Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 16 of 39

C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 151 to 160

Pages 151 to 160 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual

The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron DRT1-ID16

Page 151

Section 4-8

Analog I/O Terminals so that you do not distort it. Press the cover in until there is no gap between the cover and connector plug.

Connecting and Disconnecting the Cable Connector Connecting With terminal number 1 toward the front, insert the Cable Connector into the I/ O connector on the Slave until it clicks into place. Disconnecting Lift up on the lock lever as shown in the following diagram and remove the Cable Connector to disconnect it.

Lock lever

Note Cable Connectors (XS8A-0441/0442) are not provided with the Sensor Terminals and must be purchased separately.

4-8

Analog I/O Terminals

4-8-1

Node Address and Baud Rate Setting This section describes the Slaves’ node address setting, baud rate settings, and hold/clear outputs for communications error setting. These settings are made using the following pins on the DIP switch. Pins 1 through 6 Pins 7 and 8

Slave-specific setting:

Pins 9 and 10 (Refer to the descriptions of individual Slaves.)

ON

Node address setting: Baud rate setting:

1 2 3 4 5 6 7 8 9 10

Node address setting Baud rate setting

136

Slave-specific setting: Refer to the description of individual Slaves.

Page 152

Analog I/O Terminals

Section 4-8

Node Address Settings

Each Slave’s node address is set with pins 1 through 6 of the Slave’s DIP switch. Any node address within the setting range can be used as long as it isn’t already set on another node. Pin 6

DIP switch setting Pin 5 Pin 4 Pin 3 Pin 2

Node address Pin 1

0 0

0 0

0 0

0

0

0

0 0

0 0

0 1

0 (default) 1

0

1

0

2

: :

: :

1

1

1

1

0

1

61

1 1

1 1

1 1

1 1

1 1

0 1

62 63

0: OFF, 1: ON Note

1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).

Baud Rate Setting

Pins 7 and 8 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin 7

Note

Pin 8

OFF

OFF

125 kbps (default)

ON OFF

OFF ON

250 kbps 500 kbps

ON

ON

Not allowed.

1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate may cause communications errors between nodes with correct baud rate settings.

4-8-2

Analog Input Terminals: DRT1-AD04 and DRT1-AD04H

Specifications General Specifications Item

Specification DRT1-AD04 Voltage inputs Current inputs

DRT1-AD04H Voltage inputs Current inputs

Input points

Either 4 points or 2 points 4 points (Set with the DIP switch.) (Master Unit uses 4 (Four input words occupied at Master Unit.) input words or 2 input words respectively) Communications power 11 to 25 V DC (supplied from the communications connector) supply voltage Internal power supply voltage

20.4 to 26.4 V DC (24 V DC −15% to 10%)

137

Page 153

Section 4-8

Analog I/O Terminals Item

Specification DRT1-AD04

DRT1-AD04H

Current consumption

Voltage inputs Current inputs Communications: 30 mA max. Internal circuit: 80 mA max.

Voltage inputs Current inputs Communications: 30 mA max. Internal circuit: 130 mA max.

Noise immunity

±1.5 kVp-p, pulse width: 0.1 to 1 µs, pulse rise time: 1 ns (via noise simulator)

Vibration resistance Shock resistance

10 to 55 Hz, 1.0-mm double amplitude 200 m/s2

Dielectric strength Insulation resistance

500 V AC for 1 min (between insulated circuits) 500 V AC (between insulated circuits) 20 MΩ min. at 250 V DC (between insulated circuits)

Ambient operating tem- 0 to 55°C perature Ambient operating 35% to 85% (with no condensation) humidity Ambient operating envi- No corrosive gases. ronment Ambient storage tem−25 to 65°C perature Mounting method M4 screw mounting or 35-mm DIN track mounting Mounting strength Terminal strength Weight Input signal range

50 N 10 N min. in the DIN Track direction Pull: 50 N

Max. signal input

160 g max. 0 to 5 V, 1 to 5 V, 0 to 10 V, or –10 to 10 V ±15 V

Input impedance Resolution

1 MΩ min. 1/6000 (full scale)

Approx. 250 Ω

1 MΩ min. 1/30000 (full scale)

Approx. 250 Ω

Accuracy

±0.3% FS ±0.6% FS

±0.4% FS ±0.8% FS

±0.3% FS ±0.6% FS

±0.4% FS ±0.8% FS

25°C 0 to 55°C

0 to 20 mA or 4 to 20 mA ±30 mA

0 to 5 V, 1 to 5 V or 0 to 10 V, ±15 V

0 to 20 mA or 4 to 20 mA ±30 mA

Conversion time Converted output data (Binary)

2 ms/input (8 ms/4 points, 4 ms/2 points) Binary (4-digit hexadecimal)

Averaging function Open circuit detection

Settable (via DIP switch) Provided.

Isolation method

Photocoupler isolation between analog inputs Photocoupler isolation between analog inputs and communications lines and communications lines (There is no isolation between analog input sig- Photocoupler isolation between analog input nals.) signals.

138

–10- to 10-V range: scale Other signal ranges:

8BB8 to 0 to 0BB8 full

250 ms/4 points Binary (4-digit hexadecimal) 0000 to 7530 (hexadecimal) full scale

0000 to 1770 full scale Not provided. Provided.

Page 154

Section 4-8

Analog I/O Terminals Components of the DRT1-AD04 and DRT1-AD04H DeviceNet Indicators

(Refer to page 312.)

Rotary switch Sets the input ranges.

Open-circuit Indicators (DRT1-AD04H only) (Refer to page 147.) Corresponding indicator lights when open circuit is detected.

Terminal block

DIN track mounting hooks

Communications connector

DIP switch Pins 1 to 6: Node address setting (Refer to page 124.) Pins 7 and 8: Baud rate setting (Refer to page 124.) Pin 9: Number of inputs setting (4 points or 2 points) [DRT1-AD04 only] (Refer to page 146.) Pin 10: Averaging function setting [DRT1-AD04 only] (Refer to page 147.)

DIP Switch Settings

The following diagram shows the functions of the DIP switch on the DRT1AD04 and DRT1-AD04H Analog Input Terminals.

Node address setting Baud rate

DRT1-AD04 Averaging function setting Number of inputs setting (4 pts. or 2 pts.)

DRT1-AD04H Not used. (must be OFF.)

139

Page 155

Section 4-8

Analog I/O Terminals

The following table summarizes the DIP switch settings. (All pins are factoryset to OFF.) Pin(s)

Function

1 through 6

Node address setting

7 and 8 9

Baud rate Number of inputs setting (2 or 4) (See page 146 for details.) Averaging function (See page 147 for details.)

10

Settings

Setting contents DRT1-AD04 DRT1-AD04H

Refer to 4-8-1 Node Address and Baud Rate Setting for details. (Factory-set to OFF.) OFF*

4 points

ON

2 points

OFF*

Averaging is not performed. (Factory setting) Averaging is performed.

ON

Not used. (Must be OFF.)

Not used. (Must be OFF.)

* Factory settings. Note Always turn OFF the Slave’s power supply (including the communications power supply) before changing any settings. Rotary Switch Setting

Set the input signal range for each input with the rotary switch. Inputs 0 and 2 share the same signal range, as do inputs 1 and 3. The voltage input/current input selection is carried out by connecting the V+ terminal to the I+ terminal. Short-circuit the V+ terminal and I+ terminal when inputting current. Note Always turn OFF the Slave’s power supply (including the communications power supply) before changing any settings. DRT1-AD04 0 1

2 3

7 8

9

4

5 6

The following table shows the rotary switch settings and corresponding input signal range settings. No.

140

Signal range for inputs 0 and 2

Signal range for inputs 1 and 3

0 1

0 to 5 V or 0 to 20 mA 0 to 5 V or 0 to 20 mA

0 to 5 V or 0 to 20 mA 1 to 5 V or 4 to 20 mA

2 3

0 to 5 V or 0 to 20 mA 0 to 5 V or 0 to 20 mA

0 to 10 V –10 to +10 V

4 5

1 to 5 V or 4 to 20 mA 1 to 5 V or 4 to 20 mA

1 to 5 V or 4 to 20 mA 0 to 10 V

6 7

1 to 5 V or 4 to 20 mA 0 to 10 V

–10 to +10 V 0 to 10 V

8 9

0 to 10 V –10 to +10 V

–10 to +10 V –10 to +10 V

Page 156

Section 4-8

Analog I/O Terminals DRT1-AD04H

The following table shows the rotary switch settings and corresponding input signal range settings. No.

Internal Circuits

0

Signal range for inputs 0 and 2 0 to 5 V

Signal range for inputs 1 and 3 0 to 5 V

1 2

0 to 5 V 0 to 5 V

1 to 5 V 0 to 10 V

3 4

0 to 5 V 0 to 5 V

0 to 20 mA 4 to 20 mA

5 6

1 to 5 V 1 to 5 V

1 to 5 V 0 to 10 V

7 8

1 to 5 V 1 to 5 V

0 to 20 mA 4 to 20 mA

9 A

0 to 10 V 0 to 10 V

0 to 10 V 0 to 20 mA

B C

0 to 10 V 0 to 20 mA

4 to 20 mA 0 to 20 mA

D E

0 to 20 mA 4 to 20 mA

4 to 20 mA 4 to 20 mA

F

(Cannot be set.)

The following diagram shows the internal circuits for the DRT1-AD04 Analog Input Terminal. DRT1-AD04 Photocoupler V+

V+ CAN H DRAIN CAN L

510 kΩ Physical Photolayer coupler

250 Ω

–

V+ Internal circuitry

SOURCE 24 V DC –

Input 0

510 kΩ

V–

SOURCE 24 V DC +

I+

DC-DC converter (Isolated)

510 kΩ

250 Ω

510 kΩ 510 kΩ

I+

Input 1

–

V+ 250 Ω

I+

Input 2

–

510 kΩ V+ 510 kΩ

250 Ω

I+

Input 3

–

510 kΩ

Analog GND

141

Page 157

Section 4-8

Analog I/O Terminals

Note The DRT1-AD04H has insulation between the inputs, so there is no need for the user to be concerned with the internal circuitry.

Terminal Arrangement DRT1-AD04

SOURCE 24 V DC + SOURCE 24 V DC ±

+

+

+

+

+

+

+

±

±

±

+

±

DRT1-AD04H

SOURCE 24 V DC + SOURCE 24 V DC −

Wiring: DRT1-AD04 and DRT1-AD04 H (Common)

Connect the power supply and inputs (voltage input or current input) to the Analog Input Terminal’s terminal block as shown in the following diagram. Internal circuits power supply SOURCE 24 V DC

Voltage input connection

Current input connection

V+

V+

I+

I+

+ –

– – –

+ Shield

Shield

Internal circuits power supply 0V

0V (With current inputs, short-circuit the V+ and I+ terminals.)

Do not connect the shield when using shielded cables for the inputs. Input Ranges and Converted Data

The Analog Input Terminal converts analog input data to digital values. The digital values depend on the input signal ranges, as shown in the following diagrams. Note When the input exceeds the specified range, the AD conversion data will be fixed at either the lower limit or upper limit.

142

Page 158

Section 4-8

Analog I/O Terminals DRT1-AD04 –10- to 10-V Inputs

The –10- to 10-V range corresponds to the hexadecimal values 8BB8 to 0BB8 (–3000 to 3000). The most significant bit (bit 15) is set to 1 (ON) for negative values and the AD conversion data is set to the absolute values; the rest of the word indicates the absolute value. The entire data range is 8CE4 to 0CE4 (–3300 to 3300). Converted data Hexadecimal (decimal) 0CE4 (3300) 0BB8 (3000)

0000 (0)

–11 V –10 V

0V

Voltage 10 V 11 V

8BB8 (–3000) 8CE4 (–3300)

0- to 10-V Inputs The 0- to 10-V range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The most significant bit (bit 15) is set to 1 (ON) for negative values and the AD conversion data is set to the absolute values; the rest of the word indicates the absolute value. The entire data range is 812C to 189C (–300 to 6300). Converted data Hexadecimal (decimal) 189C (6300) 1770 (6000)

0000 (0) – 0.5 V 812C (–300)

0V

10 V

Voltage 10.5 V

0- to 5-V Inputs The 0- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The most significant bit (bit 15) is set to 1 (ON) for negative values and the AD conversion data is set to the absolute values; the rest of the word indicates the absolute value. The entire data range is 812C to 189C (–300 to 6300). Converted data Hexadecimal (decimal) 189C (6300) 1770 (6000)

0000 (0) – 0.25 V 812C (–300)

0V

Voltage 5 V 5.25 V

143

Page 159

Section 4-8

Analog I/O Terminals

1- to 5-V Inputs The 1- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The most significant bit (bit 15) is set to 1 (ON) for voltages from 0.8 V to 1 V and the AD conversion data is set to the absolute values; the rest of the word indicates the absolute value. The entire data range is 812C to 189C (–300 to 6300). If the input voltage falls below 0.8 V, the open-circuit detection function is activated and the converted data is set to FFFF. Converted data Hexadecimal (decimal) 189C (6300) 1770 (6000)

FFFF

0000 (0)

0.8 V

812C (–300)

1V

Voltage 5 V 5.2 V

0- to 20-mA Inputs The 0- to 20-mA range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The most significant bit (bit 15) is set to 1 (ON) for negative values and the AD conversion data is set to the absolute values; the rest of the word indicates the absolute value. The entire data range is 812C to 189C (–300 to 6300). Converted data Hexadecimal (decimal) 189C (6300) 1770 (6000)

0000 (0) –1 mA 0 mA

812C (–300)

Current 20 mA 21 mA

4- to 20-mA Inputs The 4- to 20-mA range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The most significant bit (bit 15) is set to 1 (ON) for currents from 3.2 to 4 mA and the AD conversion data is set to the absolute values; the rest of the word indicates the absolute value. The entire data range is 812C to 189C (–300 to 6300). If the input current falls below 3.2 mA, the open-circuit detection function is activated and the converted data is set to FFFF. Converted data Hexadecimal (decimal) 189C (6300) 1770 (6000)

FFFF

0000 (0) 812C (–300)

144

3.2 mA 4 mA

Current 20 mA 20.8 mA

Page 160

Section 4-8

Analog I/O Terminals DRT1-AD04H

0 to 10 V The 0- to 10-V range corresponds to the hexadecimal values 0000 to 7530 (0 to 30,000). The convertible data range is FA24 to 7B0C (–1,500 to 31,500). When the voltage is negative, the negative number is expressed as a two’s complement. Converted data Hexadecimal (decimal) 7B0C (31500) 7530 (30000)

0000 (0) –0.5 V FA24 (-1500)

Voltage 0V

10 V 10.5 V

0 to 5 V The 0- to 5-V range corresponds to the hexadecimal values 0000 to 7530 (0 to 30,000). The convertible data range is FA24 to 7B0C (–1,500 to 31,500). When the voltage is negative, the negative number is expressed as a two’s complement. Converted data Hexadecimal (decimal) 7B0C (31500) 7530 (30000)

0000 (0) –0.25 V FA24 (-1500)

Voltage 0V

5 V 5.25 V

1 to 5 V The 1- to 5-V range corresponds to the hexadecimal values 0000 to 7530 (0 to 30,000). The convertible data range is FA24 to 7B0C (–1,500 to 31,500). The 0.8- to 1-V range corresponds to the hexadecimal values FA24 to 7B0C (–1,500 to 0). If the voltage drops below the input range (i.e., if the input voltage drops below 0.8 V), the open-circuit detection function is activated and the data is set to 7FFF. Converted data Hexadecimal (decimal) 7B0C (31500) 7530 (30000)

7FFF

0000 (0) FA24 (–1500)

0.8 V 1V

Voltage 5 V 5.2 V

145