Page 21

Section 1-1

Overview of DeviceNet Slave Features I/O Terminals

• Provide general-purpose inputs, outputs, or both inputs and outputs via 2tier terminal blocks (M3). Available in 8-point and 16-point models with transistor inputs or outputs or in a 16-point model with 8 inputs and 8 outputs. • Provide general-purpose inputs, outputs, or both inputs and outputs via 3tier terminal blocks (M3). Available in 16-point models with transistor inputs or outputs or in a 16-point model with 8 inputs and 8 outputs. • Provide general-purpose inputs, outputs, or both inputs and outputs via a MIL connector. Available in 32-point models with transistor inputs or outputs or in a 32-point model with 8 inputs and 8 outputs. ■ Environment-resistive Slaves

Environment-resistant Terminals • Improved I/O Terminals that conform to IP66 for spatter-, water-, and oilresistance. Sensors or valves with round water-proof connectors can be easily connected with no tools. • Available in 8-point or 16-point models with transistor inputs or outputs, and 16-point models with transistor I/O (8 inputs and outputs).

• DRT1-@@@@C(-1): IP66 Water-proof Terminals

• Improved I/O Terminals that conform to IP67 for water- and oil-resistance. Sensors or valves with round water-proof connectors can be easily connected with no tools. • Available in 4-point or 8-point models with transistor inputs or outputs. • DRT1-@@@@CL(-1): IP67 B7AC Interface Unit

• Input Interface Unit that conforms to IP66 for spatter-, water-, and oilresistance. • Provides three FA connector ports for the B7A for 10 input points on each of 3 ports. Remote Adapters • Used in combination with G70D and other I/O Blocks to handle relay outputs, power MOS FET Relay outputs, etc. • Available in 16-point models with transistor inputs or outputs. CQM1 I/O Link Units

• More than one I/O Link Unit can be mounted to a CQM1 PLC. • Link 16 inputs and 16 outputs between the PLC and the Master Unit. Sensor Terminals • Accept inputs from photoelectric and proximity sensors with connectors. • Available in 16-point input and 8-point input/8-point output models. • Output signals can be used for sensor teaching and external diagnosis. Analog Input Terminals • Convert analog inputs to binary. • Switchable between 2 and 4 input points using the DIP switch. • Handle inputs of 0 to 5 V, 1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to 20 mA, or 4 to 20 mA.

6

Page 22

Section 1-1

Overview of DeviceNet

Analog Output Terminals • Convert binary data to analog outputs. • Provides outputs of 1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to 20 mA, or 4 to 20mA. • Available in models with a resolution of either 1/6,000 or 1/30,000. Temperature Input Terminals • Temperature data is input as binary data for 4 inputs. • Thermocouple and temperature-resistance thermometer inputs are available. ■ Special I/O Slaves

C200H I/O Link Units • Special I/O Slaves that mount to C200HX/HG/HE PLCs and read/write data from the Master Unit to the specified words in the CPU Unit. • Read and write areas specified for up to 512 bits each (32 words each). • Any memory area words can be read or written using DeviceNet explicit messages. RS-232C Units • Special I/O Slaves that provide two RS-232C ports and control I/O from the Master Units. MULTIPLE I/O TERMINALs • Multiple I/O Units can be combined under a Communications Unit and treated as a single Slave. • Special I/O Units, such as Analog I/O Units, and High-speed Counter Units are also available.

7

Page 23

Section 1-1

Overview of DeviceNet

1-1-2

Slaves DeviceNet Slaves are classified as follows:

• General-purpose Slaves Slaves with I/O functions that use a normal connector to connect the communications cable. • Environment-resistive Slaves Slaves with I/O functions that use a round, water-proof connector to connect the communications cable. • Special I/O Slaves Slaves with functions other than I/O functions (such as message communications) that use a normal connector to connect the communications cable. Type Cable

Normal square connector

General purpose

Name Transistor Remote I/O Terminals

Transistor Remote I/O Terminals with 3tier I/O Terminal Blocks

Appearance

I/O points 8 input points, NPN

Model DRT1-ID08

8 input points, PNP 16 input points, NPN

DRT1-ID08-1 DRT1-ID16

16 input points, PNP 8 output points, NPN

DRT1-ID16-1 DRT1-OD08

8 output points, PNP 16 output points, NPN

DRT1-OD08-1 DRT1-OD16

16 output points, PNP

DRT1-OD16-1

8 input/8 output points, DRT1-MD16 NPN 16 input points, NPN DRT1-ID16T 16 input points, PNP 16 input points, NPN

DRT1-ID16T-1 DRT1-ID16TA

16 input points, PNP 16 output points, NPN

DRT1-ID16TA-1 DRT1-OD16T

16 output points, PNP 16 output points, NPN

DRT1-OD16T-1 DRT1-OD16TA

16 output points, PNP 8 input/8 output points, NPN 8 input/8 output points, PNP 8 input/8 output points, NPN

DRT1-OD16TA-1 DRT1-MD16T DRT1-MD16T-1 DRT1-MD16TA

8 input/8 output points, DRT1-MD16TA-1 PNP

8

Features ---

Easy wiring (no need to double-wire terminals and wiring locations are easy to understand) Separate power supply not needed for the DRT1@D16TA (same power supply used as communications power supply).

Page 24

Section 1-1

Overview of DeviceNet Type Cable

Normal square connectors

General purpose

Name Transistor Remote I/O Terminals with I/O Connectors

I/O points 32 input points, NPN

Model DRT1-ID32ML

32 input points, PNP 32 output points, NPN

DRT1-ID32ML-1 DRT1-OD32ML

32 output points, PNP 16 input/16 output points, NPN

DRT1-OD32ML-1 DRT1-MD32ML

16 input/16 output points, PNP

DRT1-MD32ML-1

16 input points, NPN 16 input points, PNP

DRT1-ID16X DRT1-ID16X-1

16 output points, NPN 16 output points, PNP

DRT1-OD16X DRT1-OD16X-1

Sensor Terminals

16 input points, NPN

DRT1-HD16S

Temperature Input Terminals

4 thermocouple input points

DRT1-TS04T

4 temperature-resistant input points

DRT1-TS04P

4 analog input points (4 words) or 2 input points (2 words) (voltage or current)

DRT1-AD04

Applicable range: 1 to 5 V, 0 to 5 V, 0 to 10 V, –10 to +10 V, 0 to 20 mA, or 4 to 20 mA input (switchable) Resolution: 1/6,000

4 analog input points (4 words) (voltage or current

DRT1-AD04H

Applicable range: 1 to 5 V, 0 to 5 V, 0 to 10 V, 0 to 20 mA, or 4 to 20 mA input (switchable) Resolution: 1/30,000

Remote Adapters

Analog Input Terminals

Appearance

8 input/8 output points, DRT1-ND16S NPN

Features Compact: 35 x 60 x 80 mm (WxDxH) Connection to I/O Blocks possible through MIL cables. Separate power supply not needed (same power supply used as communications power supply). Compact: 85 x 50 x 40 mm (WxDxH) Connects to G70D I/O Block for output via relays or power MOS FET relays.

Connected to photoelectric and proximity sensors with connectors

Thermocouple Temperature-resistant input

Analog Output Terminals

2 analog output points DRT1-DA02 (2 words)

Applicable range: 1 to 5 V, 0 to 10 V, –10 to +10 V, 0 to 20 mA, or 4 to 20 mA output (switchable) Resolution: 1/6,000

CQM1 I/O Link Units

16 internal input/ 16 internal output points (between CQM1 and Master Unit)

Pier-to-pier remote I/O PLC communications

CQM1-DRT21

9

Page 25

Section 1-1

Overview of DeviceNet Type Cable

Round communications connectors

Environment-resistive Terminals

Name Waterproof Terminals

Environmentresistive Transistor Terminals

Appearance

I/O points 4 input points, NPN

Model DRT1-ID04CL

4 input points, PNP 8 input points, NPN

DRT1-ID04CL-1 DRT1-ID08CL

8 input points, PNP 4 output points, NPN

DRT1-ID08CL-1 DRT1-OD04CL

4 output points, PNP 8 output points, NPN

DRT1-OD04CL-1 DRT1-OD08CL

8 output points, PNP 8 input points, NPN

DRT1-OD08CL-1 DRT1-ID08C

8 output points, NPN 16 input points, NPN

DRT1-OD08C DRT1-HD16C

16 input points, PNP 16 output points, NPN

DRT1-HD16C-1 DRT1-WD16C

16 output points, PNP DRT1-WD16C-1 8 input/8 output points, DRT1-MD16C NPN

Features Better resistance to environment with waterproof, drop-proof construction (IP67). Connects without tools to sensors, valves, and other devices with XS2series connectors.

Better resistance to environment with spatterproof, waterproof, dropproof construction (IP66). Connects without tools to sensors, valves, and other devices with XS2series connectors.

8 input/8 output points, DRT1-MD16C-1 PNP

Normal square connectors

Special I/O Slaves

10

B7AC Interface Unit

10 inputs x 3 ports

DRT1-B7AC

C200H I/O Link Units

512 input points max. C200HW-DRT21 (32 words) 512 output points max. (32 words)

RS-232C Units

16 input points (1 word) (status area)

DRT1-232C2

Each Unit connects to three branches. Connects without tools to sensors, valves, and other devices with XS2series connectors. Better resistance to environment with spatterproof, waterproof, dropproof construction (IP66). Pier-to-pier remote I/O PLC communications Max. I/O area: 512 inputs and 512 outputs. User allocations of I/O area. Two RS-232C ports Explicit messages used for data transfers (151 bytes max.) Explicit messages used for settings and control. RS-232C port status reflected in inputs.

Page 26

Section 1-1

Overview of DeviceNet

1-1-3

Slave Mounting and Connection Methods

Type Cable

Normal square connectors

General purpose

Name

Model

Transistor Remote I/O Terminals

DRT1-ID08 DRT1-ID08-1 DRT1-ID16

Mounting

I/O connections

Combined devices

DIN Track or screws

M3 terminal block, 2 tiers

Connected to terminal block

Internal I/O power power supply supply M3 termi- M3 terminal block nal block

DIN Track or screws

M3 terminal block, 3 tiers

Connected to terminal block

M3 termi- M3 terminal block nal block

DRT1-ID16-1 DRT1-OD08 DRT1-OD08-1 DRT1-OD16 DRT1-OD16-1 DRT1-MD16 Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks

DRT1-ID16T DRT1-ID16T-1 DRT1-OD16T DRT1-OD16T-1 DRT1-MD16T DRT1-MD16T-1 DRT1-ID16TA DRT1-ID16TA-1

Same as communications power supply

DRT1-OD16TA DRT1-OD16TA-1 DRT1-MD16TA DRT1-MD16TA-1 Transistor Remote I/O Terminals with I/O Connectors

DIN Track or directly to wall with mounting bracket

MIL connector

Cable with MIL Same as connector and communications I/O Block power supply

DIN Track or screws

Flat cable connector, MIL socket

G70D I/O Block

Sensor Termi- DRT1-HD16S nals DRT1-ND16S

DIN Track or screws

I/O connector Sensor or external devices with connector

Temperature Input Terminals

DIN Track or screws

M3 terminal block

DIN Track or screws

M3 terminal block

Remote Adapters

DRT1-ID32ML DRT1-ID32ML-1 DRT1-OD32ML DRT1-OD32ML-1 DRT1-MD32ML DRT1-MD32ML-1 DRT1-ID16X DRT1-ID16X-1 DRT1-OD16X DRT1-OD16X-1

Analog Input Terminals

DRT1-TS04T DRT1-TS04P

DRT1-AD04 DRT1-AD04H

Thermometer Temperature resistance input device 0 to 5 V, 1 to 5 V, 0 to 10 V, −10 to 10 V, 0 to 20 mA, 4 to 20 mA

MIL connector (for both inputs and outputs)

M3 termi- Flat cable nal block connector with MIL socket (for both inputs and outputs) M3 termi- I/O connal block nectors (for both inputs and outputs) M3 termi- None nal block

M3 termi- None nal block

11

Page 27

Section 1-1

Overview of DeviceNet Type Cable

Name

Model

Mounting

I/O connections

Combined devices

Internal power supply

I/O power supply

Environment-resistive Terminals

Normal square connectors Round communications connectors

General purpose

Analog Output Terminals

DRT1-DA02

DIN Track or screws

M3 terminal block

1 to 5 V, 0 to 10 V, −10 to 10 V, 0 to 20 mA, 4 to 20 mA

M3 termi- None nal block

CQM1 I/O Link Units

CQM1-DRT21

Directly to PLC

None

PLC-to-PLC link

Supplied from PLC

Waterproof Terminals

DRT1-ID04CL

Screws

Round, water- Cable with XS2 Same as Cable with proof connec- connector on communi- XS2 contor (XS2 one end and cations nector compatible) cables with power XS2 connector supply on both ends with sensor with direct connector or relay sensor connector and sensor Cable with XS2 conwith pull-out nector connector

Screws

Round, water- B7AC x 3 Units Cable None proof connecwith XS2 (communitor connector cations connections to B7AC via round waterproof connector)

DRT1-ID04CL-1 DRT1-ID08CL DRT1-ID08CL-1 DRT1-OD04CL DRT1-OD04CL-1 DRT1-OD08CL

Environmentresistive Transistor Terminals

DRT1-OD08CL-1 DRT1-ID08C DRT1-OD08C DRT1-HD16C

None

DRT1-HD16C-1 DRT1-WD16C DRT1-WD16C-1 DRT1-MD16C B7AC Interface Unit

Normal square connector

Special I/O Terminals

12

DRT1-MD16C-1 DRT1-B7AC

C200H I/O Link Units

C200HW-DRT21

To Backplane

None

PLC-to-PLC link

Supplied from PLC

None

RS-232C Units

DRT1-232C2

DIN Track or screws

Two RS-232 ports

Devices with M3 termi- None RS-232C inter- nal block face (e.g., barcode reader) for two ports

Page 28

SECTION 2 Example System Setup This section provides information on hardware aspects of Masters and Slaves connected to a DeviceNet Network to ensure the proper operation of the system. Included are system configuration examples, basic procedures for wiring, mounting and setting Master and Slave Units, connecting cables and power supplies, creating I/O tables, and creating and registering scan lists. 2-1

Basic Procedures and Configuration Examples . . . . . . . . . . . . . . . . . . . . . . .

14

2-1-1

Basic Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14

2-1-2

System Configuration Example . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

2-2

Preparations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

2-3

Setting and Wiring Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

2-4

2-5

2-3-1

Mounting and Setting the Master Unit . . . . . . . . . . . . . . . . . . . . . . .

16

2-3-2

Mounting and Setting Slaves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

17

2-3-3

Mounting Connecting Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18

2-3-4

Connecting Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19

Starting Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

20

2-4-1

Creating I/O Tables for the Master Unit . . . . . . . . . . . . . . . . . . . . . .

20

2-4-2

Starting the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

20

2-4-3

Creating and Registering Scan Lists. . . . . . . . . . . . . . . . . . . . . . . . .

21

Checking Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

2-5-1

Indicator Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

2-5-2

Reading and Writing Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

13

Page 29

Basic Procedures and Configuration Examples

2-1

Section 2-1

Basic Procedures and Configuration Examples The examples shown here provide the basic operating procedures for DeviceNet.

2-1-1

Basic Procedures Use the following procedures to operate the DeviceNet Slave Units. For details on settings and connections, refer to the operation manual for the Master Unit. For further details on Slave Units, refer to SECTION 4 Generalpurpose Slaves to SECTION 6 Special I/O Slave Units Specifications.

Preparing the Units 1,2,3...

1. Select the appropriate Units. Refer to page 15. 2. Determine the appropriate wiring method. Refer to page 15. 3. Determine the appropriate method for supplying communications power. Refer to page 15.

Setting and Wiring Hardware 1,2,3...

1. Separate and lay the cables. 2. Mount the Master Unit and specify the correct settings. Refer to page 16. 3. Mount the Slave Units and specify the correct settings. Refer to page 17. 4. Mount other devices to be connected to the Network. Refer to page 15. 5. Connect the cables. Refer to page 15. 6. Wire the I/O cables. Refer to page 15.

Starting Communications 1,2,3...

1. Create the I/O tables. Refer to page 20. 2. Start up the system. Refer to page 20. 3. Create and register the scan list. Refer to page 21.

Checking Operations 1,2,3...

1. Check the status of the indicators on the Unit. Refer to page 24. 2. Check that data is reading and writing properly. Refer to page 24.

Note The examples provided in this section show the minimum settings to operate the system. If details on other settings for actual operation are required, refer the operation manual for the Master Unit. For further details on Slave Units, refer to SECTION 4 General-purpose Slaves to SECTION 6 Special I/O Slave Units Specifications.

14

Page 30

Section 2-2

Preparations

2-1-2

System Configuration Example The following diagram shows the operating procedure using a system configuration example. The system configuration shown here uses Thin Cables. C200H-OD215 Output Unit

C200HW-DRM21-V1 Master Unit S82K-05024 24-V DC Power Supply (Node 00) (100 V AC, 50 W)

C200HX PLC

C200HW-DRT21 I/O Link Unit (Node 07) C200HX PLC

H7F 7-segment Display Device

DRT1-ID16 Remote I/O Terminal 16 transistor inputs (Node 01) DRT1-OD16 Remote I/O Terminal 16 transistor outputs (Node 02)

DCN1-1C T-branch Tap DCN1-3 T-branch Tap with Terminating Resistor

DCN1-1C T-branch Tap with Terminating Resistor DRT1-232C2 RS-232C Unit allocated 1 input word (Node 08)

DRT1-TS04T Temperature Input Terminal with 4 inputs (allocated 4 words) (Node 03)

Power is supplied to each node in the above diagram using the following devices. Internal power: S82K-05024 (100 V AC, 50 W) I/O power:

2-2

S82K-05024 (100 V AC, 50 W)

Preparations

Selecting Units

Select the following Units as shown in 2-1-2 System Configuration Example. Master Unit:

C200HW-DRM21-V1

Slave Units:

DRT1-ID16 DRT1-OD16 DRT1-TS04T C200HW-DRT21 DRT1-232C2

There is a complete line of OMRON Master Units and Slave Units available that are compatible with DeviceNet. Select Units that suit the needs of the system. For further details on types of Units, refer to 1-1-2 Slaves. Wiring

Either Thick Cables or Thin Cables can be used to wire a DeviceNet Network. Flexible branching of cables is possible by using either T-branch Taps or multi-drop connections. Restrictions on the maximum network length and total branch line length depends on the baud rate and type of cable used. For details, refer to the DeviceNet Operation Manual (W267). In 2-1-2 System Configuration Example, Thin Cables are used with T-branch Taps for connecting Slave Units to the trunk line.

Communications Power Supply

Each node (Master or Slave) must be supplied with a 24-V DC power supply for proper DeviceNet communications. The communications power, however, can be supplied by communications cables and does not require separate wiring. For systems that have a short maximum network length, power can be supplied to all nodes by using one communications power supply. Various conditions, constraints, and measures affect how the communications power is

15