Page 211
Section 5-3
Environment-resistive Terminals (IP66) Wiring
The following diagram shows the wiring of the DRT1-MD16C Environmentresistive Terminal (NPN).
Input 0
Input 5
Input 2
Input 7
Black (white)
Blue (black)
Brown (white)
Input 3
Blue (black)
Output 1
Input 6
Output 5
Output 2
Solenoid
Valve
Output 6
Output 7
Internal circuits Output power power supply supply
NPN output 3-wire sensor (photoelectric or proximity sensor)
2-wire sensor (limit switch)
(End surface)
Output 4
Output 3
Brown (red)
Input 1
Output 0
Input 4
The following diagram shows the wiring of the DRT1-MD16C-1 Environmentresistive Terminal (PNP). Input CN3
CN4
CN5
4 Input 0 3 G
Output CN6
CN7
3 G
2 Input 1
4 Input 2 3 G
1 V
3 G
2 Input 5
2 Input 3
CN10
CN2
4 Output 4
1 V
3 G
4 Input 6
2 Output 1
1 V
3 G
3 G
1 V
CN9
4 Output 0
4 Input 4
1 V
CN8
2 Input 7
Output 42
3
1 V
4
2 Output 5
1 V 2 Output
CN1 (End surface) 2
CAN H 4 5
1
1 DRAIN
4 Output 6
3 G
CAN L 3
V−
2 V+
1 V 2 Output 7
2-wire sensor (limit switch)
Brown (red)
Black (white)
Blue (black)
Brown (white)
Blue (black)
3
−
Valve
Solenoid
+
−
+
Internal circuits Output power power supply supply
PNP output 3-wire sensor (photoelectric or proximity sensor)
Note
1. External power supply line 0V and input line G are connected internally, as are external power supply line 24V and input line V. When input power is supplied to external power supply connectors, power can be supplied to sensors from input lines G and V provided that the total current does not exceed 1.0 A. If the total current exceeds 1.0 A, the power must not be supplied from the connector; it must be supplied externally instead. 2. External power supply line 0V and output line G are connected internally, as are external power supply line 24V and output line V. When output power is supplied to external power supply connectors, power can be supplied to output devices from output lines G and V provided that the total current
196
Page 212
Environment-resistive Terminals (IP66)
Section 5-3 does not exceed 2.4 A. If the total current exceeds 2.4 A, the power must not be supplied from the connector; it must be supplied externally instead. 3. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors. Dimensions
The following diagram shows the dimensions for the DRT1-MD16C and DRT1-MD16C-1 Environment-resistive Terminals. All dimensions are in mm.
Four, M5
Mounting Holes When screw mounting from the front
When screw mounting from the rear
5-3-7
Four, 4.2 dia. or M4
Four, 5.4 dia.
Mounting screw Nut
Mounting screw
Mounting in Control Panels Use screws to mount an Environment-resistive Terminal in a control panel. These Terminals cannot be mounted on a DIN Track. Attaching the Terminal from the Front The Terminals are tapped with M5 threads, so use M4 screws to clear the threads and attach the Terminal to the control panel from the front. Drill the mounting holes in the control panel according to the dimensions shown in the dimensions diagrams and secure the Terminal with M4 screws. The appropriate tightening torque is 0.6 to 1.18 N⋅m. Attaching the Terminal from the Rear Drill the mounting holes in the control panel according to the dimensions shown in the dimensions diagrams and secure the Terminal with M5 screws. The appropriate tightening torque is 1.47 to 1.96 N⋅m.
197
Page 213
Section 5-3
Environment-resistive Terminals (IP66) Installation Direction
The Terminal can be mounted in any direction. Any one of the following 6 directions is acceptable. Vertical
5-3-8
Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines
Wiring the Internal Power Supply and I/O Power Supply
The internal power supply and I/O power supply are supplied from the external power supply connectors. Connect the external power supply to the Terminal with an XS2-series Round Waterproof Connector listed in the following table. Compatible Connectors Connector Cable with connectors on both ends (socket and plug)
Model number XS2W-D42@-@81-@
Cable with connector on one end (female socket) Connector socket assembly (female) (Crimp-connector or solder type) T-joint
XS2F-D42@-@80-@ XS2C-D4@@
DRT1-OD08C
CS2R-D427-5 DRT1-ID08C
Shared I/O and internal power supply
Shared I/O and internal power supply
XS2W-D42@-@81-@ Cables with shielded socket on one end and plug on the other
Power supply
XS2R-D427-5 T-joint
XS2F-D42@-@80-@ Cable with shielded socket on one end
Note
XS2R-D427-5 T-joint XS2W-D42@-@81-@ Cable with shielded socket on one end and plug on the other
1. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environmental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors. 2. The same I/O power supply can be used for both input and output devices, but the noise from the output devices may cause the input devices to malfunction. Use separate power supplies if possible.
I/O Wiring
Connect the I/O Wiring to the Environment-resistive Terminal with the XS2series Round Waterproof Connectors listed in the following table. Compatible Connectors
198
Connector Cable with connector on one end (male plug)
Model number XS2H-D421-@80-A
Cable with connectors on both ends (socket and plug) Connector plug assembly (male) (Crimp-connector or solder type)
XS2W-D42@-@81-A XS2G-D4@@
Page 214
Section 5-3
Environment-resistive Terminals (IP66)
Sensors that are pre-wired with a connector can be connected directly. Refer to the Catalog or manual for details on the device’s connections before connecting any device. XS2W-D42@-@81-A Cable with shielded socket on one end and plug on the other
XS2H-D421-@80-A Cable with shielded plug on one end
Sensor with attached connector XS2G-D4@@
Pre-wired Sensor
Pre-wired Sensor with connector
Note
1. Refer to the OMRON Sensors Catalog (X42-E1-3) for more details on the sensor connections and Round Waterproof Connectors. 2. One of the Y-joints listed in the following table will be needed when connecting sensors or limit switches to an Environment-resistive Terminal with 16 inputs (DRT1-HD16C(-1)) or 16 outputs (DRT1-WD16C(-1)). Connector
Model number
Y-joint with plug/socket (with cable) Y-joint with plug/socket (no cable)
XS2R-D426-@11F XS2R-D426-1
XS2R-D426-@11F Y-joint with cable Terminal with 16 inputs or 16 outputs
XS2R-D426-1 Y-joint without cable
Note An XS2G Connector Assembly (screw-in wire connection) cannot be connected to a Y-joint Connector. A crimp-connector or soldered connector can be connected to a a Y-joint Connector. XS2R-D426-@11F Y-joint Connector with Cable Wiring diagram
45.5
15
4.6 dia.
CN1 35
1 2 3 4
CN2 6 dia.
18 CN2
8.5
Blue mark
44.7
13.6
1 2 3 4
CN1
L
4 3 2 1
XS2R-D426-1 Y-joint Connector without Cable 7
15
Wiring diagram
27 4.5 dia.
CN2 CN0 (37)
CN2
4 3 2 1
CN1
4 3 2 1
24.5
18 12.5
CN1 58.3
4 3 CN0 2 1
Blue mark
199
Page 215
Section 5-4
Waterproof Terminals (IP67)
Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environmental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors. Always cap unused connectors with an XS2Z-12 Waterproof Cover or XS2Z15 Dust Cover, shown in the following diagram. XS2Z-12 Waterproof Cover
XS2Z-15 Dust Cover
The connector will meet IP66 standards if a Waterproof Cover is attached. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m.
Press the Dust Cover onto the connector firmly. The Dust Cover will protect the connector from dust, but does not meet IP66 standards.
Maintaining Environmental Resistance
• The IP66 environmental resistance level will be lost if the surfaces where the contact block and cover meet are subjected to excessive force. Protect the contact block and cover from excessive force or shock. • The IP66 standard is lower than waterproof standards. Do not submerge the system components. • The body of the components is plastic resin. Do not place objects on the components or allow the components to be stepped on. There are two kinds of wiring for OMRON 2-wire Proximity Switches (prewired with connector). One kind has IEC pin allocation (M1GJ type) and the other has OMRON pin allocation (M1J type). Refer to the following table to determine the appropriate Environment-resistive Terminal to use with each kind of switch. Proximity Switch
Compatible Terminals
IEC pin allocation (M1GJ type)
DRT1-HD16C-1 DRT1-MD16C-1
OMRON pin allocation (M1J type)
DRT1-ID08C DRT1-HD16C DRT1-MD16C
5-4
Waterproof Terminals (IP67)
5-4-1
Node Address, Baud Rate, and Output Hold/Clear Settings This section describes the node address setting, baud rate setting, and the hold/clear outputs for communications error setting. These settings are common to all of the Waterproof Terminals and are made on the shown in the following diagrams. Node address setting: Baud rate setting: Output hold/clear setting: O N
0 1
1 2 3 4
2 3
7 8
9
5 6
2 3
7 8
0 1
4
9
Rotary switches Pins 1 and 2 Pin 4 (affects only outputs)
Output hold/clear setting for communications errors (for outputs)
4
5 6
Reserved (Always OFF.) Node address setting
200
Baud rate setting
Page 216
Section 5-4
Waterproof Terminals (IP67) Node Address Setting
Each Waterproof Terminal’s node address is set in two-digit decimal with the rotary switches. The 10’s digit is set on the left rotary switch and the 1’s digit is set on right rotary switch. Any node address within the allowed setting range can be used as long as it isn’t already set on another node. The Waterproof Terminal won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error). Note The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).
Baud Rate Setting
Pins 1 and 2 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin settings Pin 1
Note
Baud rate
Pin 2
OFF
OFF
125 kbps (default)
ON OFF
OFF ON
250 kbps 500 kbps
ON
ON
Not allowed.
1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate setting may cause communications errors between nodes with correct baud rate settings.
ON
The functions of pins 3 and 4 differ for inputs and outputs, as shown in the following diagram. (Pins 3 and 4 are factory-set to OFF.)
3 4
Output Hold/Clear Setting
Input: Not used (Always OFF) Output: Hold/Clear outputs for communications error Reserved: Always OFF
Pin 3:
Reserved (Always OFF)
Pin 4:
As follows:
Inputs: No function (Always OFF) Outputs: Hold/Clear outputs for communications error OFF (Clear): All output data from the Master will be cleared to 0 when a communications error occurs. ON (Hold): All output data from the Master will be retained when a communications error occurs.
201
Page 217
Section 5-4
Waterproof Terminals (IP67)
5-4-2
Waterproof Terminal (IP67) with 4 Transistor Inputs: DRT1-ID04CL (NPN) and DRT1-ID04CL-1 (PNP)
Input Specifications Item
Specification DRT1-ID04CL-1
Model
DRT1-ID04CL
Internal I/O common Input points
NPN PNP 4 points (Uses one word in Master.)
ON voltage
15 V DC min. (between each input terminal and V)
15 V DC min. (between each input terminal and G)
OFF voltage
5 V DC max. (between each input terminal and V)
5 V DC max. (between each input terminal and G)
OFF current Input current
1 mA max. 6 mA max./point at 24 V DC 6 mA max./point at 24 V DC 3 mA max./point at 17 V DC 3 mA max./point at 17 V DC (between each input termi- (between each input terminal and V) nal and G)
ON delay time OFF delay time
1.5 ms max. 1.5 ms max.
Number of circuits
4 points with one common
Components of the DRT1-ID04CL and DRT1-ID04CL-1 DeviceNet indicators (Refer to page 312.)
Input indicators Indicate the input status of each contact. (Lit when the input is ON.)
Bus DRT1
Rotary Switches 1 and 2: Node address setting (Refer to page 200.)
DeviceNet communications connector
MS NS
IN
Internal Circuits
I/O PWR
DIP switch: Pins 1 and 2: Baud rate setting Pins 3 and 4: Reserved (Always OFF.) (Refer to page 200.)
External power supply connector
Input connector
The following diagram shows the internal circuits for the DRT1-ID04CL Waterproof Terminal (NPN). G 3 4
2 1
V
CAN-L 4 V1 5 3 2
V+
DRAIN
Internal circuitry
CAN-H
IN0 G
4 3
1
IN1 G
4 3
1 2
202
V
2
V
Page 218
Section 5-4
Waterproof Terminals (IP67)
The following diagram shows the internal circuits for the DRT1-ID04CL-1 Waterproof Terminal (PNP). G 3 4
2 1
CAN-H CAN-L 4 V1 5 3 2
V+
Internal circuitry
V
IN0 G
4 3
1
V
2
IN1 G
DRAIN
4 3
1
V
2
The following diagram shows the wiring of the DRT1-ID04CL Waterproof Terminal (NPN). CAN H 4 5 1 DRAIN
CAN L 3
V−
3 G 2 NC
2 V+
3 G 4 Input 0
2 NC
1 V
1 V
1 V
2 3
1
4 Input 1
4
1 V 2 NC
4 Input 3
3 G
2 NC 3 G
+
2-wire sensor (limit switch)
Brown (red)
Blue (black)
Blue (black)
I/O power supply
Brown (white)
−
4 Input 2
Black (white)
Wiring
NPN output 3-wire sensor (photoelectric or proximity sensor)
The following diagram shows the wiring of the DRT1-ID04CL-1 Waterproof Terminal (PNP). CAN H 4 5 1 DRAIN
CAN L 3
V−
3 G 2 NC
2 V+
2 3
1 4
3 G 4 Input 0
1 V
1 V
1 V
4 Input 1
2 NC
Input 2
4
2 NC
Input 3
3 G
2-wire sensor (limit switch)
Brown (red)
Black (white)
Blue (black)
Brown (white)
Blue (black)
+
I/O power supply
Note
4
1 V
3 G −
2 NC
PNP output 3-wire sensor (photoelectric or proximity sensor)
1. External power supply line 0V and input line G are connected internally, as are external power supply line 24V and input line V. When input power is
203
Page 219
Section 5-4
Waterproof Terminals (IP67)
supplied to external power supply connectors, power can be supplied to sensors from input lines G and V provided that the total current does not exceed 1.0 A. If the total current exceeds 1.0 A, the power must not be supplied from the connector; it must be supplied externally instead. 2. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors. Dimensions
The following diagram shows the dimensions for the DRT1-ID04CL and DRT1-ID04CL-1 Waterproof Terminals. All dimensions are in mm. 45 114
10
MS
54
Bus DRT1 NS
IN
I/O PWR
30 Mounting holes
10.5±0.1
10.5±0.1
Three, 4.0 dia. or M4
5-4-3
104±0.2
Waterproof Terminal (IP67) with 8 Transistor Inputs: DRT1-ID08CL (NPN) and DRT1-ID08CL-1 (PNP)
Input Specifications Item Model
DRT1-ID08CL
Internal I/O common Input points
NPN PNP 8 points (Uses one word in Master.)
ON voltage
15 V DC min. (between each input terminal and V) 5 V DC max. (between each input terminal and V) 1 mA max.
OFF voltage OFF current Input current
204
Specification DRT1-ID08CL-1
15 V DC min. (between each input terminal and G) 5 V DC max. (between each input terminal and G)
ON delay time
6 mA max./point at 24 V DC 6 mA max./point at 24 V DC 3 mA max./point at 17 V DC 3 mA max./point at 17 V DC (between each input termi- (between each input terminal and V) nal and G) 1.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with one common
Page 220
Section 5-4
Waterproof Terminals (IP67) Components of the DRT1-ID08CL and DRT1-ID08CL-1 DeviceNet indicators (Refer to page 312.)
Input indicators Indicate the input status of each contact. (Lit when the input is ON.)
Bus DRT1
Rotary Switches 1 and 2: Node address setting (Refer to page 200.)
DeviceNet communications connector
MS NS
IN
External power supply connector
Input connector
The following diagram shows the internal circuits for the DRT1-ID08CL Waterproof Terminal (NPN). G 3 4
2 1
V
CAN-L 4 V1 5 3 2
V+
Internal circuitry
CAN-H
DRAIN
IN0 G
4 3
1
V
2
IN1 G
4 3
1
V
2
The following diagram shows the internal circuits for the DRT1-ID08CL-1 Waterproof Terminal (PNP). G 3 4
2 1
V
CAN-H CAN-L 4 V1 5 3 2
V+
DRAIN
Internal circuitry
Internal Circuits
I/O PWR
DIP switch: Pins 1 and 2: Baud rate setting Pins 3 and 4: Reserved (Always OFF.) (Refer to page 200.)
IN0 G
4 3
1
V
2
IN1 G
4 3
1
V
2
205