Page 198

Section 5-3

Environment-resistive Terminals (IP66) Dimensions

The following diagram shows the dimensions for the DRT1-ID08C Environment-resistive Terminal. All dimensions are in mm.

Four, M5

Mounting Holes When screw mounting from the front

When screw mounting from the rear

5-3-3

Mounting screw

Four, 4.2 dia. or M4

Nut

Mounting screw

Four, 5.4 dia.

Environment-resistive Terminal (IP66) with 16 Transistor Inputs: DRT1-HD16C (NPN) and DRT1-HD16C-1 (PNP)

Input Specifications Item

Specification DRT1-HD16C-1

Model

DRT1-HD16C

Internal I/O common Input points

NPN 16 points

PNP

ON voltage

15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V) 1 mA max.

15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)

OFF voltage OFF current Input current

6 mA max./point at 24 V DC 6 mA max./point at 24 V DC (between each input termi- (between each input terminal and V) nal and G)

ON delay time OFF delay time

1.5 ms max. 2.5 ms max.

Number of circuits

16 points with one common

183

Page 199

Section 5-3

Environment-resistive Terminals (IP66) Components of the DRT1-HD16C and DRT1-HD16C-1 DeviceNet indicators (Refer to page 312.)

Input indicators Indicates the input status of each input. (Lit when the input is ON.)

DIP switch pins 1 and 2: Baud rate (Refer to page 179)

0 1

1 2

8 7 6 5 4

9 0 1

DR0 DR1 Datarate OFF OFF 125kbps ON OFF 250kbps OFF ON 500kbps ON ON Not in use.

DR

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

MS

NS

2 3 9 0 1

6 5 4 2 3

ADR

Node Address

8 7

Rotary switches 1 and 2: Node address (Refer to page 179)

DeviceNet communications connector

Input connector

External power supply connector

Internal Circuits

The following diagram shows the internal circuits for the DRT1-HD16C Environment-resistive Terminal (NPN). DC-DC converter (Isolated)

Photocoupler

Photocoupler

0 V (for internal circuits) CN2 3 (External power 0V 4 2 24 V supply connector) (for inputs) (for inputs) 1 24 V (for internal circuits)

CAN H 4 DRAIN

CN1 (Communications connector)

1

CAN L coupler

5 3

V−

2 V+

DC-DC converter (Not isolated)

184

Internal circuitry

4 Input 0

Physical Photolayer

3 G

1 V 2 Input 1

Photocoupler

CN3

Page 200

Section 5-3

Environment-resistive Terminals (IP66)

The following diagram shows the internal circuits for the DRT1-HD16C-1 Environment-resistive Terminal (PNP). DC-DC converter (Isolated)

Photocoupler

0 V (for internal circuits) 3 CN2 (External power 4 2 0V 24 V (for inputs) (for inputs) supply connector) 1 24 V (for internal circuits)

Photocoupler

4 Input 0

DRAIN

CAN L

Internal circuitry

CAN H 4

Physical Photolayer coupler

5

1

3

V−

2 V+

CN1 (Communications connector)

3 G

1 V

CN3

2 Input 1

Photocoupler

DC-DC converter (Not isolated)

The following diagram shows the wiring of the DRT1-HD16C Environmentresistive Terminal (NPN). CN5

4 Input 0 3 G

2 Input 1

4 Input 2 3 G

1 V

1 V

3 G

2 Input 5

4 Input 6

3 G

NPN output 3-wire sensor (photoelectric or proximity sensor)

CN10

CN2

4 Input 12 3 G

2 Input 9

4 Input 10

3 G

4

2 Input 13

2 Input 11

NPN output 3-wire sensor (photoelectric or proximity sensor)

3 G

CN1 (end surface)

3

1 V

1 V

2 Input 7

Blue (black)

Brown (white)

CN9

1 V

1 V

2 Input 3

Blue (black)

CN8

4 Input 8

Brown (red)

1 V

2-wire sensor (limit switch)

CN7

4 Input 4

Black (white)

3 G

CN6

Brown (red)

CN4

Blue (black)

CN3

Black (white)

Wiring

2

CAN H 4 5

1

1 DRAIN

4 Input 14

CAN L 3

V−

2 V+

1 V 2 Input 15

−

+

−

+

Internal power I/O power supply supply

185