The text of a manual · part 23 of 39
C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 221 to 230
Pages 221 to 230 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual
The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron DRT1-ID16
Page 221
Section 5-4
Waterproof Terminals (IP67) Wiring
The following diagram shows the wiring of the DRT1-ID08CL Waterproof Terminal (NPN). CAN H 4 5 1 DRAIN
CAN L 3
V−
3 G 2 NC
2 V+
2 3
1
3 G 4 Input 0
2 NC
2 NC
3 G 4 Input 4
2 NC
4 Input 6
1 V
1 V
1 V
1 V
1 V
1 V
1 V
1 V
4
2 NC
Input 1
4
4 Input 3
3 G
2 NC
4 Input 5
3 G
2 NC
4 Input 7
3 G
2 NC 3 G
2-wire sensor (limit switch)
Brown (red)
Blue (black)
Blue (black)
I/O power supply
Black (white)
+
Brown (white)
−
3 G 4 Input 2
NPN output 3-wire sensor (photoelectric or proximity sensor)
The following diagram shows the wiring of the DRT1-ID08CL-1 Waterproof Terminal (PNP). CAN H 4 5 1 DRAIN
CAN L 3
V−
3 G 2 NC
2 V+
4 Input 0
2 NC
1 V
1
4 Input 1 3 G
4
Input 2
2 NC
4 Input 3
3 G 4 Input 4
2 NC
1 V
1 V 2 NC
4
3 G
1 V
1 V
2 3
3 G
4 Input 5
1 V 2 NC
3 G
4 Input 6 1 V
1 V 2 NC
4 Input 7
2 NC 3 G
2-wire sensor (limit switch)
Note
Brown (red)
Black (white)
Blue (black)
I/O power supply
Blue (black)
+ Brown (white)
−
3 G
PNP output 3-wire sensor (photoelectric or proximity sensor)
1. External power supply line 0V and input line G are connected internally, as are external power supply line 24V and input line V. When input power is supplied to external power supply connectors, power can be supplied to sensors from input lines G and V provided that the total current does not exceed 1.0 A. If the total current exceeds 1.0 A, the power must not be supplied from the connector; it must be supplied externally instead. 2. Wire colors in parentheses are the previous JIS colors for photoelectric and proximity sensors.
206
Page 222
Section 5-4
Waterproof Terminals (IP67) Dimensions
The following diagram shows the dimensions for the DRT1-ID08CL and DRT1-ID08CL-1 Waterproof Terminals. All dimensions are in mm. 45 160
10
MS
54
Bus DRT1 NS
IN
I/O PWR
30 Mounting holes
10.5±0.1
10.5±0.1
Three, 4.0 dia. or M5
5-4-4
150±0.2
Waterproof Terminal (IP67) with 4 Transistor Outputs: DRT1-OD04CL (NPN) and DRT1-OD04CL-1 (PNP)
Output Specifications Item
Specification DRT1-OD04CL-1
Model
DRT1-OD04CL
Internal I/O common Output points
NPN PNP 4 points (Uses one word in Master.)
Rated output current Residual voltage
0.5 A/point, 2.0 A/common 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V)
Leakage current ON delay time
0.1 mA max. 0.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 4 points with one common
207
Page 223
Section 5-4
Waterproof Terminals (IP67) Components of the DRT1-OD04CL and DRT1-OD04CL-1 DeviceNet indicators (Refer to page 312.)
Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
Bus DRT1
Rotary Switches 1 and 2: Node address setting (Refer to page 200.)
DeviceNet communications connector
MS NS
OUT
Internal Circuits
I/O PWR
DIP switch Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error (Refer to page 200.)
External power supply connector
Output connector
The following diagram shows the internal circuits for the DRT1-OD04CL Waterproof Terminal (NPN). Voltage step-down
3
G
4
2
V
CAN-H CAN-L 4 V1 5 3 2
V+
Internal circuitry
1
DRAIN
OUT0 4
G
3
1
V
2
OUT1 4
G
3
1
V
2
The following diagram shows the internal circuits for the DRT1-OD04CL-1 Waterproof Terminal (PNP). Voltage step-down G
3 4
2
V
CAN-H CAN-L 4 V1 5 3 2
V+
Internal circuitry
1
OUT0 G
4 3
1
OUT1
DRAIN G
4 3
1 2
208
V
2
V
Page 224
Section 5-4
Waterproof Terminals (IP67) Wiring
The following diagram shows the wiring of the DRT1-OD04CL Waterproof Terminal (NPN). CAN H 4 5 1 DRAIN
CAN L 3
V−
3 G 2 NC
2 V+
2 3
1
−
2 NC
4 Output 2
1 V
1 V
1 V
1 V
4 Output 1
4
3 G 4 Output 0
2 NC
4 Output 3
2 NC
3 G
3 G
Solenoid
Valve
+
I/O power supply
The following diagram shows the wiring of the DRT1-OD04CL-1 Waterproof Terminal (PNP). CAN H 4 5 1 DRAIN
CAN L 3
V−
3 G 2 NC
2 V+
3 G 4 Output 0
2 NC
1 V
1 V
1 V
2 3
1
4 Output 1
4
1 V 2 NC
3 G −
4 Output 2
4 Output 3
2 NC 3 G
+
I/O power supply
Solenoid
Valve
Note External power supply line 0V and output line G are connected internally, as are external power supply line 24V and output line V. When output power is supplied to external power supply connectors, power can be supplied to output devices from output lines G and V provided that the total current does not exceed 2.0 A. If the total current exceeds 2.0 A, the power must not be supplied from the connector; it must be supplied externally instead.
209
Page 225
Section 5-4
Waterproof Terminals (IP67) Dimensions
The following diagram shows the dimensions for the DRT1-OD04CL and DRT1-OD04CL-1 Waterproof Terminals. All dimensions are in mm. 45 114
10
MS
54
Bus DRT1 NS
OUT
I/O PWR
30 Mounting holes
10.5±0.1
10.5±0.1
Three, 4.0 dia. or M5
5-4-5
104±0.2
Waterproof Terminal (IP67) with 8 Transistor Outputs: DRT1-OD08CL (NPN) and DRT1-OD08CL-1 (PNP)
Output Specifications Item
210
Specification DRT1-OD08CL-1
Model
DRT1-OD08CL
Internal I/O common Output points
NPN PNP 8 points (Uses one word in Master.)
Rated output current Residual voltage
0.5 A/point, 2.4 A/common 1.2 V max. (at 0.5 A, 1.2 V max. (at 0.5 A, between each output termi- between each output terminal and G) nal and V)
Leakage current ON delay time
0.1 mA max. 0.5 ms max.
OFF delay time Number of circuits
1.5 ms max. 8 points with one common
Page 226
Section 5-4
Waterproof Terminals (IP67) Components of the DRT1-OD08CL and DRT1-OD08CL-1 DeviceNet indicators (Refer to page 312.)
Output indicators Indicate the output status of each contact. (Lit when the output is ON.)
Bus DRT1
Rotary Switches 1 and 2: Node address setting (Refer to page 200.)
DeviceNet communications connector
MS NS
OUT
External power supply connector
Output connector
The following diagram shows the internal circuits for the DRT1-OD08CL Waterproof Terminal (NPN). Voltage step-down G
3 4
2
V
CAN-H CAN-L 4 V1 5 3 2
V+
Internal circuitry
1
DRAIN
OUT0 4
G
3
1
V
2
OUT1 4
G
3
1
V
2
The following diagram shows the internal circuits for the DRT1-OD08CL-1 Waterproof Terminal (PNP). Voltage step-down G
3 4
2
V
1
CAN-H CAN-L 4 V1 5 3 2
V+
Internal circuitry
Internal Circuits
I/O PWR
DIP switch Pins 1 and 2: Baud rate setting Pin 3: Reserved (Always OFF.) Pin 4: Hold/Clear outputs for communications error (Refer to page 200.)
OUT0 G
4 3
1
V
2
OUT1
DRAIN G
4 3
1
V
2
211
Page 227
Section 5-4
Waterproof Terminals (IP67) Wiring
The following diagram shows the wiring of the DRT1-OD08CL Waterproof Terminal (NPN). CAN H 4 5 1 DRAIN
CAN L 3
3 G 2 NC
V−
2 V+
2 3
1
3 G 4 Output 0
2 NC
2 NC
3 G 4 Output 4
2 NC
4
1 V
1 V
1 V
1 V
1 V
1 V
1 V
1 V
4 Output 1
2 NC
4
4 Output 3
3 G −
3 G 4 Output 2
2 NC
4 Output 5
3 G
2 NC
Output 6
4 Output 7
3 G
2 NC 3 G
+
I/O power supply
Solenoid
Valve
The following diagram shows the wiring of the DRT1-OD08CL-1 Waterproof Terminal (PNP). CAN H 4 5 1 DRAIN
CAN L 3
3 G 2 NC
V−
2 V+
2 3
1
2 NC
3 G 4 Output 2
2 NC
3 G 4 Output 4
2 NC
4 Output 6
1 V
1 V
1 V
1 V
1 V
1 V
1 V
1 V
4 Output 1
2 NC
4 3 G −
3 G 4 Output 0
4 Output 3
2 NC 3 G
4 Output 5
2 NC 3 G
4 Output 7
2 NC 3 G
+
I/O power supply
Solenoid
Valve
Note External power supply line 0V and output line G are connected internally, as are external power supply line 24V and output line V. When output power is supplied to external power supply connectors, power can be supplied to output devices from output lines G and V provided that the total current does not exceed 2.4 A. If the total current exceeds 2.4 A, the power must not be supplied from the connector; it must be supplied externally instead.
212
Page 228
Section 5-4
Waterproof Terminals (IP67) Dimensions
The following diagram shows the dimensions for the DRT1-OD08CL and DRT1-OD08CL-1 Waterproof Terminals. All dimensions are in mm. 45 160
10
MS
54
Bus DRT1 NS
OUT
I/O PWR
30 Mounting holes
10.5±0.1
10.5±0.1
Three, 4.0 dia. or M5
5-4-6
150±0.2
Mounting in Control Panels Use screws to mount a Waterproof Terminal in a control panel. These Terminals cannot be mounted on a DIN Track. Drill the mounting holes in the control panel according to the dimensions shown in the dimensions diagrams and secure the Terminal with M5 screws. The appropriate tightening torque is 1.47 to 1.96 N⋅m.
IN
Bus DRT1
I/O PWR
The Terminal can be mounted in any direction. Any one of the following 6 directions is acceptable. MS
NS
Vertical
Bus DRT1
NS
IN I/O PWR
MS
MS
Installation Direction
NS Bus DRT1
IN
I/O PWR Bus DRT1
I/O PWR MS
5-4-7
NS
IN
Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines
Wiring the Internal Power Supply and I/O Power Supply
The internal power supply shares the communications power supply, so it isn’t necessary to connect a separate internal power supply. To provide the I/O power supply, connect the external power supply to the Terminal with an XS2-series Round Waterproof Connector listed in the following table.
213
Page 229
Section 5-4
Waterproof Terminals (IP67) Compatible Connectors Connector Cable with connectors on both ends (socket and plug)
Model XS2W-D42@-@81-@
Cable with connector on one end (female socket) Connector socket assembly (female) (Crimp-connector or solder type) T-joint
XS2F-D42@-@80-@ XS2C-D4@@
DRT1-ID04CL
CS2R-D427-5
DRT1-OD04CL
I/O power supply
I/O power supply
XS2W-D42@-@81-@ Cables with shielded socket on one end and plug on the other XS2R-D427-5 T-joint XS2F-D42@-@80-@ Cable with shielded socket on one end
Note
XS2R-D427-5 T-joint XS2W-D42@-@81-@ Cable with shielded socket on one end and plug on the other
1. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environmental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors. 2. The same I/O power supply can be used for both input and output devices, but the noise from the output devices may cause the input devices to malfunction. Use separate power supplies if possible.
I/O Wiring
Connect the I/O Wiring to the Environment-resistive Terminal with the XS2series Round Waterproof Connectors listed in the following table. Compatible Connectors Connector Cable with connector on one end (male plug)
Model number XS2H-D421-@80-A
Cable with connectors on both ends (socket and plug) Connector plug assembly (male) (Crimp-connector or solder type)
XS2W-D42@-@81-A XS2G-D4@@
Sensors that are pre-wired with a connector can be connected directly. Refer to the Catalog or manual for details on the device’s connections before connecting any device. XS2W-D42@-@81-A Cable with shielded socket on one end and plug on the other
XS2H-D421-@80-A Cable with shielded plug on one end
Sensor with attached connector XS2G-D4@@
Pre-wired Sensor with connector
Note
Pre-wired Sensor
1. Refer to the OMRON Sensors Catalog (X42-E1-3) for more details on the sensor connections and Round Waterproof Connectors. 2. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environ-
214
Page 230
Section 5-5
B7AC Interface Units mental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors. 3. Always cap unused connectors with an XS2Z-12 Waterproof Cover or XS2Z-15 Dust Cover, shown in the following diagram. XS2Z-12 Waterproof Cover
XS2Z-15 Dust Cover
The connector will meet IP67 standards if a Waterproof Cover is attached. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m.
Press the Dust Cover onto the connector firmly. The Dust Cover will protect the connector from dust, but does not meet IP67 standards.
Maintaining Environmental Resistance
• The IP67 environmental resistance level will be lost if the surfaces where the contact block and cover meet are subjected to excessive force. Protect the contact block and cover from excessive force or shock. • The IP67 standard is not completely waterproof. Do not submerge the system components. • The body of the components is plastic resin. Do not place objects on the components or allow the components to be stepped on. Note There are two kinds of wiring for OMRON 2-wire Proximity Switches (prewired with connector). One kind has IEC pin allocation (M1GJ type) and the other has OMRON pin allocation (M1J type). Refer to the following table to determine the appropriate Waterproof Terminal to use with each kind of switch. Proximity Switch IEC pin allocation (M1GJ type) OMRON pin allocation (M1J type)
5-5
Compatible Terminal DRT1-ID04CL-1 DRT1-ID08CL-1 DRT1-ID04CL DRT1-ID08CL
B7AC Interface Units The B7AC Interface Unit acts as an interface between I/O Connector-type B7AC Link Terminal Units and the DeviceNet Master Unit. Up to 3 B7AC Link Terminal Units (3 Units × 10 inputs/Unit) can be connected to the B7AC Interface Unit. The B7AC Interface Unit uses shielded connectors to connect to both the DeviceNet Master Unit and B7AC Link Terminal Units, so the cable connections can be made easily without tools and the connections meet the high IP66 environmental resistance standards.
5-5-1
Node Address and Baud Rate Settings (DIP Switch 1) This section explains the B7AC Interface Unit’s node address and baud rate settings. These settings are made using the following pins on DIP switch 1.
215