Page 291

Section 6-2

RS-232C Units INITIALIZE PARAMETERS

Initializes the parameters for the RS-232C Unit. Command Block 05

00

94

Class ID Service Code Destination node address

00

01

Instance ID

Response Block

No. of received bytes

Service code

Source node address

Initializes all parameters set for the RS-232C Unit and returns the initial values. RS-232C DATA SEND

Transmits data to the RS-232C Unit from the specified port. Command Block 10

00

94

Class ID Service Code Destination node address

00

××

64

151 bytes max.

Instance ID Attribute ID

Send data

Response Block

No. of received Service code bytes Source node address

Parameters Instance ID (Command) Specifies the port to which the data is being sent, in hexadecimal as follows: 02 Hex: Port 1 03 Hex: Port 2 Send Data (Command) Specifies the data to be sent from the specified port. Word data is sent from the leftmost bits to the rightmost bits as shown in the following diagram. Bit First word First word +1 First word +2

Note

276

(1) (3) (5)

(2) (4) (6)

1. When an odd number of bytes of data are sent, the last data will be set in the last word of the leftmost bits.

Page 292

Section 6-2

RS-232C Units

2. The number of bytes of data to be sent is specified when the parameters for the CMND(194) instruction (CV-series PLCs) or the IOWR instruction (C200HX/HG/HE PLCs) are set (No. of bytes of command data). It is not necessary to set this parameter for explicit messages. 3. Before using this command, be sure that the communications status Transmission Ready Flag (Port 1: bit 00, Port 2: bit 08), allocated in the Master’s IN Area is ON (transmission enabled). If the command is executed while the Flag is OFF (transmitting data), and error will occur (error code 02FF Hex). RS-232C RECEIVE DATA READ

Receives data from the specified RS-232C Unit port, and reads the data stored in the reception buffer. Depending on whether or not the header code and delimiter code are enabled or disabled, the data read is treated as shown in the following table. (When the delimiter header is disabled, the number of bytes set in No. of bytes per frame is read.) Header code Disabled

Delimiter code Disabled

Data read

The "No. of bytes per frame" is read from the RS-232C Unit's reception buffer, starting with the first word. First Second Third N bytes

Disabled

Enabled

Enabled

Disabled

Enabled

N bytes

Data from the RS-232C Unit's reception buffer is read, from the first word to the delimiter code. (There is no limit to the amount of data read.) First

Enabled

N bytes

Second

Third

Data from the RS-232C Unit's reception buffer is read, from the header code to the "No. of bytes per frame." In this case, the data before the header code is discarded First

Second

Third

N-1 bytes

N-1 bytes

N-1 bytes

Data from the RS-232C Unit's reception buffer is read, from the header code to the delimiter code. (There is no limit to the amount of data read.) In this case, the data before the header code is discarded. First

Second

Third

Note H: Header code, D: Delimiter code, N: No. of bytes per frame, Shaded area: trashed data. The above explanation is very brief, but if the number. of bytes received after the delimiter code is set, data after the delimiter code can also be read. Command Block 0E

00

94

Class ID Service Code Destination node address

00

××

64

Instance ID Attribute ID

277

Page 293

Section 6-2

RS-232C Units Response Block 1,024 bytes max. No. of received bytes

Service code

Receive data

Source node address

Parameters Instance ID (Command) Specifies the port that reads the reception buffer data in hexadecimal as follows: 02 Hex: Port 1 03 Hex: Port 2 Receive Data (Response) Stores the data read from the specified port’s reception buffer. The data is stored in words from the leftmost byte to the rightmost byte as shown in the following diagram. Bit (1) (3) (5)

First word First word +1 First word +2

Note

(2) (4) (6)

1. RS-232C ports 1 and 2 of the RS-232C Unit each have a reception buffer of 1,024 bytes, and up to a maximum of 1,024 bytes of data can be read from the Master at any given time. From an OMRON DeviceNet Master however, the maximum amount of data that can be read at one time is 152 bytes. Be sure to configure the data so that the 152-byte read data limit is not exceeded. 2. When data is read from an OMRON DeviceNet Master, the number of read bytes is stored as a CMND instruction (CV-series PLCs) or IOWR instruction (C200HX/HG/HE PLCs) parameter, so it will be requested. 3. When an odd number of bytes of data are sent, the last data will be set in the leftmost bits of the last word. 4. Before using this command, be sure that the communications status Received Flag (Port 1: bit 3, Port 2: bit 11) allocated in the Master’s IN Area is ON (data in the reception buffer). If the command is executed while the Flag is OFF (no data in the reception buffer), and error will occur (error code 1800 Hex).

PORT RESET

Resets the RS-232C Unit’s specified port. To change the parameter settings using the PARAMETER SET command, either reset the port using the PORT RESET command or restart the RS-232C Unit. Command Block 05

00

94

Class ID Service Code Destination node address

278

00

××

Instance ID

Page 294

Section 6-2

RS-232C Units Response Block

No. of received Service code bytes Source node address

Parameters Instance ID (Command) Specifies the port to be reset, in hexadecimal as follows: 02 Hex: Port 1 03 Hex: Port 2 Note

1. When the port is reset, the transmission buffer and the reception buffers are cleared and the port’s status is initialized. The parameter settings, however, are maintained. 2. When an error occurs at a port, find the cause of the error and then use this command to reset the port.

Error Response

If there is an error in the explicit command, the RS-232C Unit will return an error response as illustrated below. Response Block

No. of received bytes

Error code

Service code (94 Hex: fixed)

Source node address

Parameters No. of Received Bytes (Response) Always 0004 Hex. Source Node Address (Response) The node address of the node that sent the command is returned in hexadecimal. Error Code (Response) The error code is returned in double-byte (4-digit) hexadecimal, as shown in the following table. Error code 02FF Hex

Error details The RS-232C port is transmitting data and therefore busy.

Appropriate command RS-232C DATA SEND

08FF Hex

The service code, Class ID, and Instance ID are not supported.

All commands

09FF Hex

Data formatting error.

PARAMETER SET RS-232C DATA SEND

1800 Hex

There is no receive data at the RS-232C RECEIVE DATA READ RS-232C port. There is a parameter setting error between RS-232C devices.

279

Page 295

Section 6-2

RS-232C Units

6-2-8

Error code 1801 Hex

Error details An error frame was received from a RS-232C device.

Appropriate command RS-232C RECEIVE DATA READ

19FF Hex

Write not possible due to a hardware error etc.

PARAMETER SET

Using Explicit DeviceNet Messages

Using CMND to Change Settings (CS-series and CV-series)

The following example shows how to use the CMND instruction to change all the parameters of port 1 of the RS-232C Unit at once from the Master Unit in a CS-series or CV-series PLC.

Note If a CS-series PLC is being used, this example is applicable only when a CSseries Master Unit is mounted. Use the IOWR instruction when a C200HX/ HG/HE or C200HS Master Unit is mounted. In this case, refer to the DeviceNet Master Unit Operation Manual for details on using the IOWR instruction. For more detailed information on explicit messages, refer to the DeviceNet Master Unit Operation Manual. For information on the CMND instruction, refer to the PLC’s Operation Manual or Programming Manual. Example Conditions Master node address: 27 Slave network address: 2 Slave node address: 14 Example: Using the CMND Instruction

Command Words (S: First Command Word) Word

S+2

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex 0E 10 Slave node address: 14 PARAMETER SET command service code: 10 Hex 00 94 Class ID: 0094 Hex

S+3 S+4

00 01 64 06

S+5

00 00

S+6

02 03

S+7

00 00

S S+1

Instance ID: 0001 Hex ALL PARAMETER SET Attribute ID: 64 Hex, (8 bits, even parity, 1 stop bit): 06 Hex Header code, delimiter code, and flow control all enabled: 00 Hex, 1,200 bps: 00 Hex. Header code STX: 02 Hex, Delimiter code ETX: 03 Hex. No. of bytes after delimiter = 0 (00 Hex)

D: Response Words (D: First Response Word) Results are stored as shown in the following table. Word D D+1

280

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex 00 00 Response code (0000 Hex: Normal completion)

Page 296

Section 6-2

RS-232C Units

D+2

Word

Contents (Hex) Meaning 00 02 No. of received bytes (data length after D+3): 2 bytes

D+3

0E 90

Slave node address: 14 PARAMETER SET response service code: 90 Hex

Control Words (C: First Control Word) Word C C+1

Using CMND to Read Data (CS-series and CV-series)

Contents (Hex) Meaning 00 0F No. of bytes of command data: S (15 bytes of command data) 00 08 No. of bytes of response data: D (8 bytes of response data)

C+2 C+3

00 02 1B FE

C+4

00 00

C+5

00 64

Destination node network address: 2 Master’s node address: 27 Master’s Unit address: FE Hex Response returned, communications port No.: 0, No. of retries: 0 Response monitoring time: 10 s

The following example shows how to use the CMND instruction to read the RS-232C Unit’s port 1 reception data from the Master Unit in a CS-series or CV-series PLC. An OMRON DeviceNet Master can read a maximum of 152 bytes of data at a time.

Note If a CS-series PLC is being used, this example is applicable only when a CSseries Master Unit is mounted. Use the IOWR instruction when a C200HX/ HG/HE or C200HS Master Unit is mounted. In this case, refer to the DeviceNet Master Unit Operation Manual for details on using the IOWR instruction. Before using the RS-232C RECEIVE DATA READ command, be sure that the communications status Received Flag (Port 1: bit 3, Port 2: bit 11), allocated in the Master’s IN Area is ON. For more detailed information on explicit messages, refer to the DeviceNet Master Unit Operation Manual. For information on the CMND instruction, refer to the PLC’s Operation Manual or Programming Manual. Example Conditions Master node address: 27 Slave network address: 2 Slave node address: 14 Example: Using the CMND Instruction

Command Words (S: First Command Word) Word

S+2

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex 0E 0E Slave node address: 14 RS-232C RECEIVE DATA READ command service code: 0E Hex 00 94 Class ID: 0094 Hex

S+3 S+4

00 02 64 00

S S+1

Instance ID: Port 1 = 0002 Hex Attribute ID: 64 Hex

281

Page 297

Section 6-2

RS-232C Units D: Response Words (D: First Response Word) Results are stored as shown in the following table. Word

D+1

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex 00 00 Response code (0000 Hex: Normal completion)

D+2 D+3

00 xx 0E 8E

D+4

HH LL to to

D

No. of received bytes (data length after D+3) Slave node address: 14 RS-232C RECEIVE DATA READ response service code: 8E Hex The receive data read from RS-232C port 1 is stored in sequence from the leftmost bit to the rightmost bit.

Control Words (C: First Control Word) Word

C+1

Contents (Hex) Meaning 00 09 No. of bytes of command data: S (9 bytes of command data) 00 xx No. of bytes of response data: D

C+2 C+3

00 02 1B FE

Destination node network address: 2 Master’s node address: 27 Master’s Unit address: FE Hex

C+4

00 00

Response returned, communications port No.: 0, No. of retries: 0

C+5

00 64

Response monitoring time: 10 s

C

Using IOWR to Write Data (C200HX/HG/HE PLCs)

The following example shows how to use the IOWR instruction to change all the parameters of port 1 of the RS-232C Unit at once from the Master Unit (C200HX/HG/HE PLC). For more detailed information on explicit messages, refer to the Master Unit’s Operation Manual. For information on the IOWR instruction, refer to the SYSMAC C200HX/HG/HE PLCs Operation Manual. Example Conditions Master node address: 27 Master’s Unit address: 5 Slave node address: 14 Example: Using IOWR

C: Control Words (C: First Control Word) Word C

Contents (Hex) Meaning 1B FE Master’s node address: 27 Master’s Unit address: FE Hex

Source Words (S: First Source Word) Word S S+1

282

Contents (Hex) Meaning 82 07 Response storage words: DM2000 82 Hex: DM Area, 07D0 Hex: 2000 words (For more detail, refer to the PLC Operation D0 00 Manual.)

S+2

00 64

Response monitoring time: 10 s

S+3

00 0F

No. of bytes of command data: 15 bytes (No. of bytes from S+4 onwards.)

Page 298

Section 6-2

RS-232C Units

S+4

Word

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex

S+5

0E 10

Slave node address: 14 PARAMETER SET response service code: 10 Hex Class ID: 0094 Hex

S+6

00 94

S+7 S+8

00 01 64 06

Instance ID: For IR Area 1: 0001 Hex ALL PARAMETER SET Attribute ID: 64 Hex, (8 bits, even parity, 1 stop bit): 06 Hex.

S+9

06 00

Header code, delimiter code, and flow control all enabled: 00 Hex, 1,200 bps: 00 Hex.

S+10

02 03

Header code STX: 02 Hex, Delimiter code ETX: 03 Hex.

S+11

00 00

No. of bytes after delimiter = 0 (00 Hex)

D: Transmission Information (Destination Unit and Number of Words). Word D

Contents (Hex) Meaning 05 12 Master’s Unit address: 5, No. of words of command data: 12 words (specified in BCD) (No. of words from S onwards)

Response Storage Words Results are stored as shown in the following table. Word DM2000

Using IOWR to Read Data (C200HX/HG/HE PLCs)

DM2001

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex 00 00 Response code (0000 Hex: Normal completion)

DM2002

00 02

No. of received bytes (data length after DM2003): 2 bytes

DM2003

0E 90

Slave node address: 14 PARAMETER SET response service code: 90 Hex

The following example shows how to use the IOWR instruction to read the reception data of port 1 of the RS-232C Unit, from the Master Unit (C200HX/ HG/HE PLC). The maximum amount of data that can be read from an OMRON DeviceNet Master at one time is 152 bytes. Before using the RS-232C RECEIVE DATA READ command, be sure that the communications status Received Flag (Port 1: bit 03, Port 2: bit 11), allocated in the Master’s IN Area is ON. For more detailed information on explicit messages, refer to the Master Unit’s Operation Manual. For information on the IOWR instruction, refer to the SYSMAC C200HX/HG/HE PLCs Operation Manual. Example Conditions Master node address: 27 Master’s Unit address: 5 Slave node address: 14 Example: Using IOWR

283

Page 299

Section 6-2

RS-232C Units C: Control Words (C: First Control Word) Word C

Contents (Hex) Meaning 1B FE Master’s node address: 27 Master’s Unit address: FE Hex

Source Words (S: First Source Word) Word S S+1

Contents (Hex) Meaning 82 07 Response storage words: DM2000 82 Hex: DM Area, 07D0 Hex: 2000 words (For more detail, refer to the PLC Operation D0 00 Manual.)

S+2

00 64

Response monitoring time: 10 s

S+3

00 09

No. of bytes of command data: 9 bytes (No. of bytes from S+4 onwards.)

S+4

28 01

EXPLICIT MESSAGE SEND command code: 28 01 Hex

S+5

0E 0E

Slave node address: 14 RS-232C RECEIVE DATA READ response service code: 0E Hex

S+6 S+7

00 94 00 02

Class ID: 0094 Hex Instance ID: For port 1: 0002 Hex

S+8

64 00

Attribute ID: 64 Hex

D: Transmission Information (Destination Unit and Number of Words). Word D

Contents (Hex) Meaning 05 09 Master’s Unit address: 5, No. of words of command data: 9 words (specified in BCD) (No. of words from S onwards)

Response Storage Words Results are stored as shown in the following table. Word DM2000

284

DM2001

Contents (Hex) Meaning 28 01 EXPLICIT MESSAGE SEND command code: 28 01 Hex 00 00 Response code (0000 Hex: Normal completion)

DM2002 DM2003

00 xx 0E 8E

DM2004 on

HH LL...

No. of received bytes (data length after D+3) Slave node address: 14 RS-232C RECEIVE DATA READ response service code: 8E Hex The receive data read from RS-232C port 1 is stored in sequence from the leftmost bit to the rightmost bit.

Page 300

Section 6-2

RS-232C Units

6-2-9

Dimensions

Mounting holes Two, 4.2 dia. or M4

Unit: mm

6-2-10 Mounting in Control Panels Either of the following methods can be used to mount an RS-232C Unit in a control panel. Using Screws

Drill mounting holes in the control panel according to the dimensions provided for mounting holes in the dimensions diagrams and then secure the RS-232C Unit with M4 screws. The appropriate tightening torque is 0.6 to 0.98 N⋅m.

Using DIN Track

Mount the back of the RS-232C Unit to a 35-mm DIN Track. To mount the Unit, pull down on the mounting hook on the back of the Unit with a screwdriver, insert the DIN Track on the back of the Unit, and then secure the Unit to the DIN Track. When finished, secure all Slaves on both ends of the DIN Track with End Plates.

285