Page 171

Section 4-8

Analog I/O Terminals

4-8-4

Mounting in Control Panels Either of the following methods can be used to mount an Analog I/O Terminal in a control panel.

Using Screws

Open mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the Analog I/O Terminal with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.

Using DIN Track

Mount the back of the Analog I/O Terminal to a 35-mm DIN Track. To mount the Terminal, pull down on the mounting hook on the back of the Terminal with a screwdriver, insert the DIN Track on the back of the Terminal, and then secure the Terminal to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates. Connecting End Plates Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2

1

End Plate

Note Always attach End Plate to both ends of Slaves connected to DIN Track. Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. Vertical 3

IN

1

No.

3

2

2

1

3

0

2

DRT1-AD04

1

NS

IN 0

DRT1-AD04

NS

MS

No.

NS

MS

ANALOG TERMINAL

MS

DRT1-AD04 ANALOG TERMINAL

ANALOG TERMINAL

No.

IN

Mounting Direction

0

0

MS

NS

3 No.

ANALOG TERMINAL

2

DRT1-AD04

1

IN

4-8-5

Wiring Internal Power Supplies and I/O Lines The internal circuit power supplies and I/O lines are all wired to M3 screw terminals. Connect M3 crimp terminals and then connect them to the terminal block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to 0.5 N⋅m. 6.0 mm max.

156

6.0 mm max.

Page 172

Section 4-9

Temperature Input Terminals Wiring the Internal Power Supply

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block. The following example shows the internal power supply for a DRT1-AD04 Analog Input Terminal. DRT1-AD04

No.

ANALOG TERMINAL

0 1

2 3

7 8

9

4

5 6

−

Wiring I/O

+

Refer to the wiring details for each Slave for information on the terminal arrangement at the terminal block and external I/O wiring. The following example shows the wiring to input 0 on a DRT1-AD04 Analog Input Terminal. DRT1-AD04

No.

ANALOG TERMINAL

0 1

2 3

7 8

9

4

5 6

V+

4-9

Temperature Input Terminals

4-9-1

Node Address and Baud Rate Settings

−

This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Pins 1 through 6 Pins 7 and 8

Slave-specific setting:

Pins 9 and 10 (Refer to the descriptions of individual Slaves.)

ON

Node address setting: Baud rate setting:

1 2 3 4 5 6 7 8 9 10

Node address setting Baud rate setting

Slave-specific setting: Refer to the descriptions of individual Slaves.

157

Page 173

Section 4-9

Temperature Input Terminals Node Address Settings

Each Slave’s node address is set with pins 1 through 6 of the Slave’s DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. Pin 6

DIP switch setting Pin 5 Pin 4 Pin 3 Pin 2

Node address Pin 1

0 0

0 0

0 0

0

0

0

0 0

0 0

0 1

0 (default) 1

0

1

0

2

: :

Note

: :

1

1

1

1

0

1

61

1 1

1 1

1 1

1 1

1 1

0 1

62 63

1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

Pins 7 and 8 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 7

Note

Pin 8

Baud rate

OFF ON

OFF OFF

125 kbps (default) 250 kbps

OFF ON

ON ON

500 kbps Not allowed.

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.

4-9-2

Temperature Input Terminals: DRT1-TS04T and DRT1-TS04P

Specifications General Specifications Item Model Input type Input points

DRT1-TS04P Resistance temperature sensor input 4 points (allocated four words in the Master Unit.)

Communications power supply voltage

11 to 25 V DC (supplied from the communications connector)

Internal power supply voltage Current consumption

20.4 to 26.4 V DC (24 V DC −15% to 10%)

Noise immunity

±1.5 kVp-p, pulse width: 0.1 to 1 µs, pulse rise time: 1 ns (via noise simulator) 10 to 55 Hz, 1.0-mm double amplitude

Vibration resistance

158

Specification DRT1-TS04T Thermocouple input

Communications: 30 mA max. Internal circuit: 130 mA max.

Page 174

Section 4-9

Temperature Input Terminals Item Shock resistance

Specification 200 m/s

Dielectric strength Insulation resistance

500 V AC for 1 min (between insulated circuits) 20 MΩ min. at 250 V DC (between insulated circuits)

2

Ambient operating temper- 0 to 55°C ature Ambient operating humidity 35% to 85% (with no condensation) Ambient operating environ- No corrosive gases. ment Ambient storage temperature

−25 to 65°C

Mounting method Mounting strength

M4 screw mounting or 35-mm DIN track mounting 50 N 10 N min. in the DIN Track direction

Terminal strength Weight

Pull: 50 N 230 g max.

Input classification

R, S, K1, K2, J1, J2, T, E, B, N, L1, L2, U, W, PL II convertible (4-point common input class) (Instruction value ±0.5% or ±2°C, whichever is larger) ±1 digit max. (See note.)

Instruction precision

160 g max. Pt100, JPt100 convertible (4-point common input class) (Instruction value ±0.5% or ±1°C, whichever is larger) ±1 digit max.

Conversion period Temperature conversion data

250 ms / 4 pts. Binary data (4-digit hexadecimal)

Isolation method

Photocoupler isolation between temperature inputs and communications lines (Photocoupler isolation between temperature input signals.)

Note Less than –100°C of K1, T, N: ±4°C ±1 digit max. U, L1, L2: ±4°C ±1 digit max. Less than 200°C of R, S: ±6°C ±1 digit max. No regulation Less than 400°C of B: W: (Instruction value ±0.5% or ±6°C, whichever is larger) ±1 digit max. PL II: (Instruction value ±0.5% or ±4°C, whichever is larger) ±1 digit max.

159

Page 175

Section 4-9

Temperature Input Terminals Components of the DRT1-TS04T and DRT1-TS04P DeviceNet Display

(Refer to page 312.)

Broken wire display The indicator for the relevant number lights when the open-circuit detection function is activated.

Rotary switch Sets the input range.

Cold Junction Compensator (DRT1-TS04T only) Corrects the input temperature. Do not touch or remove it. Terminal block Connects the operation power supply (the internal circuit power supply) and the temperature sensors. The wiring will vary depending on the model.

DIN track mounting rack

Communications connector DIP switch 1 to 6: Node address (Refer to page 124.) 7, 8: Baud rate (Refer to page 124.) 9: Temperature unit (5C or 5F) (See below) 10: Display mode for 2 digits below decimal point (See below)

DIP Switch Settings

The following diagram shows the functions of the DIP switch for the DRT1TS04T and DRT1-TS04P Temperature Input Terminals.

Node address

Two digits below decimal point Temperature unit

Baud rate

Pin(s) Function 1 through 6 Node address setting 7 and 8 9 10

Baud rate setting Temperature unit setting Display mode for 2 digits below the decimal (Refer to page 164.)

Settings Refer to 4-9-1 Node Address and Baud Rate Settings for details. OFF (factory setting)

°C

ON OFF (factory setting)

°F Normal mode (0 or 1 digit depending on input classification)

ON

Two digits below decimal point

Note Always turn OFF the Slave’s power supply (including the communications power supply) before changing any settings.

160

Page 176

Section 4-9

Temperature Input Terminals Rotary Switch Setting

Set the common input classification and input signal range for each input with the rotary switch. (The input classification and input range cannot be set for 4point classification.) Note Always turn OFF the Slave’s power supply (including the communications power supply) before changing any settings. DRT1-TS04T The following table shows the input classifications and input ranges according to the rotary switch settings.

0

Number R

Input classification

Range (°C) 0 to 1700

Range (°F) 0 to 3000

1 2

S K1

0 to 1700 –200 to 1300

0 to 3000 –300 to 2300

3 4

K2 J1

0.0 to 500.0 –100 to 850

0.0 to 900.0 –100 to 1500

5 6

J2 T

0.0 to 400.0 –200.0 to 400.0

0.0 to 750.0 –300.0 to 700.0

7 8

E L1

0 to 600 –100 to 850

0 to 1100 –100 to 1500

9 A

L2 U

0.0 to 400.0 –200.0 to 400.0

0.0 to 750.0 –300.0 to 700.0

B C

N W

–200 to 1300 0 to 2300

–300 to 2300 0 to 4100

D E

B PL II

100 to 1800 0 to 1300

300 to 3200 0 to 2300

F

Cannot be set.

DRT1-TS04P The following table shows the input classifications and input ranges according to the rotary switch settings.

Number 0

Input classification PT100

Range (°C) –200.0 to 650.0

Range (°F) –300.0 to 1200.0

1 2 to 9

JPT100 Cannot be set.

–200.0 to 650.0

–300.0 to 1200.0

161

Page 177

Section 4-9

Temperature Input Terminals Terminal Arrangement DRT1-TS04T Cold Junction Compensator

SOURCE 24 V DC

Input 0

Input 0

SOURCE 24 V DC −

Input 1

Input 2

Input 1

Input 2

Input 3

Input 3

Note Do not touch or remove the Cold Junction Compensator. DRT1-TS04P

SOURCE 24 V DC SOURCE 24 V DC

Wiring

Input 0 Input 0 Input 1 Input 1

Input 0

Input 1

Input 2 Input 2 Input 3 Input 3

Input 2

Input 3

Connect the inputs to the Temperature Input Terminal’s terminal block as shown in the following diagram, depending on whether thermocouple inputs or resistance temperature sensor inputs are used. Internal circuit power supply Source: 24 V DC

DRT1-TS04T Thermocouple input

DRT1-TS04P Resistance temperature sensor input

Internal circuit power supply

Temperature Conversion Data for the DRT1-TS04T and DRT1-TS04P

162

Data that is input is converted to binary data (4-digit hexadecimal) and the Master is notified. If the converted data is a negative number, it is expressed as a two’s complement.

Page 178

Section 4-9

Temperature Input Terminals

The four inputs occupy four words at the Master, as shown below. If the input classification is set for up to one digit below the decimal point, a multiple of 10 will be transmitted as binary data. Bit Beginning word

Input 0: Temperature conversion data

Beginning word + 1

Input 1: Temperature conversion data

Beginning word + 2

Input 2: Temperature conversion data

Beginning word + 3

Input 3: Temperature conversion data

Input classification

Unit: 1°C (°F)

R, S, K1, J1, E, L1, N, W, B, PL K2, J2, T, L2, U, Pt100, JPt100

Unit: 0.1°C (°F)

Note

850° → 0352 (4 digits hex) –200° → FF38 (4 digits hex) x10 500.0° → 5000 → 1388 (4 digits hex) –20.0° → 200 → FF38 (4 digits hex) –200.0° → 2000 → F830 (4 digits hex)

1. For more details regarding temperature conversion data with a unit setting of two digits below the decimal point (unit: 0.01), refer to page 164. 2. If there is a sudden temperature change, condensation may develop inside of the Terminal and cause incorrect values to be displayed. If condensation does develop, leave the Terminal for approximately one hour at a stable temperature before using it.

Data Ranges and the Open-circuit Detection Function

The following table shows the convertible data ranges according to the number set by the rotary switch. DRT1-TS04T Number

Input classification

Range (°C)

Range (°F)

0 1

R S

–20 to 1720 –20 to 1720

–20 to 3020 –20 to 3020

2 3

K1 K2

–220 to 1200 –20.0 to 520.0

–320 to 2320 –20.0 to 920.0

4 5

J1 J2

–120 to 870 –20.0 to 420.0

–120 to 1520 –20.0 to 770.0

6 7

T E

–220.0 to 420.0 –20 to 620

–320.0 to 720.0 –20 to 1120

8 9

L1 L2

–120 to 870 –20.0 to 420.0

–120 to 1520 –20.0 to 770.0

A B

U N

–220.0 to 420.0 –220 to 1320

–320.0 to 720.0 –320 to 2320

C D

W B

–20 to 2320 80 to 1820

–20 to 4120 280 to 3220

E F

PL II Cannot be set.

–20 to 1320

–20 to 2320

163

Page 179

Section 4-9

Temperature Input Terminals DRT1-TS04P Number 0

Input classification Range (°C) Pt100 –220.0 to 670.0

Range (°F) –320.0 to 1220.0

1 2 to 9

JPt100 Cannot be set.

–320.0 to 1220.0

–220.0 to 670.0

If the input temperature goes outside of the permissible conversion range, the temperature data is fixed at the upper or lower limit. If the input temperature goes beyond a given constant value, outside of the permissible conversion range, it is determined that the input wiring has been disconnected. The open-circuit detection function is then activated so that the temperature data is set to 7FFF (hexadecimal), and the broken wire indicator on the Temperature Input Terminal lights up. The open-circuit detection function will operate even if there is an error at the Cold Junction Compensator. When the input temperature returns to within the conversion range, the opencircuit detection function is automatically cleared and the conversion data is returned to normal. Temperature Input Terminal’s Display Mode for 2 Digits Below the Decimal Point

This section explains the Temperature Input Terminal’s display mode for 2 digits below the decimal point. When the Temperature Input Terminal is in this mode, each single item of temperature data (four integer digits and two digits below the decimal point, in six digits of hexadecimal binary data) is provided to the Master Unit multiplied by 100 with the sign affixed. At that time the temperature data is divided into two parts as shown below, and these parts are alternately transmitted every 125 ms. (The two respective data items are each configured as one word of data.)

!Caution In the display mode for 2 digits below the decimal point, temperature data is converted for up to two digits below the decimal point, but the actual resolution is not 0.01°C (°F). Therefore there may be some oscillation or jumping at the 0.01°C (°F) and 0.1°C (°F) digits. Resolutions beyond those prescribed for the normal mode should be treated as reference data.

164

Page 180

Section 4-9

Temperature Input Terminals

The following diagram shows how temperature data is divided and the data configuration.

Temperature data (Actual temperature x 100, in binary data)

Notification format for leftmost 3 digits Bit Left/right

Temp. unit

Broken wire

Not used.

0: Left 1: Right

0: C° 1: F°

0: OK 1: Error

0 (Fixed)

Sign/determination area

Data area

Notification format for rightmost 3 digits Bit Right/left

Temp. unit

Broken wire

Not used.

0: Left 1: Right

0: C° 1: F°

0: OK 1: Error

0 (Fixed)

Sign/determination area

Data area

Leftmost/rightmost bit: Determines whether leftmost or rightmost digits are displayed. Temperature unit bit:

Determines whether temperature is expressed in °C or °F.

Broken wire bit:

Turns ON (1) to notify of broken wire. At that time the data in the leftmost three digits is “7FF” and the data in the rightmost three digits is “FFF.”

The three leftmost digits and three rightmost digits, each comprising one word of data, are alternately provided to the Master every 125 ms as shown in the following diagram. 125 mms

125 mms

125 mms

Leftmost 3 digits

Rightmost 3 digits

Leftmost 3 digits

Time Data refresh

Data refresh

165