The text of a manual · part 19 of 39
C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 181 to 190
Pages 181 to 190 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual
The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron DRT1-ID16
Page 181
Section 4-9
Temperature Input Terminals Example 1: 1130.25°C
Value multiplied by 100: 113025 Notification value: 01B981 (113025 expressed in hexadecimal) Contents of 3 Leftmost Digits Sign/Determin.
11 to 8 7 to 4
Bits Data
C Normal
Leftmost
3 to 0
Temperature conversion data
Data area Sign/determination area
Contents of 3 Rightmost Digits Sign/Determin.
11 to 8 7 to 4
Bits Data Rightmost
C Normal
3 to 0
Temperature conversion data
Sign/determination area
Data area
Example 2: –100.12°C Value multiplied by 100: –10012 Notification value: FFD8E4 (–10012 expressed in hexadecimal) Contents of 3 Leftmost Digits Sign/Determin.
11 to 8 7 to 4
Bits Data
Leftmost C Normal
3 to 0
Temperature conversion data
Data area Sign/determination area
Contents of 3 Rightmost Digits Sign/Determin.
11 to 8 7 to 4 3 to 0
Bits Data Rightmost C
Temperature conversion data
Normal Sign/determination area
Data area
Example 3: –200.12°F Value multiplied by 100: –20012 Notification value: FFB1D4 (–20012 expressed in hexadecimal) Contents of 3 Leftmost Digits Sign/Determin.
11 to 8 7 to 4 3 to 0
Bits Data Leftmost
F
Normal
Temperature conversion data
Sign/determination area
Data area
Contents of 3 Rightmost Digits Sign/Determin.
11 to 8 7 to 4 3 to 0
Bits Data Rightmost
F
Temperature conversion data
Data area
Normal Sign/determination area
166
Page 182
Section 4-9
Temperature Input Terminals Example 4: Input Error (Broken Wire) (Unit:°F) Notification value: 7FFFFF Contents of 3 Leftmost Digits Sign/Determin.
Temperature conversion data
11 to 8 7 to 4 3 to 0
Bits Data Leftmost
F
Error
Sign/determination area
Data area
Contents of 3 Rightmost Digits Sign/Determin.
Rightmost
Note
Temperature conversion data
11 to 8 7 to 4 3 to 0
Bits Data F
Error
Sign/determination area
Data area
1. Data notification is provided in order, from the leftmost digits to the rightmost. When reading data with the program, be sure to read it in that same order. 2. Taking the Programmable Controller’s cycle time and the communications time into consideration, lower the reading cycle to 125 ms or less. If the reading cycle exceeds 125 ms, normal data cannot be read.
Sample Program for the DRT1-TS04T and DRT1TS04P
The following program is an example of using the Temperature Input Terminal in the display mode for 2 digits below the decimal point. Settings Temperature Input Terminal’s allocated words: 350 to 353 Temperature Input Terminal’s mode: Two digits below decimal point (DIP switch pin 10: ON) Operation The temperature data from the Temperature Input Terminal’s input 0 is stored in words 30 to 32 in binary data multiplied by 100, as shown below.
Word
Bit
15 to 12
11 to 8
7 to 4
30 x163 x162 x161
31 x167 0 (Fixed)
x166 0 (Fixed)
x165 0 (Fixed)
32
Temperature unit bit Broken wire bit:
3
2
1
0 x160 0 x164 Temperature Broken wire unit bit bit
0
0: °C; 1: °F 0: Normal; 1: Error
The data in words 30 and 31 can be treated as 32-bit binary data.
167
Page 183
Section 4-9
Temperature Input Terminals Program Example
35015 MOV 350
Leftmost 3 digits notification
Stores leftmost 3 digits of data in IR word 040.
040 35015 MOVD 350
Leftmost 3 digits notification
#0020
Transfers rightmost 3 bits of data (160 to 162) to word 030.
030
MOVD 350 #0300
Transfers163 data to word 030.
030
MOVD 040 #0011
Transfers 164 and 165 data to word 031.
031 04011 MOVD #00FF
When data is negative
#0210
If data is negative, stores "FF" in leftmost two digits of word 031.
031 04011 MOVD #0000
When data is positive
#0210
If data is positive, stores "00" in leftmost two digits of word 031.
031
XFRB #0210 040 032
168
Transfers the temperature-units bit and broken-wire bit information to word 032.
Page 184
Section 4-9
Temperature Input Terminals Dimensions
The following diagram shows the dimensions for the DRT1-TS04T and DRT1TS04P Temperature Input Terminals. All dimensions are in mm. Approx. 73
Unit: mm
(With connector installed)
50 max.
12
150 max.
40 max.
Mounting Hole Dimensions
40±0.3
Two, 4.2 dia. or M4
140±0.3
4-9-3
Mounting in Control Panels Either of the following methods can be used to mount a Temperature Input Terminal in a control panel.
Using Screws
Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Temperature Input Terminals with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.
Using DIN Track
Mount the back of the Temperature Input Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates.
169
Page 185
Section 4-9
Temperature Input Terminals Connecting End Plates
Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2
1
End Plate
Note Always attach End Plate to both ends of Slaves connected to DIN Track. Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical
MS
DRT1-TS04T 3 2
2
3
0
1
1
0
1
IN 0
2
NS
BROKEN WIRE
MS
DRT1-TS04T
3
0
3
1
NS
BROKEN WIRE
2
No.
ANALOG TERMINAL
ANALOG TERMINAL
No.
IN
Mounting Direction
0
MS
NS
2
3
3
0
1 No.
ANALOG TERMINAL
2
BROKEN WIRE
DRT1-TS04T
1
IN
4-9-4
Wiring Internal Power Supplies and I/O Lines The internal circuit power supplies and I/O lines are all wired to M3 screw terminals. Connect M3 crimp terminals and then connect them to the terminal block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.
170
6.0 mm max.
Page 186
Section 4-10
CQM1 I/O Link Unit Wiring the Internal Power Supply
Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the internal power supply for a DRT1-TS04T Temperature Input Terminal. DRT1-TS04T
No.
ANALOG TERMINAL
BROKEN WIRE
A
789
−
Wiring I/O
2
3456
BCD
F01
3
0
2
E
1
+
Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block and external I/O wiring. The following example shows the wiring to input 0 on a DRT1-TS04T Temperature Input Terminal. DRT1-TS04T
No.
ANALOG TERMINAL
BROKEN WIRE
A
0
2
3456
BCD
F01
3
2
E
1
789
−
+
4-10 CQM1 I/O Link Unit 4-10-1 Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Node address setting: Baud rate setting:
Pins 1 through 6 Pins 7 and 8
ON
Output hold/clear setting:Pin 10 (affects only outputs)
1 2 3 4 5 6 7 8 9 10 Output hold/clear setting for communications errors (for outputs
Node address setting
Reserved (Always OFF.) Baud rate setting
171
Page 187
CQM1 I/O Link Unit
Section 4-10
Node Address Settings
Each Slave’s node address is set with pins 1 through 6 of the Slave’s DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. Pin 6
DIP switch setting Pin 5 Pin 4 Pin 3 Pin 2
Node address Pin 1
0 0
0 0
0 0
0
0
0
0 0
0 0
0 1
0 (default) 1
0
1
0
2
: :
: :
1
1
1
1
0
1
61
1 1
1 1
1 1
1 1
1 1
0 1
62 63
0: OFF, 1: ON Note
1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).
Baud Rate Setting
Pins 7 and 8 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 7
Note
Pin 8
Baud rate
OFF
OFF
125 kbps (default)
ON OFF
OFF ON
250 kbps 500 kbps
ON
ON
Not allowed.
1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.
Setting Pins 9 and 10
The functions of pins 9 and 10 differ for inputs and outputs, as shown in the following diagram. Pin 9:
Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF
Reserved (Always OFF)
Pin 10: As follows: Inputs: Outputs: OFF (Clear): ON (Hold):
No function (Always OFF) Hold/Clear outputs for communications error All output data from the Master will be cleared to 0 when a communications error occurs. All output data from the Master will be retained when a communications error occurs.
Pins 9 and 10 are factory-set to OFF.
172
Page 188
Section 4-10
CQM1 I/O Link Unit
4-10-2 CQM1 I/O Link Unit: CQM1-DRT21 Specifications
The general specifications for the CQM1-DRT21 I/O Link Unit conform to CQM1 specifications. Item Model number
CQM1-DRT21
Number of I/O points Compatible PLCs
16 inputs, 16 outputs (32 I/O points total) All CQM1 PLCs and all CQM1H PLCs.
Max. number of Units
11 Units max. with CQM1H-CPU51-E/61-E PLCs (512 points max.) or CQM1H-CPU11-E/21-E PLCs (256 points max.) 7 Units max. with CQM1-CPU4@-EV1 PLCs (256 points max.) Connection to previous models: CQM1-CPU4@-E: 5 Units max. (192 points max.) CQM1-CPU11-E/21-E: 3 Units max. (128 points max.) Communications power: 40 mA max. Internal circuits: 80 mA max. (5 V DC)
Current consumption Weight
Specification
185 g max.
General Specifications Conform to SYSMAC CQM1 specifications.
Components
Indicators (Refer to page 312.)
DIP switch (Refer to page 40.) Pins 1 to 6: Node address Pins 7 and 8: Baud rate Pin 9: Reserved (Always OFF.) Pin 10: Hold/Clear outputs for communications error
Communications connector
CQM1 Word Allocation
In the CQM1 PLCs, an I/O Link Unit is treated just like an I/O Unit with one input word and one output word, so word allocation is identical to a standard I/ O Unit. Words are allocated from the left side of the PLC, beginning with IR
173
Page 189
Section 4-10
CQM1 I/O Link Unit
001 for inputs and IR 100 for outputs. The following diagram shows a word allocation example. PS: Power supply unit CPU: CPU Unit IN: Input Unit/Terminals OUT: Output Unit DRT: I/O Link Unit Word allocation Inputs
IR 000 IR 001 IR 002
Outputs
IR 100 IR 101 IR 102
From the Master's output area To the Master's input area
Dimensions
The following diagram shows the dimensions for the CQM1-DRT21 I/O Link Unit. Refer to the PLC’s Installation Guide for the dimensions of the Unit when it is mounted to the Backplane. (All dimensions are in mm.)
(With the cover removed)
4-10-3 Mounting to Control Panels The CQM1 I/O Link Unit is assembled with the rest of the Units in the CQM1 PLC for use as one assembled PLC. The CQM1 I/O Link Unit is connected to the PLC just like any other PLC Unit. Refer to the operation manual for the PLC for details. Note No internal power, I/O power, or I/O wiring is required for the CQM1 I/O Link Unit because it uses internal I/O bits in the CPU Unit to communicate with the master.
174
Page 190
SECTION 5 Environment-resistive and Waterproof Slaves This section provides specifications and describes the components, indicators, switch settings, and other aspects of Environment-resistive Slaves. 5-1
Environment-resistive Slave Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-1
5-2 5-3
Current Consumption, Weight, Degree of Protection. . . . . . . . . . . .
176
Connecting Communications Cables to Environment-resistive Slaves . . . . .
177
5-2-1
Example System Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
179
Environment-resistive Terminals (IP66) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
179
5-3-1
Node Address and Baud Rate Settings . . . . . . . . . . . . . . . . . . . . . . .
179
5-3-2
Environment-resistive Terminal (IP66) with 8 Transistor Inputs: DRT1-ID08C (NPN). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
180
Environment-resistive Terminal (IP66) with 16 Transistor Inputs: DRT1-HD16C (NPN) and DRT1-HD16C-1 (PNP) . . . . . . . . . . . . .
183
Environment-resistive Terminal (IP66) with 8 Transistor Outputs: DRT-OD08C (NPN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
187
5-3-5
Environment-resistive Terminal (IP66) with 16 Transistor Outputs: DRT1-WD16C (NPN) and DRT1-WD16C-1 (PNP) . . . . . . . . . . . .
189
5-3-6
Environment-resistive Terminal (IP66) with 8 Inputs 8 Outputs: DRT1-MD16C (NPN) and DRT1-MD16C-1 (PNP) . . . . . . . . . . . .
193
5-3-7
Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
197
5-3-8
Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines
198
Waterproof Terminals (IP67) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
200
5-4-1
Node Address, Baud Rate, and Output Hold/Clear Settings . . . . . .
200
5-4-2
Waterproof Terminal (IP67) with 4 Transistor Inputs: DRT1-ID04CL (NPN) and DRT1-ID04CL-1 (PNP) . . . . . . . . . . . .
202
Waterproof Terminal (IP67) with 8 Transistor Inputs: DRT1-ID08CL (NPN) and DRT1-ID08CL-1 (PNP) . . . . . . . . . . . .
204
5-4-4
Waterproof Terminal (IP67) with 4 Transistor Outputs: DRT1-OD04CL (NPN) and DRT1-OD04CL-1 (PNP). . . . . . . . . . .
207
5-4-5
Waterproof Terminal (IP67) with 8 Transistor Outputs: DRT1-OD08CL (NPN) and DRT1-OD08CL-1 (PNP). . . . . . . . . . .
210
5-4-6
Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
213
5-4-7
Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines
213
B7AC Interface Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
215
5-5-1
Node Address and Baud Rate Settings (DIP Switch 1) . . . . . . . . . .
215
5-5-2
Example System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . .
217
5-5-3
B7AC Interface Unit: DRT1-B7AC . . . . . . . . . . . . . . . . . . . . . . . . .
217
5-5-4
Mounting in Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
223
5-5-5
Wiring the Internal Power Supply and Input Lines . . . . . . . . . . . . .
224
5-3-3 5-3-4
5-4
5-4-3
5-5
176
175