C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 301 to 310

Pages 301 to 310 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual

The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron DRT1-ID16

Page 301

Section 6-2

RS-232C Units Connecting End Plates

Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the following diagram, then hook the top of the End Plate as shown at (2). 2

1

End Plate

Note Always attach End Plate to both ends of Slaves connected to DIN Track. Mounting Direction

Unless specific restrictions are given for the Slave, it can be mounted in any direction. Any of the following directions are okay. PORT1

Vertical

PORT2

DRT1-232C2 RS232C UNIT

SD2

No.

No.

RD2

SD2

PORT2

SD1

NS

RD1 ERR

PORT1

MS

SD1

SD2

RD2

PORT1

PORT1

SD2 NS

RS232C UNIT

RD2

RD1

RS232C UNIT

MS

DRT1-232C2

ERR

DRT1-232C2

SD1

PORT2

No.

RD1

No.

NS

RD2

RS232C UNIT

SD1

DRT1-232C2

RD1

ERR

NS

ERR

MS

MS

PORT2

6-2-11 Wiring Internal Power Supply

The recommended Power Supply Units are as follows: • S82K-05024 (OMRON) or equivalent. • S82J-@524 (OMRON) or equivalent. Source 24 V DC –

+ + –

Internal power supply

Note

1. Always use crimp terminals for wiring. 2. Do not connect wires directly to the terminals. 3. Tighten terminal screws to a torque of 0.3 to 0.5 N • m. 4. Use the following M3 crimp terminals. 6.0 mm max.

286

6.0 mm max.

Page 302

Section 6-2

RS-232C Units RS-232C Connector Pin Arrangement (Same for Ports 1 and 2)

Pin No.

Symbol

Signal name

Signal direction RS-232C Unit ↔ External devices

1 2

--RD

Not used Receive data

--←

3 4

SD ---

Send data Not used

→ ---

5 6

SG ---

Signal ground Not used

-----

7 8

RS CS

Request send (See note.) Can send (See note.)

→ ←

9

---

Not used

---

Note The CS signal is always checked. Data will not be output if CS is not connected. Short-circuit the RS-CS signals when they are not used. A connection example using applicable connectors and recommended cables is provided below. Refer to the following explanation when creating cables. Applicable Connectors Plug: XM2D-0901 (OMRON, 9-pin female) or equivalent. Hood: XM2S-0913 (OMRON, 9-pin inch-pitch screws) or equivalent. Recommended Cables UL2464 AWG28 × 5P IFS-RVV-SB (UL product, Fujikura) AWG28 × 5P IFVV-SB (Non-UL products, Fujikura) UL2464-SB 5P × AWG28 (UL product, Hitachi) CO-MA-VV-SB 5P × AWG28 (Non-UL product, Hitachi) Connection Example The following diagram gives an connection example. Connection methods however, may differ depending on the connected devices, so refer to the connected device’s instruction manual for further information. Connecting an OMRON V500-R32@ Bar Code Reader RS-232C Unit end Bar Code Reader end Abbreviation Pin No. Pin No. Abbreviation -----

RS-232C interface

RS-232C interface

----------Hood metal

(9-pin)

(9-pin, male) Shield

287

Page 303

Section 6-2

RS-232C Units

6-2-12 RS-232C Unit Application Examples This section explains the procedure for using explicit messages with an RS232C Unit. The following system configuration example is used in this example. When explicit messages are used with an RS-232C Unit, the communications conditions for ports 1 and 2 on the RS-232C Unit can be set individually, and data can be read or written to the RS-232C Unit. C200HW-DRM21-V1 Master Unit (node address 00, unit number 0)

24-V DC power supply

C200HX PLC T-branch Tap Terminating Resistor T-branch Tap

Terminating Resistor T-branch Tap Port 1 Port 2 DRT1-232C2 RS-232C Unit (node address 08)

Bar Code Bar Code Reader 1 Reader 2

Setting Port Parameters

When IR 00000 (port 1 settings) or IR 00001 (port 2 settings) turns ON in the CPU Unit of the Master Unit, the RS-232C Unit’s port parameters will be set. For details on Bar Code Reader settings, refer to the Bar Code Reader’s Operation Manual. Set the port parameters as follows: • Port 1 Parameters Data length:

8 bits

Parity:

None

Stop bits:

1

Header code:

Disabled

Delimiter code:

Enabled

Flow control:

Enabled

Baud rate:

9,600 bps

Delimiter code CR code:

0D Hex

Number of bytes received after delimiter:0 • Port 2 Parameters

288

Data length:

7 bits

Parity:

Even

Stop bits:

2

Header code:

Enabled

Delimiter code:

Enabled

Flow control:

Disabled

Baud rate:

2,400 bps

Header code STX code:

02 Hex

Page 304

Section 6-2

RS-232C Units Delimiter code ETX code:

03 Hex

Number of bytes received after delimiter:0 If any of the port parameters are changed, the changed settings will become valid only when the port is reset or the RS-232C Unit is started up again. In the following programming example, the ports are reset after the parameters are set. Ladder Program 25315

Clears the DM Area words being used when the program starts.

BSET(71) #0000 DM0000 DM0999

Port 1 and 2 parameter setting common data

25315 MOV(21) #8200 DM0000 MOV(21)

Response storage word: DM 0100 (82 Hex: DM; 0064 Hex: word 100; 00 Hex: Word data)

#6400 DM0001

Response monitoring time: 10 s MOV(21) #0064 DM0002

Number of command data bytes: 15 bytes MOV(21) #000F DM0003

EXPLICIT MESSAGE SEND command code (FINS): 2801 Hex

MOV(21) #2801 DM0004

Slave node address: 08 PARAMETER SET command service code: 10 Hex

MOV(21) #0810 DM0005

Class ID: 94 Hex MOV(21) #0094 DM0006

Instance ID: 01 Hex MOV(21) #0001 DM0007

289

Page 305

Section 6-2

RS-232C Units

25315

Port 1 and 2 resetting common data

MOV(21) #8201 DM0400 MOV(21)

Response storage words: DM 0450 (82 Hex: DM; 01C2 Hex: word 450; 00 Hex: Word data)

#C200 DM0401

Response monitoring time: 10 s

MOV(21) #0064 DM0402

Number of command data bytes: 8 bytes

MOV(21) #0008 DM0403 MOV(21)

EXPLICIT MESSAGE SEND command code (FINS): 2801 Hex

#2801 DM0404 MOV(21)

Slave node address: 08 RS-232C PORT RESET command service code: 05 Hex

#0805 DM0405

Class ID: 94 Hex MOV(21) #0094 DM0406 25315 MOV(21) #6408

Port 1 parameter setting data ALL PARAMETER SET Attribute ID: 64 Hex 8-bit data length, no parity, 1 stop bit: 08 Hex

DM0020 MOV(21) #0103

Disabled header code, enabled delimiter code, enabled flow control: 01 Hex 9,600-bps baud rate: 03 Hex

DM0021 MOV(21)

Delimiter code: CR code (0D Hex) #000D DM0022

MOV(21)

Number of transmission bytes after delimiter: 0 #0000 DM0023

Port 2 parameter setting data

MOV(21) #6B03 DM0024 MOV((21) #0401 DM0025 MOV(21) #0203

ALL PARAMETER SET Attribute ID: 6B Hex 7-bit data length, even parity, 2 stop bits: 03 Hex Enabled header code, enabled delimiter code, disabled flow control: 04 Hex 2,400-bps baud rate: 01 Hex Header code: STX code (02 Hex) Delimiter code: ETX code (03 Hex)

DM0026

Number of transmission bytes after delimiter: 0

MOV(21) #0000 DM0027

290

Page 306

Section 6-2

RS-232C Units 00000

00001

Writing data from port 1 to command data area

XFER(70) #0004 DM0020 DM0008

When IR 00000 turns ON, data held at port 1 will be written to the command data area.

MOV(21) #0002 DM0407 DIFU(13) 00002 00000

IR 00002 turned ON for one cycle (as a differentiated bit). Writing data from port 2 to command data area

00001 XFER(70) #0004 DM0024 DM0008

When IR 00001 turns ON, data held at port 2 will be written to the command data area.

MOV(21) #0003 DM0407

IR 00003 turned ON for one cycle (as a differentiated bit).

DIFU(13) 00003 00002 MOV(21) #0001

00003

When IR 00002 or IR 00003 turns ON, the sequential processing control bit IR 03000 will turn ON.

030 03001 IOWR #00FE DM0400 #0008 25506 MOV(21) #0002

When IR 03001 turns ON, the port reset message will be transmitted. 00FE: Master's node address 00, Master's unit address FE Hex DM 0400: Command data storage words 0008 Hex: Master's unit number 00, 8 command data words (BCD) If the Equals Flag is OFF (error in writing to the Master), IR 03001 will be turned ON, and the data will be transmitted again.

030 25506 MOV(21) #0000 030 03000

10112 MOV(21) #0000 030 IOWR

If the Equals Flag is ON (writing to the Master has been completed normally), IR 03001 will be cleared (message transmission completed). When IR 03000 turns ON, the CPU Unit will check that IR 10112 (unit no. 0 Master's Message Communications Enabled Flag) is ON, and the ALL PARAMETER SET message is transmitted. 00FE: Master's node address 00, Master's unit address FE Hex DM 0000: Command data storage words

#00FE DM0000 #0012 25506 MOV(21) #0001 030 25506

0012 Hex: Master's unit number 00, 12 command data words (BCD) If the Equals Flag is OFF (error in writing to the Master), IR 03001 will be turned ON, and the data will be transmitted again. If the Equals Flag is ON (writing to the Master has been completed normally), IR 03001 will be turned ON (the port will be reset).

MOV(21) #0002 030 END(01)

291

Page 307

Section 6-2

RS-232C Units Note

1. When transmitting explicit messages from an OMRON Master Unit, specify 2 bytes each for the Class ID and the Instance ID. Set 1 byte as the Attribute ID for the parameter setting command. 2. The parameters that are set are held internally. 3. To enable the parameters that have been set, the RS-232C PORT RESET command has been used in the program examples. The parameters can also be enabled, however, by turning OFF the power to the RS-232C Unit and then turning it ON again. Responses The following responses will be stored if the parameters are set properly. PARAMETER SET Response Words DM 0100

Contents (Hex) 28 01

DM 0101

00 00

DM 0102

00 02

DM 0103

08 90

Meaning EXPLICIT MESSAGE SEND command code is 28 01 Hex. Response code is 0000 Hex (normal completion). Number of bytes received (data length from word DM 0103 onwards) is 2 bytes. Slave node address is 08. PARAMETER SET response service code is 90 Hex.

PORT RESET Response Words

Contents (Hex)

DM 0450

28 01

DM 0451

00 00

DM 0452

00 02

DM 0453

08 85

Meaning EXPLICIT MESSAGE SEND command code is 28 01 Hex. Response code is 0000 Hex (normal completion). Number of bytes received (data length from word DM 0453 onwards) is 2 bytes. Slave node address is 08. PORT RESET response service code is 85 Hex.

6-2-13 Reading RS-232C Unit Parameters With the following example, the port parameters that are set for the RS-232C Unit are all read for the port when IR 00004 (port 1) or IR 00005 (port 2) turns ON in the CPU Unit of the Master Unit. When the RS-232C Unit’s PARAMETER READ command is used, the parameters that are valid at that time will be read. After setting the parameters, the RS-232C Unit must be turned OFF and then ON again, or the ports must be reset for the new parameters to be enabled.

292

Page 308

Section 6-2

RS-232C Units Ladder Program 25315 BSET(71) #0000

Clears all DM Area words being used when the program starts.

M0000 DM0999 25315 MOV(21) #8200 DM0050 MOV(21)

Response storage words: DM 0150 (82 Hex: DM; 0096 Hex: word 150; 00 Hex: Word data)

#9600 DM0051 MOV(21)

Response monitoring time: 10 s #0064 DM0052

MOV(21)

Number of command data bytes: 9 bytes #0009 DM0053

MOV(21) #2801

EXPLICIT MESSAGE SEND command code (FINS): 2801 Hex

DM0054 MOV(21) #080E

Slave node address: 08 PARAMETER READ command service code: 0E Hex

DM0055

Class ID: 94 Hex

MOV(21) #0094 DM0056 MOV(21)

Instance ID: 01 Hex #0001 DM0057

00004

00005 MOV(21) #6400

When IR 00004 turns ON, the ALL PARAMETER READ command for port 1 and Attribute ID (64 Hex) are written as command data.

DM0058

00006

IR 00006 is turned ON for one cycle (as a differentiated bit).

#6B00

When IR 00005 turns ON, the ALL PARAMETER READ command for port 2 and Attribute ID (6B Hex) are written as command data.

DIFU(13)

00004

00005 MOV((21)

DM0058 DIFU(13) 00007

IR 00007 is turned ON for one cycle (as a differentiated bit). When IR 00006 or IR 00007 turns ON, the sequential processing control bit IR 03100 turns ON.

00006 MOV(21) #0001 031 00007

293

Page 309

Section 6-2

RS-232C Units 03100

10112 IOWR #00FE DM0050

When IR 03100 turns ON, the CPU Unit will check that IR 10112 (unit no. 0 Master's Message Communications Enabled Flag) is ON, and message transmission will start.

#0009 25506

00FE: Master's node address 00, Master's unit address FE Hex

MOV(21) #0000 031 25506 MOV(21) #0001 031

END(01)

DM 0050: Command data storage words 0009 Hex: Master's unit number 00, 9 command data words (BCD) If the Equals Flag is ON (writing to the Master has been completed normally), IR 03101 will be cleared (message transmission completed). If the Equals Flag is OFF (error in writing to the Master), IR 03101 will be turned ON, and the data will be transmitted again.

Note When transmitting explicit messages from an OMRON Master Unit, specify 2 bytes each for the Class ID and the Instance ID. Set 1 byte as the Attribute ID for the PARAMETER READ command. Response The following response will be stored if the parameters are read properly. Words DM 0150

Contents (Hex) 28 01

Meaning EXPLICIT MESSAGE SEND command code is 28 01 Hex.

DM 0151

00 00

Response code is 0000 Hex (normal completion).

DM 0152

00 08

Number of bytes received (data length from word DM 0153 onwards) is 8 bytes.

DM 0153

08 8E

Slave node address is 08. PARAMETER READ response service code is 8E Hex.

DM 0154 xx xx

DM 0155 xx xx

Leftmost byte: Setting for the data bit length Rightmost byte: Setting for the header code enable/disable Leftmost byte: Setting for the baud rate Rightmost byte: Setting for the header code

DM 0156 xx xx

Leftmost byte: Setting for the delimiter code Rightmost byte: Setting for the number of bytes/frames received after the delimiter

6-2-14 Reading Data Received by RS-232C Unit Ports In the following example, the data received by the Bar Code Reader is stored in the receive buffer of the RS-232C Unit and read to the Master Unit. If there is data already in the receive buffer of the RS-232C Unit, it will be read to the Master Unit. Response data from port 1 is stored in DM 0300 onwards, and response data from port 2 is stored in DM 0350 onwards. In the following program example, however, the data received is no more than 50 words (100 bytes).

294

Page 310

Section 6-2

RS-232C Units Ladder Program 25315 BSET(71) #0000

Clears all DM Area words being used when the program starts.

DM0000 DM0999 25315 MOV(21) #8201 DM0200

Setting data for executing the RECEIVE DATA READ command for port 1 Response storage word: DM 0300 (82 Hex: DM; 012C Hex: word 300; 00 Hex: Word data)

MOV(21) #2C00 DM0201

Response monitoring time: 10 s

MOV(21) #0064 DM0202

Number of command data bytes: 9 bytes

MOV(21) #0009 DM0203 MOV(21) #2801

EXPLICIT MESSAGE SEND command code (FINS): 2801 Hex

DM0204 MOV(21) #080E

Slave node address: 08 RECEIVE DATA READ command service code: 0E Hex

DM0205

Class ID: 94 Hex

MOV(21) #0094 DM0206

Port 1 RECEIVE DATA READ Instance ID: 02 Hex

MOV(21) #0002 DM0207

Attribute ID: 64 Hex

MOV(21) #6400 DM0208

295