The text of a manual · part 24 of 39
C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 231 to 240
Pages 231 to 240 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual
The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron DRT1-ID16
Page 231
Section 5-5
B7AC Interface Units Node address setting: Baud rate setting: SW1
DIP switch 1, pins 1 through 6 DIP switch 1, pins 7 and 8
SW2
ON
1 2 3 4 5 6 7 8
Node address setting
DIP switch 1 Pins 1 to 6: Node address setting ON Pins 7 to 8: Baud rate setting DIP switch 2 Pins 1 to 3: B7AC transmission delay 1 2 3 4 5 6 7 8 Pins 4 to 5: Reserved (Always OFF) Pins 6 to 8: B7AC communications error signal setting B7AC B7AC communications transmission error signal setting delay setting
Baud rate setting
Reserved (Always OFF.)
The settings on DIP switch 2 are communications settings for the individual B7AC Interface Unit. Refer to Settings on DIP Switch 2 on page 219 for details on these settings. Node Address Settings
The B7AC Interface Unit’s node address is set with pins 1 through 6 of DIP switch 1. Any node address within the setting range can be used as long as it isn’t already set on another node. DIP switch setting
Node address
Pin 6 Pin 5 Pin 4 Pin 3 Pin 2 Pin 1 0 0 0 0 0 0 0 (default) 0 0
0 0
0 0
0 0
0 1
1 0
1 2
: :
: :
1 1
1 1
1 1
1 1
0 1
1 0
61 62
1
1
1
1
1
1
63
0: OFF, 1: ON Note
1. Refer to Appendix A Node Address Settings Table for a complete table of DIP switch settings. 2. The Slave won’t be able to participate in communications if the same node address is used for the Master or another Slave node (node address duplication error).
Baud Rate Setting
Pins 7 and 8 of DIP switch 1 are used to set the baud rate as shown in the following table. (These pins are factory-set to OFF.) Pin Settings Pin 7
Note
Baud rate
Pin 8
OFF
OFF
125 kbps
ON OFF
OFF ON
250 kbps 500 kbps (default)
ON
ON
Not allowed.
1. Always turn OFF the Slave’s power supply (including the communications power supply) before changing the baud rate setting. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any Slaves with baud rates different from the Master’s rate won’t be able to participate in communications. Furthermore, a node with an incorrect baud rate setting may cause communications errors between nodes with correct baud rate settings.
216
Page 232
Section 5-5
B7AC Interface Units
5-5-2
Example System Configuration DeviceNet Master Unit
DCN2-1 Shielded T-branch connector
T-branch Tap
DRT1-B7AC B7AC Interface Unit Internal power supply
DeviceNet communications cable DCA1-5CN@@W1 Cable with shielded connectors on both ends
B7AC-series I/O Connector-type Link Terminal Units (10 points/Unit)
Sensors with attached connectors 10 sensors
10 inputs 10 sensors
Communications media XS2W-D42@-@81-@ Cables with shielded connector plugs
10 inputs 10 sensors 10 inputs
Compatible B7AC Link Terminal Units
The following B7AC Link Terminal Units (Sensor I/O Connector type) can be connected to the B7AC Interface Unit. Model
5-5-3
Number of inputs
Input format
Transmission delay with the B7AC Interface Unit
B7AC-T10A1 B7AC-T10A1-A
10 inputs 10 inputs
NPN NPN
19.2 ms 19.2 ms or 3 ms (switchable)
B7AC-T10A1-B
10 inputs
PNP
19.2 ms or 3 ms (switchable)
B7AC Interface Unit: DRT1-B7AC
Specifications General Specifications Item Model
Specification DRT1-B7AC
Number of I/O points 30 B7AC inputs max. (up to 3 B7AC Link Terminal Units can be connected with 10 inputs/Unit) Uses two input words in Master. Internal current consumption
24-V DC communications power supply: 70 mA max. 24-V DC internal power supply: 500 mA max. (This is the current when 3 B7AC Link Terminal Units are connected and all inputs are OFF. It does not include the current consumed by connected external devices.)
Dielectric strength
500 V AC for 1 min. (between insulated circuits, detected leakage current 1 mA) Internal power supply normal: ±600 V, 10 min., with pulse widths of 100 ns to 1 µs Internal power supply common: ±1.5 kV, 10 min., with pulse widths of 100 ns to 1 µs
Noise immunity
Vibration resistance
Malfunction: 10 to 150 kHz, single amplitude 0.5 mm, or 70 m/s2 Destruction: 10 to 150 kHz, single amplitude 0.75 mm, or 100 m/s2
Shock resistance
Malfunction: 200 m/s2 Destruction: 300 m/s2 −10 to 55°C
Ambient operating temperature
217
Page 233
Section 5-5
B7AC Interface Units Item Ambient operating humidity
Specification 25% to 85% (with no condensation)
Degree of protection IP66 Mounting method M5 screws Mounting strength Communications connector strength Weight
100 N for 10 s 100 N pull for 10 s Approx. 500 g max.
Communications Specifications (with B7AC-series Units) Item
Specification
Number of ports
3 ports for communications with B7AC Link Terminal Units (Round shielded connectors)
Number of I/O points 30 inputs (10 inputs/port × 3 ports) Communications Split multiplex transmission in one direction method Transmission delay Standard: 19.2 ms typical (31 ms max.) High-speed: 3 ms typical (5 ms max.) Communications path
0.5 mm VCTF cable, 1 A current max. on +/− lines
Communications dis- With standard transmission delay: 50 m max. tance With high-speed transmission delay: 30 m max.
Components of the DRT1-B7AC DIP switch 1: Pins 1 to 6: Node address setting Pins 7 and 8: Baud rate setting (Refer to page 215.)
B7A
ERR OFF
1 2 3 4 5 6 7 8
ON
1 2 3 8 1632 0 1 A B C NCNC A B C
1 2 3 4 5 6 7 8
ON
B7A ONNODE ADDRESSDR SPEED
ERR A ERR B ERR C MS
A NC
DIP switch 2: Not used. Pins 1 to 3: B7AC transmission delay setting Pins 4 and 5: Reserved (Always OFF.) Pins 6 to 8: B7AC communications error signal setting (Refer to page 219.)
218
DeviceNet indicators (Refer to page 312.)
B7AC-series indicators Indicate the status of each port.
NS
C B
B7AC-series Unit connectors
P DeviceNet communications connector External power supply connector
Page 234
Section 5-5
B7AC Interface Units LED Indicators Usage DeviceNet indicators
Name MS
Status Lit Flashing Lit Flashing Not lit
NS
Color Green
Normal status
Red
Settings not made. Fatal error
---
Non-fatal error Power is not being supplied.
Lit Flashing
Green
Normal status Communications not established (negotiating with Master)
Lit
Red
Fatal communications error (such as a node address duplication error) Non-fatal communications error
Not lit Lit
--Green
Power is not being supplied. Normal status
Lit Lit
Red Orange
Not lit
---
Communications error A communications error occurred but the error was resolved later. (See note 1.) Power is not being supplied. A B7AC Link Terminal Unit was not connected when the power was turned ON. (See note 2.)
Flashing B7AC-series indicators
ERR A ERR B ERR C (for ports A, B, and C)
Meaning
Note
1. The indicator can be restored to green by resetting the power (turning the power OFF and then ON again.) 2. The indicator will become green or orange if a B7AC-series Unit is connected after the power was turned ON. Depending on the B7AC communications timing at startup, a momentary communications error may occur and cause the indicator to become orange after the error is resolved. It the indicator is orange, it can be restored to green by resetting the power (turning the power OFF and then ON again.)
Settings on DIP Switch 2
The settings on DIP switch 2 are B7AC communications settings for the individual B7AC Interface Unit. For details on the DIP switch 1 settings, refer to 5-5-1 Node Address and Baud Rate Settings (DIP Switch 1). SW1
SW2
ON
1 2 3 4 5 6 7 8
Node address setting
DIP switch 1 Pins 1 to 6: Node address setting ON Pins 7 to 8: Baud rate setting DIP switch 2 Pins 1 to 3: B7AC transmission delay 1 2 3 4 5 6 7 8 Pins 4 to 5: Reserved (Always OFF) Pins 6 to 8: B7AC communications error signal setting B7AC B7AC communications transmission error signal setting delay setting
Baud rate setting
Reserved (Always OFF.)
219
Page 235
Section 5-5
B7AC Interface Units B7AC Transmission Delay Setting (Pins 1 to 3)
Pins 1 to 3 set the transmission delay time for communications with the B7AC Link Terminal Unit at each port, as shown in the following table. These pins are set to ON (high-speed) at the factory. Pin 1 Port A OFF ON
Pin 2 Port B
Pin 3 Port C
OFF ON
Transmission delay time
OFF ON
19.2 ms typical 3 ms typical (factory setting)
B7AC Communications Error Signal Setting Pins 6 to 8 specify whether an error signal (notification) will be sent to the Master Unit when an error occurs in B7AC communications through the corresponding port. These pins are set to ON (send error signal) at the factory Pin 6 Port A OFF ON
Pin 7 Port B
Pin 8 Port C
OFF ON
B7AC communications error signal setting
OFF ON
Do not send error signal. Send error signal. (factory setting)
If an error occurs in a port and the corresponding pin is ON (send error signal), the B7AC Communications Error Flag will be turned ON in the words allocated in the Master Unit. See I/O Allocation below for details on the location of the B7AC Communications Error Flag. Note
1. Always turn OFF the Unit’s power supply (including the communications power supply) before changing any DIP switch settings. 2. Set the appropriate transmission delay time for the B7AC Link Terminal Unit connected to each port. 3. Always turn OFF the B7AC communications error signal setting for a port if there isn’t a B7AC Link Terminal Unit connected to the port.
I/O Allocation
The B7AC Interface Unit is allocated two input words in the Master Unit. The following table shows the usage of these two words when word “m+0” is the first word allocated and “m+1” is the second word allocated. Port on B7AC Interface Unit
Input connector 0 to 9 Input connector 0 to 5
Word m+0, bits 00 to 09 Word m+0, bits 10 to 15
Port C
Input connector 6 to 9 Input connector 0 to 9
Word m+1, bits 00 to 03 Word m+1, bits 04 to 13
9
8
5
4 ERR
3
2
1
7
6
5
4
0
9
8
7
6
5
4
8
7
2
1
0
6
5
4
3
3
2
1
0
Inputs for B7AC Unit connected to port B
Inputs for B7AC Unit connected to port C
9
3
Inputs for B7AC Unit connected to port A
Inputs for B7AC Unit connected to port B
Note 1
Wd m+1
15 14 13 12 11 10
Note 2
Wd m+0
220
I/O bits allocated to Master Unit
Port A Port B
Bit:
Note
Connector on B7AC Link Terminal Unit
2
1
0
9
8
7
6
1. Bit 14 of word m+1 is the B7AC Communications Error Flag for the B7AC Interface Unit. This flag will be turned ON if there is a communications error in any one of the ports set to “send error signal” in pins 6 to 8 of DIP switch 2. The flag will be reset to 0 automatically when the communications error is resolved.
Page 236
Section 5-5
B7AC Interface Units 2. This bit is always 0 (OFF). I/O Allocation Example
When the Master Unit is mounted in a C200HX/HG/HE PLC and fixed allocation is used for DeviceNet, IR area words IR 350 through IR 399 are allocated to inputs from Slaves with node addresses 0 through 49. If the B7AC Interface Unit’s node address is set to 01, the first allocated word (m+0) will be IR 351. Ports A, B, and C will be allocated the following bits: Port on B7AC Interface Unit Port A
Connector on B7AC Link Terminal Unit Input connector 0 to 9
I/O bits allocated to Master Unit IR 35100 to IR 35109
Port B
Input connector 0 to 5 Input connector 6 to 9
IR 35110 to IR 35115 IR 35200 to IR 35203
Port C
Input connector 0 to 9
IR 35204 to IR 35213
IR 35214 is the B7AC Communications Error Flag for the B7AC Interface Unit. Note If a communications error occurs in communications with a B7AC Link Terminal Unit, normal communications will be restored automatically when the communications error is resolved. The time required to restore communications depends on the error continuation time (time from error occurrence to error resolution), as shown below. • Error continuation time less than 500 ms: The B7AC Communications Error Flag will be turned OFF 500 ms after the error occurred. • Error continuation time greater than 500 ms: The B7AC Communications Error Flag will be turned OFF after the error is resolved. 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0 m+0: Wd 351 m+1: Wd 352
0 ERR
B7AC Communications Error Flag
B7AC Unit connected to port A B7AC Unit connected to port B B7AC Unit connected to port C
221
Page 237
Section 5-5
B7AC Interface Units Internal Circuits DC-DC converter (Isolated)
24 V (for internal circuits) 1 2 3
Photocoupler
Communications connector
V−
2 V+
DC-DC converter (Not isolated)
Photocoupler Photocoupler
CN1
3
B7AC
SIG-IN
Input A power supply +24 V B7AC trans. delay switch Input A power supply 0 V
1 4
2
B7AC
SIG-IN
Input B power supply +24 V B7AC trans. delay switch Input B power supply 0 V
A
Port A connector
1
B 4
2
Port B connector
3 B7AC
SIG-IN
Input C power supply +24 V B7AC trans. delay switch Input C power supply 0 V
1 4
2
3
222
External power supply connector
3
Photocoupler
1 DRAIN
5
0 V (for internal circuits)
Internal circuitry
CAN H 4
Physical layer Photocoupler CAN L
P
4
C
Port C connector
Page 238
Section 5-5
B7AC Interface Units Dimensions
The following diagram shows the dimensions for the DRT1-B7AC Interface Unit. All dimensions are in mm. 57 115
8
ERR AERR BERR C MS
51
A NC
NS
C B
P
Four, M5
135
6
45
Mounting Holes Four, 4.2 dia. or M4
Mounting screw
Nut
28+ --0.5
When mounting from the front with M4 screws and nuts
125+ --0.5
Four, 5.4 dia.
Mounting screw
28+ --0.5
When mounting directly from the rear with M5 screws
125+ --0.5
5-5-4
Mounting in Control Panels Use screws to mount a B7AC Interface Unit in a control panel. These Units cannot be mounted on a DIN Track. Attaching the Unit from the Front The Units are tapped with M5 threads, so use M4 screws to clear the threads and attach the Unit to the control panel from the front. Drill the mounting holes in the control panel according to the dimensions shown in the dimensions diagrams and secure the Unit with M4 screws. The appropriate tightening torque is 0.6 to 1.18 N⋅m. Attaching the Unit from the Rear Drill the mounting holes in the control panel according to the dimensions shown in the dimensions diagram and secure the Unit with M5 screws. The appropriate tightening torque is 1.47 to 1.96 N⋅m.
223
Page 239
Section 5-5
B7AC Interface Units
The Unit can be mounted in any direction. Any one of the following 6 directions is acceptable. P C P
P
Vertical
NC
C
A
B
B P
NC
A
C
5-5-5
B
C B
A
A NC
NC
Installation Direction
Wiring the Internal Power Supply and Input Lines
Wiring the Internal Power Supply
Connect the external power supply to the B7AC Interface Unit with an XS2series Round Waterproof Connector listed in the following table. Compatible Connectors Connector Cable with connectors on both ends (socket and plug)
Model XS2W-D42@-@81-@
Cable with connector on one end (female socket) Connector socket assembly (female) (Crimp-connector or solder type) T-joint
XS2F-D42@-@80-@ XS2C-D4@@
DRT1-B7AC
CS2R-D427-5 DRT1-B7AC
I/O power supply
I/O power supply
XS2W-D42@-@81-@ Cables with shielded socket on one end and plug on the other XS2R-D427-5 T-joint XS2F-D42@-@80-@ Cable with shielded socket on one end
XS2R-D427-5 T-joint XS2W-D42@-@81-@ Cable with shielded socket on one end and plug on the other
Note Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environmental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors. Connecting to B7AC Link Terminal Units (Communications Media)
224
Connect the I/O Wiring to the B7AC Interface Unit with the XS2-series Round Waterproof Connectors listed in the following table. Compatible Connectors Connector Cable with connector on one end (male plug)
Model XS2H-D42@-@80-@
Cable with connectors on both ends (socket and plug) Connector plug assembly (male) (Crimp-connector or solder type)
XS2W-D42@-@81-@ XS2G-D4@@
Page 240
Section 5-5
B7AC Interface Units
Refer to the Catalog or manual for details on the device’s connections before connecting any device. DRT1-B7AC B7AC Interface Unit
B7AC-series I/O Connector-type Link Terminal Units (10 points/Unit)
Sensors with attached connectors (See note 3.) 10 sensors
10 inputs Communications media XS2W-D42@-@81-@ Cables with shielded connector plugs
10 sensors 10 inputs 10 sensors 10 inputs
Note
1. Refer to the OMRON Sensors Catalog (X42-E1-3) for more details on the sensor connections and Round Waterproof Connectors. 2. A separate power supply cannot be connected to a B7AC Link Terminal Unit to supplement the power from the B7AC Interface Unit’s internal power supply. 3. Limit Switches, Proximity Switches, Photoelectric Switches, etc. (Sensors with attached connectors, Pre-wired Sensors with connectors, and regular Pre-wired Sensors can be used. 4. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m. If the connector is not tightened sufficiently, it will not provide the expected environmental resistance and may come loose from vibration. Do not use pliers or other tools to tighten the connectors, because the tools may damage the connectors. 5. Always cap unused connectors with an XS2Z-12 Waterproof Cover or XS2Z-15 Dust Cover, shown in the following diagram. XS2Z-12 Waterproof Cover
XS2Z-15 Dust Cover
The connector will meet IP66 standards if a Waterproof Cover is attached. Tighten the connector by hand to a torque of 0.39 to 0.49 N⋅m.
Press the Dust Cover onto the connector firmly. The Dust Cover will protect the connector from dust, but does not meet IP66 standards.
Maintaining Environmental Resistance
• The IP66 environmental resistance level will be lost if the surfaces where the contact block and cover meet are subjected to excessive force. Protect the contact block and cover from excessive force or shock. • The IP66 standard is lower than waterproof standards. Do not submerge the system components. • The body of the components is plastic resin. Do not place objects on the components or allow the components to be stepped on.
225