Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 19 of 39

C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 181 to 190

Pages 181 to 190 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual

The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron DRT1-ID16

Page 181

Section 4-9

Temperature Input Terminals Example 1: 1130.25°C

Value multiplied by 100: 113025 Notification value: 01B981 (113025 expressed in hexadecimal) Contents of 3 Leftmost Digits Sign/Determin.

11 to 8 7 to 4

Bits Data

C Normal

Leftmost

3 to 0

Temperature conversion data

Data area Sign/determination area

Contents of 3 Rightmost Digits Sign/Determin.

11 to 8 7 to 4

Bits Data Rightmost

C Normal

3 to 0

Temperature conversion data

Sign/determination area

Data area

Example 2: –100.12°C Value multiplied by 100: –10012 Notification value: FFD8E4 (–10012 expressed in hexadecimal) Contents of 3 Leftmost Digits Sign/Determin.

11 to 8 7 to 4

Bits Data

Leftmost C Normal

3 to 0

Temperature conversion data

Data area Sign/determination area

Contents of 3 Rightmost Digits Sign/Determin.

11 to 8 7 to 4 3 to 0

Bits Data Rightmost C

Temperature conversion data

Normal Sign/determination area

Data area

Example 3: –200.12°F Value multiplied by 100: –20012 Notification value: FFB1D4 (–20012 expressed in hexadecimal) Contents of 3 Leftmost Digits Sign/Determin.

11 to 8 7 to 4 3 to 0

Bits Data Leftmost

F

Normal

Temperature conversion data

Sign/determination area

Data area

Contents of 3 Rightmost Digits Sign/Determin.

11 to 8 7 to 4 3 to 0

Bits Data Rightmost

F

Temperature conversion data

Data area

Normal Sign/determination area

166

Page 182

Section 4-9

Temperature Input Terminals Example 4: Input Error (Broken Wire) (Unit:°F) Notification value: 7FFFFF Contents of 3 Leftmost Digits Sign/Determin.

Temperature conversion data

11 to 8 7 to 4 3 to 0

Bits Data Leftmost

F

Error

Sign/determination area

Data area

Contents of 3 Rightmost Digits Sign/Determin.

Rightmost

Note

Temperature conversion data

11 to 8 7 to 4 3 to 0

Bits Data F

Error

Sign/determination area

Data area

1. Data notification is provided in order, from the leftmost digits to the rightmost. When reading data with the program, be sure to read it in that same order. 2. Taking the Programmable Controller’s cycle time and the communications time into consideration, lower the reading cycle to 125 ms or less. If the reading cycle exceeds 125 ms, normal data cannot be read.

Sample Program for the DRT1-TS04T and DRT1TS04P

The following program is an example of using the Temperature Input Terminal in the display mode for 2 digits below the decimal point. Settings Temperature Input Terminal’s allocated words: 350 to 353 Temperature Input Terminal’s mode: Two digits below decimal point (DIP switch pin 10: ON) Operation The temperature data from the Temperature Input Terminal’s input 0 is stored in words 30 to 32 in binary data multiplied by 100, as shown below.

Word

Bit

15 to 12

11 to 8

7 to 4

30 x163 x162 x161

31 x167 0 (Fixed)

x166 0 (Fixed)

x165 0 (Fixed)

32

Temperature unit bit Broken wire bit:

3

2

1

0 x160 0 x164 Temperature Broken wire unit bit bit

0

0: °C; 1: °F 0: Normal; 1: Error

The data in words 30 and 31 can be treated as 32-bit binary data.

167

Page 183

Section 4-9

Temperature Input Terminals Program Example

35015 MOV 350

Leftmost 3 digits notification

Stores leftmost 3 digits of data in IR word 040.

040 35015 MOVD 350

Leftmost 3 digits notification

#0020

Transfers rightmost 3 bits of data (160 to 162) to word 030.

030

MOVD 350 #0300

Transfers163 data to word 030.

030

MOVD 040 #0011

Transfers 164 and 165 data to word 031.

031 04011 MOVD #00FF

When data is negative

#0210

If data is negative, stores "FF" in leftmost two digits of word 031.

031 04011 MOVD #0000

When data is positive

#0210

If data is positive, stores "00" in leftmost two digits of word 031.

031

XFRB #0210 040 032

168

Transfers the temperature-units bit and broken-wire bit information to word 032.

Page 184

Section 4-9

Temperature Input Terminals Dimensions

The following diagram shows the dimensions for the DRT1-TS04T and DRT1TS04P Temperature Input Terminals. All dimensions are in mm. Approx. 73

Unit: mm

(With connector installed)

50 max.

12

150 max.

40 max.

Mounting Hole Dimensions

40±0.3

Two, 4.2 dia. or M4

140±0.3

4-9-3

Mounting in Control Panels Either of the following methods can be used to mount a Temperature Input Terminal in a control panel.

Using Screws

Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Temperature Input Terminals with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.

Using DIN Track

Mount the back of the Temperature Input Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates.

169

Page 185

Section 4-9

Temperature Input Terminals Connecting End Plates

Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2

1

End Plate

Note Always attach End Plate to both ends of Slaves connected to DIN Track. Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical

MS

DRT1-TS04T 3 2

2

3

0

1

1

0

1

IN 0

2

NS

BROKEN WIRE

MS

DRT1-TS04T

3

0

3

1

NS

BROKEN WIRE

2

No.

ANALOG TERMINAL

ANALOG TERMINAL

No.

IN

Mounting Direction

0

MS

NS

2

3

3

0

1 No.

ANALOG TERMINAL

2

BROKEN WIRE

DRT1-TS04T

1

IN

4-9-4

Wiring Internal Power Supplies and I/O Lines The internal circuit power supplies and I/O lines are all wired to M3 screw terminals. Connect M3 crimp terminals and then connect them to the terminal block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.

170

6.0 mm max.

Page 186

Section 4-10

CQM1 I/O Link Unit Wiring the Internal Power Supply

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the internal power supply for a DRT1-TS04T Temperature Input Terminal. DRT1-TS04T

No.

ANALOG TERMINAL

BROKEN WIRE

A

789

−

Wiring I/O

2

3456

BCD

F01

3

0

2

E

1

+

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block and external I/O wiring. The following example shows the wiring to input 0 on a DRT1-TS04T Temperature Input Terminal. DRT1-TS04T

No.

ANALOG TERMINAL

BROKEN WIRE

A

0

2

3456

BCD

F01

3

2

E

1

789

−

+

4-10 CQM1 I/O Link Unit 4-10-1 Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Baud rate setting:

Pins 1 through 6 Pins 7 and 8

ON

Output hold/clear setting:Pin 10 (affects only outputs)

1 2 3 4 5 6 7 8 9 10 Output hold/clear setting for communications errors (for outputs

Node address setting

Reserved (Always OFF.) Baud rate setting

171

Page 187

CQM1 I/O Link Unit

Section 4-10

Node Address Settings

Each Slave’s node address is set with pins 1 through 6 of the Slave’s DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. Pin 6

DIP switch setting Pin 5 Pin 4 Pin 3 Pin 2

Node address Pin 1

0 0

0 0

0 0

0

0

0

0 0

0 0

0 1

0 (default) 1

0

1

0

2

: :

: :

1

1

1

1

0

1

61

1 1

1 1

1 1

1 1

1 1

0 1

62 63

0: OFF, 1: ON Note

1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

Pins 7 and 8 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 7

Note

Pin 8

Baud rate

OFF

OFF

125 kbps (default)

ON OFF

OFF ON

250 kbps 500 kbps

ON

ON

Not allowed.

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.

Setting Pins 9 and 10

The functions of pins 9 and 10 differ for inputs and outputs, as shown in the following diagram. Pin 9:

Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF

Reserved (Always OFF)

Pin 10: As follows: Inputs: Outputs: OFF (Clear): ON (Hold):

No function (Always OFF) Hold/Clear outputs for communications error All output data from the Master will be cleared to 0 when a communications error occurs. All output data from the Master will be retained when a communications error occurs.

Pins 9 and 10 are factory-set to OFF.

172

Page 188

Section 4-10

CQM1 I/O Link Unit

4-10-2 CQM1 I/O Link Unit: CQM1-DRT21 Specifications

The general specifications for the CQM1-DRT21 I/O Link Unit conform to CQM1 specifications. Item Model number

CQM1-DRT21

Number of I/O points Compatible PLCs

16 inputs, 16 outputs (32 I/O points total) All CQM1 PLCs and all CQM1H PLCs.

Max. number of Units

11 Units max. with CQM1H-CPU51-E/61-E PLCs (512 points max.) or CQM1H-CPU11-E/21-E PLCs (256 points max.) 7 Units max. with CQM1-CPU4@-EV1 PLCs (256 points max.) Connection to previous models: CQM1-CPU4@-E: 5 Units max. (192 points max.) CQM1-CPU11-E/21-E: 3 Units max. (128 points max.) Communications power: 40 mA max. Internal circuits: 80 mA max. (5 V DC)

Current consumption Weight

Specification

185 g max.

General Specifications Conform to SYSMAC CQM1 specifications.

Components

Indicators (Refer to page 312.)

DIP switch (Refer to page 40.) Pins 1 to 6: Node address Pins 7 and 8: Baud rate Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error

Communications connector

CQM1 Word Allocation

In the CQM1 PLCs, an I/O Link Unit is treated just like an I/O Unit with one input word and one output word, so word allocation is identical to a standard I/ O Unit. Words are allocated from the left side of the PLC, beginning with IR

173

Page 189

Section 4-10

CQM1 I/O Link Unit

001 for inputs and IR 100 for outputs. The following diagram shows a word allocation example. PS: Power supply unit CPU: CPU Unit IN: Input Unit/Terminals OUT: Output Unit DRT: I/O Link Unit Word allocation Inputs

IR 000 IR 001 IR 002

Outputs

IR 100 IR 101 IR 102

From the Master's output area To the Master's input area

Dimensions

The following diagram shows the dimensions for the CQM1-DRT21 I/O Link Unit. Refer to the PLC’s Installation Guide for the dimensions of the Unit when it is mounted to the Backplane. (All dimensions are in mm.)

(With the cover removed)

4-10-3 Mounting to Control Panels The CQM1 I/O Link Unit is assembled with the rest of the Units in the CQM1 PLC for use as one assembled PLC. The CQM1 I/O Link Unit is connected to the PLC just like any other PLC Unit. Refer to the operation manual for the PLC for details. Note No internal power, I/O power, or I/O wiring is required for the CQM1 I/O Link Unit because it uses internal I/O bits in the CPU Unit to communicate with the master.

174

Page 190

SECTION 5 Environment-resistive and Waterproof Slaves This section provides specifications and describes the components, indicators, switch settings, and other aspects of Environment-resistive Slaves. 5-1

Environment-resistive Slave Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-1

5-2 5-3

Current Consumption, Weight, Degree of Protection. . . . . . . . . . . .

176

Connecting Communications Cables to Environment-resistive Slaves . . . . .

177

5-2-1

Example System Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

179

Environment-resistive Terminals (IP66) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

179

5-3-1

Node Address and Baud Rate Settings . . . . . . . . . . . . . . . . . . . . . . .

179

5-3-2

Environment-resistive Terminal (IP66) with 8 Transistor Inputs: DRT1-ID08C (NPN). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

180

Environment-resistive Terminal (IP66) with 16 Transistor Inputs: DRT1-HD16C (NPN) and DRT1-HD16C-1 (PNP) . . . . . . . . . . . . .

183

Environment-resistive Terminal (IP66) with 8 Transistor Outputs: DRT-OD08C (NPN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

187

5-3-5

Environment-resistive Terminal (IP66) with 16 Transistor Outputs: DRT1-WD16C (NPN) and DRT1-WD16C-1 (PNP) . . . . . . . . . . . .

189

5-3-6

Environment-resistive Terminal (IP66) with 8 Inputs 8 Outputs: DRT1-MD16C (NPN) and DRT1-MD16C-1 (PNP) . . . . . . . . . . . .

193

5-3-7

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

197

5-3-8

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines

198

Waterproof Terminals (IP67) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

200

5-4-1

Node Address, Baud Rate, and Output Hold/Clear Settings . . . . . .

200

5-4-2

Waterproof Terminal (IP67) with 4 Transistor Inputs: DRT1-ID04CL (NPN) and DRT1-ID04CL-1 (PNP) . . . . . . . . . . . .

202

Waterproof Terminal (IP67) with 8 Transistor Inputs: DRT1-ID08CL (NPN) and DRT1-ID08CL-1 (PNP) . . . . . . . . . . . .

204

5-4-4

Waterproof Terminal (IP67) with 4 Transistor Outputs: DRT1-OD04CL (NPN) and DRT1-OD04CL-1 (PNP). . . . . . . . . . .

207

5-4-5

Waterproof Terminal (IP67) with 8 Transistor Outputs: DRT1-OD08CL (NPN) and DRT1-OD08CL-1 (PNP). . . . . . . . . . .

210

5-4-6

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

213

5-4-7

Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines

213

B7AC Interface Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

215

5-5-1

Node Address and Baud Rate Settings (DIP Switch 1) . . . . . . . . . .

215

5-5-2

Example System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . .

217

5-5-3

B7AC Interface Unit: DRT1-B7AC . . . . . . . . . . . . . . . . . . . . . . . . .

217

5-5-4

Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

223

5-5-5

Wiring the Internal Power Supply and Input Lines . . . . . . . . . . . . .

224

5-3-3 5-3-4

5-4

5-4-3

5-5

176

175