Section 4-8
Analog I/O Terminals
0 to 20 mA The 0- to 20-mA range corresponds to the hexadecimal values 0000 to 7530 (0 to 30,000). The convertible data range is FA24 to 7B0C (–1,500 to 31,500). When the current is negative, the negative number is expressed as a two’s complement. Converted data Hexadecimal (decimal) 7B0C (31500) 7530 (30000)
0000 (0) –1 mA FA24 (-1500)
Current 0 mA
20 mA 21 mA
4 to 20 mA The 4- to 20-mA range corresponds to the hexadecimal values 0000 to 7530 (0 to 30,000). The convertible data range is FA24 to 7B0C (–1,500 to 31,500). The 3.2- to 4-mA range corresponds to the hexadecimal values FA24 to 0000 (–1,500 to 0). If the current drops below the input range (i.e., if the current voltage drops below 3.2 mA), the open-circuit detection function is activated and the data is set to 7FFF. Converted data Hexadecimal (decimal) 7B0C (31500) 7530 (30000)
7FFF
0000 (0) FA24 (–1500)
Number of Inputs Setting (DRT1-AD04 Only)
3.2 mA 4 mA
Current 20 mA 20.8 mA
The number of inputs can be limited to two by turning ON pin 9 of the DIP switch. Changing the number of inputs from four to two reduces the sampling time from 8 ms/4 inputs to 4 ms/2 inputs, which provides faster conversion. If the number of inputs is two, the number of words allocated to the Input Terminal in the PLC is also reduced to 2 words. When only two inputs are used, inputs 0 and 1 are used (inputs 2 and 3 cannot be used.)
146
Page 162
Section 4-8
Analog I/O Terminals Averaging Function Setting (DRT1-AD04 Only)
With the DRT1-AD04, the averaging function can be enabled for all inputs (0 through 3) by turning ON pin 10 of the DIP switch. The averaging function outputs the average (a moving average) of the last eight input values as the converted value. Use this function to smooth inputs that vary like the one in the following diagram.
Actual input Input after averaging
Time
Note The time required for converted data refreshing remains 2 ms/point when the averaging function is enabled. The first communications data after the power is turned ON will be output after averaging eight samples. Open-circuit Detection Function
The open-circuit detection function is activated when the input range is set to 1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4 to 20 mA and the current drops below 3.2 mA. When the open-circuit detection function is activated, the converted data is set to FFFF for the DRT1AD04 and 7FFF for the DRT1-AD04H. In addition, with the DRT1-AD04H, the broken wire indicator lights when the open-circuit detection function is activated. The open-circuit detection function is enabled or cleared at the same time as the conversion time. If the input returns to the convertible range, the open-circuit detection is cleared automatically and the output returns to the normal range.
Converted Data
The converted data is transferred to the Master as shown in the following diagram. DRT1-AD04 Bit First word
Sign bit
Input 0 converted data
First word + 1
Sign bit
Input 1 converted data
First word + 2
Sign bit
Input 2 converted data*
First word + 3
Sign bit
Input 3 converted data*
Note *Not used when there are two input points. At that time only two words are occupied. The sign bit is turned ON to indicate that the converted value is negative; the converted value will be the absolute value (not the two’s complement).
147
Page 163
Section 4-8
Analog I/O Terminals
Example: When –300 is converted, the sign bit (bit 15) is set to 1 and 300 is output as the binary value as 12C hexadecimal. The contents of the word is thus 812C, as shown in the following illustration. 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
1
1
0
0
1
0
1
1
0
0
0
0
8 (163)
0
0
0
0
1 (162)
2 (161)
C (160)
DRT1-AD04H Bit First word
Input 0 converted data
First word + 1
Input 1 converted data
First word + 2
Input 2 converted data
First word + 3
Input 3 converted data
If the converted data is a negative number, it is expressed as a two’s complement. The NEG command can be useful to obtain the absolute value from the two’s complement.
Conversion Time DRT1-AD04 AD conversion values are refreshed every 2 ms for each input point. DRT1-AD04H AD conversion values are refreshed every 250 ms. It may take up to 650 ms, however, from when the step response is input until AD conversion data of 90% of that value can be transmitted.
148
Page 164
Section 4-8
Analog I/O Terminals Dimensions
The following diagram shows the dimensions for the DRT1-AD04 and DRT1AD04H Analog Input Terminals. All dimensions are in mm. Approx. 73
12
50 max.
(With connector attached)
40 max.
150 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
140± 0.3
4-8-3
Analog Output Terminal: DRT1-DA02
Specifications General Specifications Item
Specification Voltage outputs Current outputs
Output points Communications power supply voltage
2 points (allocated two words in the Master Unit.) 11 to 25 V DC (supplied from the communications connector)
Internal power supply voltage
20.4 to 26.4 V DC (24 V DC −15% to 10%)
Current consumption
Communications: 30 mA max. Internal circuit: 140 mA max.
Noise immunity
±1.5 kVp-p, pulse width: 0.1 to 1 µs, pulse rise time: 1 ns (via noise simulator)
Vibration resistance Shock resistance
10 to 55 Hz, 1.0-mm double amplitude 200 m/s2
Dielectric strength Insulation resistance
500 V AC for 1 min (between insulated circuits) 20 MΩ min. at 250 V DC (between insulated circuits)
Ambient operating temperature
0 to 55°C
Ambient operating humidity
35% to 85% (with no condensation)
149
Page 165
Section 4-8
Analog I/O Terminals Item
Specification Voltage outputs Current outputs
Ambient operating environment Ambient storage temperature Mounting method
No corrosive gases.
Mounting strength
50 N 10 N min. in the DIN Track direction
Terminal strength Weight
Pull: 50 N 160 g max.
−25 to 65°C M4 screw mounting or 35-mm DIN track mounting
Output signal range
1 to 5 V, 0 to 10 V, or –10 to 10 V Allowable external out- 1 KΩ min. put load resistance Output impedance 0.5 Ω max.
0 to 20 mA or 4 to 20 mA 600 Ω max. ---
Resolution Accuracy 25°C
1/6000 (full scale) ±0.4% FS
0 to 55°C Conversion time
±0.8% FS 4 ms/2 points
Conversion output data (Binary)
–10- to 10-V range: Other signal ranges:
Isolation method
Photocoupler isolation between analog outputs and communications lines (There is no isolation between analog output signals.)
8BB8 to 0 to 0BB8 full scale 0000 to 1770 full scale
Components DeviceNet Indicators (Refer to page 312.) Rotary switch Sets the output ranges.
Terminal block Connect the internal circuits power supply and the analog outputs.
DIN track mounting hooks
Communications connector
DIP switch (Refer to page 40.) Pins 1 to 6: Node address Pins address setting setting Pins 7 and 8: Baud rate Pins rate setting setting Pins 9 and 10: Outputt status Pins stat s after aftercommunications comm nicationserror error
150
Page 166
Section 4-8
Analog I/O Terminals DIP Switch Settings
The following diagram shows the functions of the DIP switch.
Node address setting
Output status after communications error
Baud rate
The following table summarizes the DIP switch settings. (All pins are factoryset to OFF.) Pin(s)
Function
Settings
1 through 6 Node address setting 7 and 8 Baud rate
Refer to 4-8-1 Node Address and Baud Rate Setting for details.
9 and 10
9 OFF
10 OFF
OFF ON ON
ON OFF ON
Output status at communications error. (See page 154 for details.)
Output Clear at “Low” (see below) (Factory setting) Clear at “High” (see below) Hold Hold
Outputs for “High” and “Low” Clear Pins 9 and 10 of the DIP switch determine the status of the outputs after a communications error occurs in DeviceNet communications. The following table shows the lower and upper limits of the output ranges for each output signal range setting. Output signal range
“Low”
“High”
–10 to 10 V 0 to 10 V
–11 V –0.5 V
11 V 10.5 V
1 to 5 V 0 to 20 mA
0.8 V 0 mA
5.2 V 21 mA
4 to 20 mA
3.2 mA
20.8 mA
Note Always turn OFF the Slave’s power supply (including the communications power supply) before changing any settings. Rotary Switch Setting
Set the output signal range for each output with the rotary switch. The following table shows the rotary switch settings and corresponding output signal range settings.
No.
Signal range for output 0
Signal range for output 1
0 1
1 to 5 V 1 to 5 V
1 to 5 V 0 to 10 V
2 3
1 to 5 V 1 to 5 V
–10 to 10 V 0 to 20 mA
4 5
1 to 5 V 0 to 10 V
4 to 20 mA 0 to 10 V
6 7
0 to 10 V 0 to 10 V
–10 to 10 V 0 to 20 mA
151
Page 167
Section 4-8
Analog I/O Terminals No. 8
Signal range for output 0 0 to 10 V
Signal range for output 1 4 to 20 mA
9 A
–10 to 10 V –10 to 10 V
–10 to 10 V 0 to 20 mA
B C
–10 to 10 V 0 to 20 mA
4 to 20 mA 0 to 20 mA
D E
0 to 20 mA 4 to 20 mA
4 to 20 mA 4 to 20 mA
F
(Setting not possible.)
Internal Circuits Photocoupler V+ CAN H
CAN L
Physical Photolayer coupler
V–
I+ V+
Internal circuitry
DRAIN
Output 0
–
I+ SOURCE 24 V DC + SOURCE 24 V DC –
Output 1
V+
DC-DC converter (Isolated)
– Analog GND
Terminal Arrangement
SOURCE 24 V DC + SOURCE 24 V DC −
152
+
–
+
+
–
+
Page 168
Section 4-8
Analog I/O Terminals Wiring
Connect the power supply and outputs (voltage output or current output) to the Analog Output Terminal’s terminal block as shown in the following diagram. Internal circuits power supply
Voltage output connection
SOURCE 24 V DC
V+
–
Current output connection V+
I+
–
I+
+
– –
+
Internal circuits power supply External device
Output Ranges and Converted Data
External device
+ –
+ –
The Analog Output Terminal converts the digital output data to analog values. The analog values depend on the output signal ranges, as shown in the following diagrams. –10- to 10-V Outputs The hexadecimal values 8BB8 to 0BB8 (–3000 to 3000) correspond to an analog voltage range of –10 to 10 V. The entire output range is –11 to 11 V. Voltage 11 V 10 V 8CE4 8BB8 FFFF (–3300) (–3000) 0000 (0) 0V
Converted data Hexadecimal 0BB8 0CE4 7FFF (Decimal) (3000) (3300)
–10 V –11 V
0- to 10-V Outputs The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 0 to 10 V. The entire output range is –0.5 to 10.5 V. Voltage 10.5 V 10 V
0V FFFF 812C (–300) –0.5 V
0000 (0)
Converted 1770 189C 7FFF data Hexadecimal (6000) (6300) (Decimal)
153
Page 169
Section 4-8
Analog I/O Terminals 1- to 5-V Outputs
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V. Voltage 5.2 V 5V
1V 0.8 V 0V FFFF 812C 0000 (0) (–300)
Converted data 1770 189C 7FFF Hexadecimal (Decimal) (6000) (6300)
0- to 20-mA Outputs The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 0 to 20 mA. The entire output range is 0 to 21 mA. Current 21 mA 20 mA
0 mA 0000 (0)
FFFF
Converted data 1770 189C 7FFF Hexadecimal (Decimal) (6000) (6300)
4- to 20-mA Outputs The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 4 to 20 mA. The entire output range is 3.2 to 20.8 mA. Current 20.8 mA 20 mA
4 mA 0V FFFF
Output Status after Communications Error
812C 0000 (0) (–300)
Converted data 1770 189C 7FFF Hexadecimal (Decimal) (6000) (6300)
Pins 9 and 10 of the DIP switch determine the status of the outputs after a communications error occurs in DeviceNet communications. Hold: Low: High:
154
3.2 mA
Maintains the previous output status. Clears to the lower limit of the output signal range. Clears to the upper limit of the output signal range.
Page 170
Section 4-8
Analog I/O Terminals
The following table shows the lower and upper limits of the output ranges for each output signal range setting.
Converted Data
Output signal range –10 to 10 V
“Low”
“High”
–11 V
11 V
0 to 10 V 1 to 5 V
–0.5 V 0.8 V
10.5 V 5.2 V
0 to 20 mA 4 to 20 mA
0 mA 3.2 mA
21 mA 20.8 mA
Output the converted data to the Master as shown in the following diagram. Bit Sign bit
Output 0 converted data
First word + 1 Sign bit
Output 1 converted data
First word
The sign bit is turned ON to indicate that the converted value is negative, at which time the converted value will be an absolute value.
Dimensions The following diagram shows the dimensions for the DRT1-DA02 Analog Output Unit. All dimensions are in mm. Approx. 73
Unit: mm
12
50 max.
(With connector attached)
150 max.
40 max.
Mounting holes
40 ± 0.3
Two, 4.2 dia. or M4
140 ± 0.3
155